Operating instructions G3G140AW0512

G3G140-AW05-12
Operating instructions
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2
D-74673 Mulfingen
Phone +49 (0) 7938 81-0
Fax +49 (0) 7938 81-110
[email protected]
www.ebmpapst.com
1. SAFETY REGULATIONS AND NOTES
Please read these operating instructions carefully before starting to work
with the device. Observe the following warnings to prevent malfunctions
or physical damage to both property and people.
These operating instructions are to be regarded as part of this device.
If the device is sold or transferred, the operating instructions must
accompany it.
These operating instructions may be duplicated and forwarded for
information about potential dangers and their prevention.
Translation of the original operating instructions
CONTENTS
1. SAFETY REGULATIONS AND NOTES
1
1.1 Levels of hazard warnings
1
1.2 Staff qualification
1
1.3 Basic safety rules
1
1.4 Electrical voltage
1
1.5 Safety and protective functions
2
1.6 Electromagnetic radiation
2
1.7 Mechanical movement
2
1.8 Emission
2
1.9 Hot surface
2
1.10 Storage
2
1.11 Disposal
2
2. PROPER USE
3
3. TECHNICAL DATA
4
3.1 Product drawing
4
3.2 Nominal data
5
3.3 Technical features
5
3.4 Mounting data
5
3.5 Transport and storage conditions
5
3.6 Electromagnetic compatibility
5
4. CONNECTION AND START-UP
6
4.1 Connecting the mechanical system
6
4.2 Connecting the electrical system
6
4.3 Connection of the cables
6
4.4 Connection screen
7
4.5 Checking the connections
8
4.6 Switch on device
8
4.7 Switching off the device
8
5. INTEGRATED PROTECTIVE FUNCTIONS
8
6. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES
9
6.1 Cleaning
9
6.2 Safety test
9
1.1 Levels of hazard warnings
These operating instructions use the following hazard levels to indicate
potentially hazardous situations and important safety regulations:
DANGER
Indicates an imminently hazardous situation which, if not
avoided, will result in death or serious injury. Compliance with
the measures is mandatory.
WARNING
Indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury. Exercise extreme
caution while working.
CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury or damage of property.
NOTE
A potentially harmful situation can occur and, if not avoided, can
lead to property damage.
1.2 Staff qualification
Only specialised electrical personnel may install the device, perform the
test run and work on the electrical system.
Only trained and authorised specialist personnel are permitted to
transport, unpack, assemble, operate or maintain the device, or to use it
in any other manner.
1.3 Basic safety rules
Any safety hazards stemming from the device must be re-evaluated
once it is installed in the end device.
Observe the following when working on the unit:
; Do not make any modifications, additions or conversions to the
device without the approval of ebm-papst.
1.4 Electrical voltage
; Check the electrical equipment of the device at regular intervals, refer
to chapter 6.2 Safety test.
; Replace loose connections and defective cables immediately.
DANGER
Electrical load on the device
Risk of electric shock
→ Stand on a rubber mat if you are working on an electrically
charged device.
WARNING
Terminals and connections have voltage even with a
unit that is shut off
Electric shock
→ Wait five minutes after disconnecting the voltage at all poles
before opening the device.
Item no. 50889-5-9970 · Revision 78380 · Release 2013-06-03 · Page 1 / 10
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
G3G140-AW05-12
Operating instructions
CAUTION
In the event of failure, there is electric voltage at the
rotor and impeller
The rotor and impeller are base insulated.
→ Do not touch the rotor and impeller once they are installed.
→ Protect long hair by wearing a cap.
1.8 Emission
CAUTION
If control voltage is applied or a speed setpoint is stored,
the motor automatically restarts, e.g. after a power failure.
Danger of injury
WARNING
Depending on the installation and operating conditions,
a sound pressure level greater than 70 dB(A) may arise.
Danger of noise-induced hearing loss
→ Keep out of the danger zone of the device.
→ Take appropriate technical safety measures.
→ When working on the device, switch off the mains
supply voltage and secure the latter from being switched on
again.
→ Protect operating personnel with appropriate safety
equipment, e.g. hearing protection.
→ Wait until the device stops.
→ After working on the device, remove any used tools or
other objects from the device.
1.5 Safety and protective functions
DANGER
Missing safety device and non-functioning safety device
If there is no safety device, you could be seriously injured, for
example by reaching into the running device with your hands.
→ Also observe the requirements of local agencies.
1.9 Hot surface
CAUTION
High temperature at the electronics enclosure
Danger of burn injuries
→ Ensure that sufficient protection against accidental contact is
provided.
1.10 Storage
→ Operate the device only with a fixed and isolating safety
protection and a fixed guard grille. The guard must withstand
the kinetic energy of a fan blade detaching at maximum
speed.
; Store the device, partially or fully assembled, in a dry and
weatherproof manner in the original packing in a clean environment.
→ The device is a built-in component. You, the owner/
operator, are responsible for providing adequate protection for
the device.
; We recommend storing the device for a maximum up to one year to
guarantee proper operation and longest possible service life.
→ Shut down the device immediately if you detect a
missing or ineffective protective feature.
1.6 Electromagnetic radiation
Interference from electromagnetic radiation is possible, e.g. in conjunction
with open and closed-loop control devices.
If unacceptable emission intensities occur when the fan is installed,
appropriate shielding measures have to be taken by the user.
Translation of the original operating instructions
→ Do not wear any loose clothing or jewellery while working
on rotating parts.
; Protect the device from environmental impacts and dirt until the final
installation.
; Even devices explicitly suited for outdoor use are to be stored as
described prior to being commissioned.
; Maintain the storage temperature, see
chapter 3.5 Transport and storage conditions.
1.11 Disposal
When disposing of the device, please comply with all relevant
requirements and regulations applicable in your country.
NOTE
Electrical or electromagnetic interferences after
integrating the device in installations on the customer's
side.
→ Verify that the entire setup is EMC compliant.
1.7 Mechanical movement
DANGER
Rotating device
Body parts that come into contact with the rotor and impeller
can be injured.
→ Secure the device against accidental contact.
→ Before working on the system/machine, wait until all
parts have come to a standstill.
WARNING
Rotating device
Long hair, loose items of clothing and jewellery could become
entangled and pulled into the device. You could be injured.
Item no. 50889-5-9970 · Revision 78380 · Release 2013-06-03 · Page 2 / 10
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
G3G140-AW05-12
Operating instructions
2. PROPER USE
The device is exclusively designed as a built-in device for moving air
according to its technical data.
Any other or secondary use is deemed improper and constitutes a
misuse of the device.
Installations on the customer's side must meet the mechanical, thermal
and service life-related stresses that can occur.
Proper use also includes:
●
Moving air with a density of 1.2 kg/m³.
●
Using the device in accordance with the permitted ambient
temperature, see chapter 3.5 Transport and storage conditions and
chapter 3.2 Nominal data.
●
Operating the device with all protective features in place.
●
Minding the operating instructions.
Improper use
Using the device in the following ways is particularly prohibited and
may cause hazards:
Operating the device with an imbalance, e.g. caused by dirt deposits
or icing.
●
Moving air that contains abrasive particles.
●
Moving highly corrosive air, e.g. salt spray mist. Exceptions are
devices that are intended for salt spray mist and protected accordingly.
●
Moving air that contains dust pollution, e.g. suctioning off saw dust.
●
Operating the device close to flammable materials or components.
●
Operating the device in an explosive atmosphere.
●
Using the device as a safety component or for taking on safetyrelated functions.
●
Operation with completely or partially disassembled or modified
protective features.
●
In addition, all application options that are not listed under proper use.
Translation of the original operating instructions
●
Item no. 50889-5-9970 · Revision 78380 · Release 2013-06-03 · Page 3 / 10
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
G3G140-AW05-12
Operating instructions
3. TECHNICAL DATA
3.1 Product drawing
All measures have the unit mm.
Connection line PVC 3G 0.5 mm², 3x brass lead tips crimped
Connection line PVC 4 x 0.5 mm²; 4 x brass lead tips crimped
Translation of the original operating instructions
1
2
Item no. 50889-5-9970 · Revision 78380 · Release 2013-06-03 · Page 4 / 10
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
Operating instructions
G3G140-AW05-12
3.2 Nominal data
Motor
M3G055-CF
Phase
Nominal voltage / VAC
Frequency / Hz
1~
230
50/60
Type of data definition
Speed / min-1
Power input / W
Current draw / A
Min. ambient temperature
/ °C
Max. ambient temperature
/ °C
ml
2300
67
0.5
-25
60
ml = Max. load · me = Max. efficiency · fa = Running at free air
cs = Customer specs · cu = Customer unit
Subject to alterations
3.3 Technical features
Mass
Size
Surface of rotor
Material of electronics
housing
Material of impeller
Direction of rotation
Type of protection
Insulation class
Humidity class
Mounting position
Translation of the original operating instructions
Condensate discharge
holes
Operation mode
Motor bearing
Technical features
Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)
Motor protection
Cable exit
Protection class
Product conforming
to standard
Approval
2.5 kg
140 mm
Galvanised
Die-cast aluminium
PP-TV40 plastic
Clockwise, seen on rotor
IP 44
"B"
F3-1
Shaft horizontal, discharge on right side
or on left side
Rotor-side
For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.
3.4 Mounting data
For depth of screw, see chapter 3.1 Product drawing
; Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).
Strength class for
mounting screws
8.8
You can obtain additional mounting data from the product drawing if
necessary.
3.5 Transport and storage conditions
; Use the device in accordance with its protection type.
Max. permissible
ambient motor temp.
(transp./ storage)
Min. permissible
ambient motor temp.
(transp./storage)
+ 80 °C
- 40 °C
3.6 Electromagnetic compatibility
EMC interference
immunity
EMC harmonics
EMC interference
emission
Acc. to EN 61000-6-2 (industrial
environment)
Acc. to EN 61000-3-2/3
Acc. to EN 61000-6-3 (household
environment)
S1
Ball bearing
- Output 10 VDC, max. 1.1 mA
- Tach output
- Motor current limit
- Soft start
- Control interface with SELV potential
safely disconnected from the mains
- Overtemperature protection for motor
Set value input Lin 0-10 VDC / PWM
(1.7 V = 50 m³/h, 10 V = 300 m³/h),
output 10 VDC max. 1.1 mA, tach
output, locked-rotor protection
<= 3.5 mA
Thermal overload protector (TOP) wired
internally
Variable
I (if protective earth is connected by
customer)
EN 60335-1; CE
GOST
Item no. 50889-5-9970 · Revision 78380 · Release 2013-06-03 · Page 5 / 10
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
G3G140-AW05-12
Operating instructions
4. CONNECTION AND START-UP
→ Make sure that the cable end is connected in a dry
environment.
4.1 Connecting the mechanical system
Connect the device only to circuits that can be switched off
using an all-pole disconnecting switch.
CAUTION
Cutting and crushing hazard when removing the blower
from the packaging
→ Carefully remove the blower from its packaging, only
touching the housing. Make sure to avoid any shock.
→ Wear safety shoes and cut-resistant safety gloves.
; Check the device for transport damage. Damaged devices must no
longer be installed.
; Check whether the data on the type plate agree with the connection
data.
; Before connecting the device, ensure that the supply voltage matches
the operating voltage of the device.
DANGER
Electric voltage on the device
Electric shock
; Only use cables designed for current according to the type plate.
For determining the cross-section, follow the basic principles in
accordance with EN 61800-5-1. The protective earth must have a
cross-section equal to or greater than the outer conductor crosssection.
We recommend the use of 105°C cables. Ensure that the minimum
cable cross-section is at least
AWG26/0.13 mm².
→ Always install a protective earth first.
Earth wire contact resistance in accordance with EN 60335
→ Check the protective earth.
Compliance with the impedance specifications in accordance with EN
60335 for the protective earth circuit must be verified in the end
application.
Depending on the installation situation, it may be necessary to install an
additional protective earthing conductor via the additional protective earth
connection point available on the device.
; Install the undamaged device according to your application.
4.2 Connecting the electrical system
DANGER
Incorrect insulation
Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation
requirements for voltage, current, insulation material, load etc.
→ Route cables such that they cannot be touched by any
rotating parts.
DANGER
Electrical load (>50 µC) between mains wire and
protective earth connection after switching of the supply
when switching multiple devices in parallel.
Electric shock, risk of injury
→ Make sure that sufficient protection against accidental contact
is provided.
Before working on the electrical connection, the
connections to the mains supply and PE must be shorted.
Translation of the original operating instructions
4.2.1 Prerequisites
CAUTION
Electrical voltage
The device is a built-in component and features no electrically
isolating switch.
→ Connect the device only to circuits that can be switched off
using an all-pole disconnecting switch.
4.2.2 Idle current
Because of the EMC filter integrated for compliance with EMC
limits (interference emission and interference immunity), idle
currents in the mains cable can be measured even when the
motor is at a standstill and the mains voltage is switched on.
4.2.3 Locked-rotor protection
Due to the locked-rotor protection, the start-up current (LRA) is
equal to or less than the nominal current (FLA).
4.3 Connection of the cables
External leads are brought out of device.
; First connect the "PE" (protective earth) connection.
●
Connect the lines according to your application. When doing so,
observe chapter 4.4 Connection screen.
→ When working on the device, you must switch off the
system/machine in which the device is installed and secure
it from being switched on again.
NOTE
Interferences and failures are possible
Maintain a distance to the power supply line when routing the
control lines of the device.
→ Ensure a sufficiently large clearance.
Recommendation: clearance > 10 cm (separate cable
routing)
NOTE
Water penetration into leads or wires
Water enters at the cable end on the customers side and can
damage the device.
Item no. 50889-5-9970 · Revision 78380 · Release 2013-06-03 · Page 6 / 10
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
Operating instructions
G3G140-AW05-12
4.4 Connection screen
No.
2
3
1
Signal
L
N
PE
7
5
6
4
0-10 V PWM
Tach
10V
GND
Colour
brown
blue
green/
yellow
yellow
white
red
blue
Function / assignment
Power supply 230 VAC, 50-60 Hz, see type plate for voltage range
Neutral conductor
Protective earth
Control input 0 - 10 V or PWM, electrically isolated
Tach output: Open Collector, 1 pulse per revolution, electrically isolated
max. 1.1 mA, voltage output 10 V/1.1 mA, electrically isolated, not short-circuit-proof
GND - Connection for control interface
Translation of the original operating instructions
Line
Item no. 50889-5-9970 · Revision 78380 · Release 2013-06-03 · Page 7 / 10
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
G3G140-AW05-12
Operating instructions
4.5 Checking the connections
5. INTEGRATED PROTECTIVE FUNCTIONS
; Make sure that the power is off (all phases).
; Secure it from being switched on again.
The integrated protective functions cause the motor to switch off
automatically in case of faults described in the table.
; Check the correct fit of the connection lines.
Malfunctions
; Route the connecting cables in the terminal box so that the terminal
box cover closes without resistance.
; Use all plug screws (the entire number). In doing so, insert the
screws manually to avoid damage to the thread.
4.6 Switch on device
Rotor position detection error
Locked rotor
Description / Function of
safety feature
An automatic restart occurs.
; After the blockage is
removed, the motor restarts
automatically.
WARNING
Hot motor housing
Fire hazard
→ Ensure that no combustible or flammable materials are
located close to the blower.
; Inspect the device for visible external damage and the proper function
of the protective features before switching it on.
; Check the air flow paths of the fan for foreign objects and remove any
that are found.
; Apply the nominal voltage to the voltage supply.
; Start the device by changing the input signal.
4.7 Switching off the device
; Disconnect the device from the supply voltage at the main switch for
the supply line.
Translation of the original operating instructions
; When disconnecting, be sure to disconnect the earth wire connection
last.
Item no. 50889-5-9970 · Revision 78380 · Release 2013-06-03 · Page 8 / 10
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
Operating instructions
G3G140-AW05-12
6. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES
Overtemperature of
electronics/motor
Insufficient cooling
Do not perform any repairs on your device. Return the device to ebmpapst for repair or replacement.
WARNING
Terminals and connections have voltage even with a
unit that is shut off
Electric shock
Ambient temperature
too high
→ Wait five minutes after disconnecting the voltage at all poles
before opening the device.
CAUTION
If control voltage is applied or a speed setpoint is stored,
the motor automatically restarts, e.g. after a power failure.
Danger of injury
→ Keep out of the danger zone of the device.
→ When working on the device, switch off the mains
supply voltage and secure the latter from being switched on
again.
→ Wait until the device stops.
→ After working on the device, remove any used tools or
other objects from the device.
If the device remains out of use for some time, e.g. when in
storage, we recommend switching the device on for at least
two hours to allow any condensate to evaporate and to move
the bearings.
Translation of the original operating instructions
Malfunction/error
Impeller running
roughly
Motor does not turn
Possible cause
Imbalance in rotating
parts
Mechanical blockage
Mains supply
voltage faulty
Faulty connection
Thermal overload
protector responded
Possible remedy
Clean the device; if
imbalance is still
evident after
cleaning, replace the
device.
If you have
attached any weight
clips during cleaning,
make sure to
remove them
afterwards.
Switch off, deenergise, and
remove mechanical
blockage.
Check mains supply
voltage,
restore power
supply,
apply control signal.
De-energise, correct
connection, see
connection diagram.
Allow motor to cool
off, locate and rectify
cause of error, if
necessary cancel
restart lock-out
Unacceptable
operating point
Improve cooling. Let
the device cool
down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Reduce the ambient
temperature. Let the
device cool down.
Correct the operating
point. Let the device
cool down.
If you have any other problems, contact ebm-papst.
6.1 Cleaning
NOTE
Damage to the device during cleaning.
Malfunction possible
→ Do not clean the device using a water jet or high-pressure
washer.
→ Do not use any cleaners containing acids,
bases or solvents.
→ Do not use any pointed or sharp-edged objects to clean.
6.2 Safety test
NOTE
High-voltage test
The integrated EMC filter contains Y capacitors. Therefore, the
trigger current is exceeded when AC testing voltage is applied.
→ Test the device with DC voltage when you carry out the
high-voltage test required by law. The voltage to be used
corresponds to the peak value of the AC voltage required by
the standard.
What has to
be tested?
Check the
protective
casing against
accidental
contact for
damage and to
ensure that it is
intact
Check the
device for
damage to
blades and
housing
Mounting the
connection lines
Mounting of
protective
earth connection
How to test?
Frequency
Visual inspection At least every
6 months
Which
measure?
Repair or
replacement of
the device
Visual inspection At least every
6 months
Replacement
of the device
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Fasten
Fasten
Item no. 50889-5-9970 · Revision 78380 · Release 2013-06-03 · Page 9 / 10
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
G3G140-AW05-12
Visual inspection At least every
6 months
Replace wires
Visual inspection At least every
6 months
Open bore holes
Translation of the original operating instructions
Check the
insulation of
the wires for
damage
Condensate
discharge
holes for
clogging, as
necessary
Operating instructions
Item no. 50889-5-9970 · Revision 78380 · Release 2013-06-03 · Page 10 / 10
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com