Marshalling Solutions - Interface Modules Passive Interface Unit 32 pole, disconnect interface • CLAMSHELL style connection on module module (Field wiring left) • Test points for HART monitoring • Disconnects for each channel • Reduce Cabinet Space • Field wiring termination from LEFT side • 16 channels • Feed through connections with disconnects • For analog signals • 32 points • 4 additional terminations for power/ return connections • Honeywell C300 IOTAs – CC-TAOX01/TAOX11/TAON01/ TAON1: CC-TDIL01/TDIL11 (NEED 2) Technical data Connection data Process side Type Torque Control side Type Rated data Rated voltage Max. current per channel Operating temperature Storage temperature General Features LED status indicator per channel Disconnection per channel Voltage measuring test points Current measuring test points Fuse via channel Supply voltage LED status Power supply fuse Terminal wire size Insulation stripping length Approvals Standards Dimensions Length x width x height (inches / mm) Screw connection LP2N terminal 4.4 in-lbs (0.5Nm) Plug connection CLAMSHELL SLD 32-Pole 50V 1A 0°C to +50°C 0°C to +50°C No Yes Yes No No No No AWG 26 …12 6mm cURus (E141197) 5.1 x 4.4 x 3.6 / 129.5 x 111.8 x 91.5 Note Ordering data Model 32-pole, disconnect interface module (Field wiring left): Screw connection Note Accessories Optional Cables Note 12 Qty 1 Part No. 6720000764 Disconnects located on terminals 1,3,5….29,31 Qty MS - C32x - C32x - Lxx - xxx (a clam1 shell 32-pole to clamshell 32-pole) OR MS - C2+xxx - C2+xxx - Lxx - xxx (a 1 clamshell 32-pole + 4-pole each end) Required quantity based on Honeywell IOTA used DWG No. 1101221 1101222