EP65-12 - BB

VRLA Rechargeable Battery
Measures
EP65-12
Technology
Values
Innovation
APPLICATION
FEATURES
Absorbent Glass Mat technology for efficient gas recombination
Maintenance free(no water topping-up required)
No free acid(Non-spillable battery)
Can be used in any orientation(excluding used inverted)
The battery is designed for heavy duty cyclic application
Low self-discharge rate, lower than 3% capacity loss per month
UPS
Golf-Carts
Lawn Mowers
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
Operating Temperature Range
12 V
65Ah @ 20 hour rate F.V.(1.75V/cell)
22.8Kg(50.30lbs.)
B5 (Fitting M6 bolt & nut) I2 is optional
6m (Fully Charged )
650 A (5 sec.)
19.5 A
Charge 0oC~40oC(32oF~104oF)
Discharge -20oC~50oC(-4oF~122oF)
Storage. -20oC~40oC(-4oF~104oF)
Container Material
IEC 61056-1
JIS C 8702-1
GB/T 19639.1
Standard: ABS( UL 94-HB) EP65-12
Optional: Flame Retardant ABS(UL 94-V0) EP65-12FR
DIMENSION(mm/inch)
OUTER DIMENSIONS
TERMINAL TYPE
Length
M6x1.0
0.08)
174 2.0(6.86 0.08)
Container Height
174±2.0 (6.85±0.08)
2.0 (6.54
Total Height
174±2.0 (6.85±0.08)
2.0(0.08)
166
0.08)
7.0(0.28)
2.0 (13.78
6.3 (0.25)
19.0(0.75)
350
7.0(0.28)
21.0 (0.83)
166±2.0 (6.54±0.08)
[M6 BOLT]
[M6 BOLT & NUT]
Terminal Hardware Initial Torque: B5/ I2(5.5 Nm ± 5%)
Constant power discharge characteristics at 25 oC/77 oF
Discharge
Time
Terminal I2
Terminal B5
350±2.0 (13.78±0.08)
Width
Unit: W
10 Min
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
1.80V
1568
1298
808
455.0
192.0
132.4
73.90
39.00
1.75V
1700
1362
842
469.0
195.6
134.9
74.70
39.60
1.70V
1769
1408
862
478.0
198.3
136.0
75.20
39.90
1.65V
1833
1442
878
484.0
199.2
136.5
75.50
40.20
1.60V
1878
1465
886
488.0
200.2
136.5
76.00
40.50
F.V.
(V/cell)
Constant current discharge characteristics at 25 oC/77 oF
Discharge
Time
Unit: A
10 Min
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
1.80V
141.7
113.8
68.4
40.70
16.39
11.25
6.26
3.30
1.75V
155.7
119.4
71.0
42.30
16.60
11.36
6.35
3.37
1.70V
162.2
123.2
72.7
43.10
16.72
11.53
6.40
3.38
1.65V
166.7
126.7
73.6
43.70
16.78
11.57
6.42
3.39
1.60V
169.2
129.1
74.5
44.20
16.98
11.63
6.42
3.41
F.V.
(V/cell)
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
A/3
REV. Mar. 2013
Powered by