Powered by UPS12460 UPS 12460 is specially designed for high efficient discharge application. Its characteristics are high energy density, small footprint and high discharge efficiency. It can be used for more than 260 cycles at 100% discharge in cycle service, up to 5 years in standby service. Specification Cells Per Unit Voltage Per Unit 6 12 460W @ 5min-rate to Watt(1.60V)/pcs @25 Capacity Weight Maximum Discharge Current Internal Resistance Operating Temperature Range Nominal Operating Temperature Range Float Charging Voltage Recommended Maximum Charging Current Limit Equalization and Cycle Service Self Discharge Terminal Container Material Approx. 2.50 kg(5.51 lbs) 130A(5sec) Approx. 18.0m Discharge: -15 ~50 ( 5 ~122 ) Charge: -15 ~40 ( 5 ~104 ) Storage: -15 ~40 ( 5 ~104 ) 25 3 (77 5 ) 13.5 to 13.8 VDC/unit Average at 25 3.60A (77 ) TUV Asia Pacific Ltd. Taiwan Branch (77 ) TUV Asia Pacific Ltd. Taiwan Branch 14.4 to 15.0 VDC/unit Average at 25 (77 ) CSB Batteries can be stored for more than 6 months at 25 (77 ). Please charge batteries before using. For higher temperatures the time interval will be shorter. F2-Faston Tab 250 ABS(UL 94-HB) & Flammability resistance of (UL 94-V0) can be available upon request. Dimensions : Overall Height (H) 98.3±1.0(3.87±0.04) Unit: mm (inch) Container height (h) 94.0±1.0 (3.70±0.04) CSB-manufactured VRLA (Absorbent Glass Mat type) batteries are UL-recognized components under UL1989. CSB is also certified by ISO 9001 and ISO 14001. Length (L) 151.0±2.0 (5.95±0.08) Width (W) 65.0±1.0 (2.56±0.04) (http://www.csb-battery.com) The system of manufacturer was certified by TUV CERT according to ISO 9001,ISO 14001. Constant Current Discharge Characteristics F.V/Time 1.60V 1.67V 1.70V 1.75V 1.80V 1.85V 2MIN 77.2 3MIN 63.0 4MIN 52.7 5MIN 44.9 6MIN 39.7 7MIN 35.6 8MIN 32.3 10MIN 27.3 Unit:A (25 15MIN 19.9 20MIN 15.9 ,77 30MIN 11.57 ) 60MIN 6.65 90MIN 4.80 69.5 58.9 50.0 43.4 38.7 34.7 31.7 26.9 19.7 15.7 11.49 6.63 4.78 66.0 56.9 48.6 42.4 37.9 34.0 31.1 26.5 19.6 15.6 11.44 6.60 4.75 60.5 52.1 45.1 39.9 35.6 32.4 29.8 25.4 19.0 15.3 11.28 6.52 4.72 53.8 46.5 41.1 36.5 33.0 30.2 27.8 24.0 18.2 14.7 10.95 6.38 4.62 46.3 40.5 36.0 32.1 29.4 27.0 24.9 21.8 16.8 13.8 10.42 6.12 4.43 Constant Power Discharge Characteristics Unit:W (25 ,77 ) F.V/Time 1.60V 2MIN 710 3MIN 606 4MIN 520 5MIN 460 6MIN 412 7MIN 373 8MIN 343 10MIN 296 15MIN 224 20MIN 180 30MIN 133 60MIN 77.3 90MIN 56.4 1.67V 673 579 500 444 400 367 338 291 221 178 132 77.0 56.0 1.70V 650 561 489 435 394 362 334 288 220 178 132 76.7 56.0 1.75V 605 523 462 414 378 349 321 280 215 175 130.4 76.4 55.7 1.80V 555 482 429 387 356 327 303 266 207 168 127.5 75.1 54.7 1.85V 486 432 387 355 324 297 276 244 189 158 121.5 72.2 52.8 Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version. RA1406 UPS 12460 140 0.049 2.60 120 0.042 2.40 100 0.035 2.20 80 0.028 2.00 60 0.021 1.80 40 0.014 1.60 20 0.007 1.40 )Ratio 1PWx15Min 1PWx7.5Min 0.025PA 0 140 0.049 2.60 120 0.042 2.40 100 0.035 2.20 80 0.028 2.00 60 0.021 1.80 40 0.014 1.60 20 0.007 1.40 3 6 9 12 15 18 68 )Ratio 1PWx15Min 1PWx7.5Min 14.70V 2.45V 0.025PA 1PW 0 3 6 9 12 15 0.62PW 0.47PW 0.25PW 0.16PW 18 Charging Procedures Application Cycle Use Standby Charge Voltage(V/Cell) Temperature 25 (77 ) Set Point Allowable Range 2.45 2.40~2.50 25 (77 ) 2.275 2.25~2.30 Max.Charge Current Final Discharge Voltage V/Cell 1.75 1.70 1.60 1.30 0.1PA Discharge Power(W) 0.1P>(W) 0.1P (W)<0.25P 0.25P (W)<1.0P (W) 1.0P P: For single cell wattage at 15 minute rate to 1.67V per cell. EUROPE OFFICE Tel: +31(0)180 418 140 Fax: +31(0)180 418 327 E-mail: [email protected] Tel: +886-2-2880-5600 Fax: +886-2-2888-3300 +86-21-5064-1046 E-mail: [email protected] +86-10-5820-5336/5338 +86-10-58203053 Tel: +86-755-8831-6488/6396/16356 Fax: +86-755-8831-6548 E-mail: [email protected]