MAA150T

Thru Mount Thermoelectric Air Conditioners
MAA150T-12/24
The MAA150T-12/24 Thermoelectric air conditioners
are designed for electronic cabinets and environmental chambers. They can cool to 72˚F below ambient or maintain ambient temperatures while removing up to 150 BTU/Hr (@ 77˚F ambient). These models are available in 12 or 24 VDC configurations.
Because there is no air exchanged between the cabinet and the ambient, the MAA150T-12/24 series are
ideal for NEMA 12 requirements. These air conditioners are virtually maintenance-free, with no filters
to change, and they can be mounted in any orientation, offering design flexibility with solid-state reliability.
Wiring Schematic (Power Connector)
Model MAA150T-12
4
3
2
1
Model Number Nomenclature
M A A 150 T
–
__
Voltage: 12 = 12 VDC
24 = 24 VDC
Thru Mount
Capacity (BTU/Hr)
Ambient Side (Air)
Cabinet Side (Air)
Position
Description
1
TEC +
2
TEC
3
FAN +
4
FAN
-
MELCOR
Specifications:
Model:
Capacity
Input Voltage
Max. Ambient Temp.**
Current (Running)
Weight
Rating Maintained
Overall Dimensions
MAA150T-12
150 BTU/Hr (44 Watts)
12 VDC
140˚F / 60˚C
9.5 amps
4.4 lbs. (2.0 kg)
NEMA 12
8.0” H x 5.5” W x 6.4” D
203mm x 140mm x 165mm
MAA150T-24
150 BTU/Hr (44 Watts)
24VDC
140˚F / 60˚C
4.5 amps
4.4 lbs. (2.0 kg)
NEMA 12
8.0” H x 5.5” W x 6.4” D
203mm x 140mm x 165mm
** Consult MELCOR for higher ambient temperature.
18
1040 Spruce Street • Trenton, NJ 08648 • TEL: 609-393-4178 • FAX: 609-393-9461 • WEB: www.melcor.com • E-Mail: [email protected]
Thru Mount Thermoelectric Air Conditioners
Performance Curve: MAA150T-12/24 Series
Q Required (Watts)
6
12
18
23
29
35
41
47
53
0
Important:
0
77˚F (25˚C)
Ambient
-18
-10
-20
-36
140˚F (60˚C)
Ambient
-30
-54
-40
-72
-50
-90
200
0
20
40
60
80
100
120
Q Required (BTU/HR)
140
160
180
T (˚F)
T (˚C)
59
18
10
The air conditioner performance curves
are dependent upon active
and passive heat loads. To calculate
passive cabinet heat gain, see the
instructions on pages 6 and 7.
For assistance contact MELCOR.
T = Tmax Cabinet - Tmax Ambient
Installation Cutout
Dimensional Drawing
Inches (mm)
1040 Spruce Street • Trenton, NJ 08648 • TEL: 609-393-4178 • FAX: 609-393-9461 • WEB: www.melcor.com • E-Mail: [email protected]