BPL85-12 - BB

VRLA Rechargeable Battery
Measures
BPL85-12
Technology
Values
Innovation
APPLICATION
FEATURES
Maintenance free(no water topping-up required).
No free acid(Non-spillable battery).
Low self-discharge rate, lower than 3% capacity loss per month.
Can be used in any orientation(excluding used inverted).
Filtered with explosion proof filter.
Flame-arrestor is installed to ensure safety.
Carry handles for easy installation.
Absorbent Glass Mat technology for efficient gas recombination.
UPS
Telecom
Golf-carts
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
Operating Temperature Range
12 V
85.0Ah @ 20 hour rate F.V.(1.75V/cell)
31.2Kg(68.8lbs.)
B3 (Fitting M6 bolt & nut) I2 is optional
5.0m (Fully Charged )
800 A (5 sec.)
25.5 A
Charge 0oC~40oC(32oF~104oF)
Discharge -20oC~50oC(-4oF~122oF)
Storage. -20oC~40oC(-4oF~104oF)
DIMENSION(mm/inch)
OUTER DIMENSIONS
TERMINAL TYPE
Length
329±2.0 (12.95±0.08)
0.08)
172
2 (6.77
0.08)
M6x1.0
7.0(0.28)
2 (12.95
24.5(0.96)
11.0(0.43)
329
Total Height
B3:238±2.0 (9.37±0.08)
I2:218.5±2.0 (8.60±0.08)
[M6 BOLT & NUT]
[M6 BOLT]
Terminal Hardware Initial Torque: B3/ I2 (5.5Nm±5%)
o
o
Constant power discharge characteristics at 25 C/77 F
Discharge
Time
7.3(0.29)
25.0(0.98)
(6.77±0.08)
Container Height
215±2.0 (8.46±0.08)
Terminal I2
Terminal B3
215 2 (8.46 0.08)
238 2 (9.37 0.08)
Width
172±2.0
IEC 60896-21/22
JIS C 8704-2
GB/T 19638.2
Standard: ABS( UL 94-HB) BPL85-12
Optional: Flame Retardant ABS(UL 94-V0) BPL85-12FR
2.0(0.08)
Container Material
Unit: W
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
1.80V
1586
1074
585.8
246.6
170.9
95.24
49.84
1.75V
1683
1115
604.0
251.8
173.5
96.67
51.00
1.70V
1761
1139
614.5
254.4
174.2
97.19
51.14
1.65V
1802
1156
622.3
255.7
174.8
97.45
51.27
1.60V
1839
1167
628.8
257.0
174.8
97.45
51.27
F.V.
(V/cell)
o
o
Constant current discharge characteristics at 25 C/77 F
Discharge
Time
Unit: A
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
1.80V
143
95.1
49.2
20.5
14.2
7.94
4.15
1.75V
153
98.6
50.8
21.0
14.5
8.06
4.25
1.70V
160
100.8
51.6
21.2
14.5
8.10
4.26
1.65V
164
102.3
52.3
21.3
14.6
8.12
4.27
1.60V
167
103.3
52.8
21.4
14.6
8.12
4.27
F.V.
(V/cell)
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
A/4
REV. Mar. 2013