EP100-12 - BB

VRLA Rechargeable Battery
Measures
EP100-12
Technology
Values
Innovation
APPLICATION
FEATURES
Absorbent Glass Mat technology for efficient gas recombination
Maintenance free(no water topping-up required)
No free acid(Non-spillable battery)
Can be used in any orientation(excluding used inverted)
The battery is designed for heavy duty cyclic application
Flame-arrestor is installed to ensure safety
Carry handles for easy installation
Low self-discharge rate, lower than 3% capacity loss per month
UPS
Telecom
Golf-Carts
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
12 V
100Ah @ 20 hour rate F.V.(1.75V/cell)
40.0Kg(88.2lbs.)
B4 (Fitting M6 bolt & nut) I2 is optional
4.0m (Fully Charged )
800 A (5 sec.)
30 A
Charge 0oC~40oC(32oF~104oF)
Discharge -20oC~50oC(-4oF~122oF)
Storage. -20oC~40oC(-4oF~104oF)
Operating Temperature Range
Container Material
DIMENSION(mm/inch)
IEC 60896-21/22
JIS C 8704-2
GB/T 19638.2
Standard: ABS( UL 94-HB) EP100-12
Optional: Flame Retardant ABS(UL 94-V0) EP100-12FR
OUTER DIMENSIONS
TERMINAL TYPE
Length
407±2.0 (16.02±0.08)
Width
2 (6.81
0.08)
210 2 (8.27 0.08)
239 2 (9.41 0.08)
173
Total Height
239±2.0 (9.41±0.08)
2.0(0.08)
0.08)
7.0(0.28)
2 (16.02
M6x1.0
7.3(0.29)
26.5(1.04)
407
Container Height
210±2.0 (8.27±0.08)
10.0(0.39)
25.0(0.98)
173±2.0 (6.81±0.08)
[M6 BOLT]
[M6 BOLT & NUT]
Terminal Hardware Initial Torque: B4 ,I2(5.5Nm±5%)
o
o
Constant power discharge characteristics at 25 C/77 F
Discharge
Time
Terminal I2
Terminal B4
Unit: W
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
1.80V
1983
1193
691
291
201
112.3
58.7
1.75V
2076
1239
711
297
204
114.0
60.0
1.70V
2139
1266
724
300
206
114.6
60.3
1.65V
2189
1284
734
303
207
114.9
60.4
1.60V
2231
1297
741
304
207
114.9
60.4
F.V.
(V/cell)
o
o
Constant current discharge characteristics at 25 C/77 F
Discharge
Time
Unit: A
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
1.80V
178.7
105.6
58.07
24.25
16.75
9.36
4.89
1.75V
188.7
109.6
59.75
24.75
17.00
9.50
5.00
1.70V
194.5
112.0
60.84
25.00
17.17
9.55
5.03
1.65V
199.0
113.6
61.68
25.25
17.25
9.58
5.03
1.60V
202.8
114.8
62.27
25.33
17.25
9.58
5.03
F.V.
(V/cell)
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
A/2
REV. Mar. 2013
Powered by
B.B. Battery Co., Ltd.