XTV121000 Spec Sheet_2008-(533.79K

Powered by
XTV121000
12V 100Ah
XTV 121000 is a general battery up to 12 years expected life in
standby service or more than 400 cycles at 100% discharge in
cycle service . XTV!has a wider operating temperature range,
which makes them more suitable for the systems in harsh
conditions.
Specification
Cells Per Unit
Voltage Per Unit
Capacity
Weight
Maximum Discharge Current
Internal Resistance
Operating Temperature Range
6
12
100 A h @ 10hr-rate to 1.80V per cell @25 (77 )
Approx. 32 kg(70.55 lbs)
800A(5sec)
Approx. 6.5m
Discharge: -20 ~50
(-4 ~122 )
(-4 ~122 )
Charge: -20 ~50
(5 ~104 )
Storage: -15 ~40
3 (77
5 )
Nominal Operating Temperature Range 25
13.5 to 13.8 VDC/unit Average at 25 (77 )
Float Charging Voltage
Recommended Maximum Charging
30A
Current Limit
14.4 to 15.0 VDC/unit Average at 25 (77 )
Equalization and Cycle Service
Self Discharge
CSB Batteries can be stored for more than 6 months at
25 (77 ). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
Terminal
I2-Thread lead alloy recessed terminal to accept M6 bolt
PP (UL 94-V0/File E50955)*Flammability resistance
Container Material
of (UL 94-HB/File E216959) can be available upon request.
Dimensions :
Unit: mm (inch)
Overall Height (H)
216.3±2.5 (3.94±0.1)
Container height (h)
213.8±2.5 (8.39±0.1)
Length (L)
342±2.5 (13.46±0.1)
Constant Current Discharge Characteristics
F.V/Time
1.60V
1.67V
1.70V
1.75V
1.80V
1.85V
5MIN
369
326
304
270
245
202
10MIN
255
238
228
210
190
170
15MIN
195
186
181
173
159
139
30MIN
118
116
114
109
103
94.3
1HR
70.7
69.2
68.4
66.5
64.0
59.7
2HR
42.0
41.0
40.7
39.5
37.8
35.4
3HR
28.9
28.6
28.2
27.5
27.0
25.5
5MIN
3454
3194
3085
2893
2549
2169
10MIN
2578
2451
2379
2232
2072
1842
15MIN
2075
2014
1991
1867
1710
1507
30MIN
1284
1270
1258
1218
1161
1078
1HR
784
773
771
755
728
686
2HR
467
461
457
446
428
406
3HR
331
328
325
317
310
295
Unit:A (25
4HR
22.1
22.0
21.8
21.4
21.1
19.9
Constant Power Discharge Characteristics
F.V/Time
1.60V
1.67V
1.70V
1.75V
1.80V
1.85V
CSB-manufactured
batteries are ULrecognized components
under UL924 and
UL1989.
CSB is also certified by
ISO 9001 and
ISO 14001.
5HR
18.3
18.1
18.0
17.8
17.4
16.6
Unit:W (25
4HR
259
255
254
250
243
231
5HR
213
211
210
208
202
193
Width (W)
170±2 (6.69±0.08)
,77
8HR
12.2
12.1
12.0
11.8
11.6
11.2
,77
8HR
143
142
141
139
137
132
)
10HR
10.2
10.0
9.92
9.79
9.70
9.24
20HR
5.29
5.26
5.24
5.18
5.08
4.89
)
10HR
119
118
117
116
115
110
20HR
62.0
61.3
61.0
60.7
59.7
58.0
RA: 0808
XTV121000
140
0.20
2.60
120
0.17
2.40
100
0.14
2.20
80
0.11
2.00
60
0.08
1.80
40
0.05
1.60
20
0.02
1.40
12V 100Ah
)Ratio
13.65V
0
140
0.20
2.60
120
0.17
2.40
100
0.14
2.20
80
0.11
2.00
60
0.08
1.80
40
0.05
1.60
20
0.02
1.40
0
Application
(2.275V/Cell)
4
8
12
16
20
24
68
)Ratio
4
8
12
16
Charge Voltage(V/Cell)
Set Point
Allowable Range
Cycle Use
Temperature
25 (77 )
2.45
2.40~2.50
Standby
25 (77 )
2.275
2.25~2.30
20
24
Max.Charge Current
Final Discharge
Voltage V/Cell
1.75
1.70
1.60
1.30
0.3C
Discharge
Current(A)
0.2C>(A)
0.2C<(A)<0.5C
0.5C<(A)<1.0C
(A)>1.0C
Tel: +886-2-2555-5600
Fax: +886-2-2555-3300
CSB BATTERY TECHNOLOGIESȞBEIJINGȟCO., LTD.
CSB BATTERY LOGISTIC ( SHANGHAI ) CO., LTD.
BEIJING OFFICE
Tel : +86-10-59621300/59621301/59621302/59621303
Fax : +86-10-59621304
mail : [email protected]
SHENZHEN OFFICE
Tel : +86-755-8831-6488/6396/16356
Fax : +86-755-8831-6548
mail : [email protected]
E-mail: [email protected]