Field wiring left

Marshalling Solutions - Interface Modules
Passive Interface Unit
32 pole, disconnect interface
• CLAMSHELL style connection on module module (Field wiring left)
• Test points for HART monitoring
• Disconnects for each channel
• Reduce Cabinet Space
• Field wiring termination from LEFT side
• 16 channels
• Feed through connections with disconnects
• For analog signals
• 32 points
• 4 additional terminations for power/
return connections
• Honeywell C300 IOTAs
– CC-TAOX01/TAOX11/TAON01/
TAON1: CC-TDIL01/TDIL11
(NEED 2)
Technical data
Connection data
Process side
Type
Torque
Control side
Type
Rated data
Rated voltage
Max. current per channel
Operating temperature
Storage temperature
General Features
LED status indicator per channel
Disconnection per channel
Voltage measuring test points
Current measuring test points
Fuse via channel
Supply voltage LED status
Power supply fuse
Terminal wire size
Insulation stripping length
Approvals
Standards
Dimensions
Length x width x height (inches / mm)
Screw connection
LP2N terminal
4.4 in-lbs (0.5Nm)
Plug connection
CLAMSHELL SLD 32-Pole
50V
1A
0°C to +50°C
0°C to +50°C
No
Yes
Yes
No
No
No
No
AWG 26 …12
6mm
cURus (E141197)
5.1 x 4.4 x 3.6 / 129.5 x 111.8 x 91.5
Note
Ordering data
Model
32-pole, disconnect interface module
(Field wiring left): Screw connection
Note
Accessories
Optional Cables
Note
12
Qty
1
Part No.
6720000764
Disconnects located on terminals 1,3,5….29,31
Qty
MS - C32x - C32x - Lxx - xxx (a clam1
shell 32-pole to clamshell 32-pole) OR
MS - C2+xxx - C2+xxx - Lxx - xxx (a
1
clamshell 32-pole + 4-pole each end)
Required quantity based on Honeywell IOTA used
DWG No.
1101221
1101222