BP120-12

VRLA Rechargeable Battery
Measures
BP120-12
Technology
Values
Innovation
APPLICATION
FEATURES
Maintenance free(no water topping-up required).
No free acid(Non-spillable battery).
Low self-discharge rate, lower than 3% capacity loss per month.
Can be used in any orientation(excluding used inverted).
Flame-arrestor is installed to ensure safety.
Carry handles for easy installation.
Absorbent Glass Mat technology for efficient gas recombination.
UPS
Telecom
Golf-Carts
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
12 V
120Ah @ 20 hour rate F.V.(1.75V/cell)
39.5Kg(87.1lbs.)
B4 (Fitting M6 bolt & nut) I2 is optional
4m (Fully Charged )
800 A (5 sec.)
36 A
Charge 0oC~40oC(32oF~104oF)
Discharge -20oC~50oC(-4oF~122oF)
Storage. -20oC~40oC(-4oF~104oF)
Operating Temperature Range
Standard: ABS( UL 94-HB) BP120-12
Optional: Flame Retardant ABS(UL 94-V0) BP120-12FR
Container Material
DIMENSION(mm/inch)
IEC 60896-21/22
JIS C 8704-2
GB/T 19638.2
OUTER DIMENSIONS
TERMINAL TYPE
Length
0.08)
210 2 (8.27 0.08)
239 2 (9.41 0.08)
Container Height
210±2.0 (8.27±0.08)
2 (6.81
Total Height
239±2.0 (9.41±0.08)
[M6 BOLT & NUT]
2.0(0.08)
173
0.08)
7.0(0.28)
2 (16.02
M6x1.0
7.3(0.29)
26.5(1.04)
407
10.0(0.39)
25.0(0.98)
173±2.0 (6.81±0.08)
[M6 BOLT]
Terminal Hardware Initial Torque: B4 ,I2(5.5Nm±5%)
Constant power discharge characteristics at 25 oC/77 oF
Discharge
Time
Terminal I2
Terminal B4
407±2.0 (16.02±0.08)
Width
Unit: W
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
1.80V
2346
1523
873.4
349.8
241.2
134.8
70.92
1.75V
2454
1581
899.6
356.8
244.8
136.8
72.00
1.70V
2530
1617
915.7
360.0
246.1
137.5
72.36
1.65V
2588
1640
926.7
362.5
247.2
137.9
72.58
1.60V
2640
1656
936.0
364.7
247.7
137.9
72.58
F.V.
(V/cell)
o
o
Constant current discharge characteristics at 25 C/77 F
Discharge
Time
Unit: A
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
1.80V
204
129
73.4
29.1
20.10
11.23
5.91
1.75V
213
134
75.6
29.7
20.40
11.40
6.00
1.70V
220
137
77.0
30.0
20.51
11.46
6.03
1.65V
225
139
77.9
30.2
20.60
11.49
6.05
1.60V
230
140
78.7
30.4
20.64
11.49
6.05
F.V.
(V/cell)
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
A/3
REV. Mar. 2013
Powered by