SAG582126100 SYSTEM OVERVIEW

SAG582126100
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
Issue AH, July 4, 2012
Home
SYSTEM OVERVIEW
Description:
-48VDC @ up to 10,000 amperes power system.
This power system is designed to power a load while charging a positive grounded
battery. This system is capable of operating in a battery-less installation or off-battery for
maintenance purposes. The system is designed for operation with the positive output
grounded.
The NetSure™ 702NBDB DC Power System is an integrated power system containing
rectifiers, intelligent control, metering, monitoring, and a bulk DC output panel. This
power system consists of the following components.
•
Power Bays
The system consists of one (1) Main Power Bay and up to four (4) optional
Supplemental Power Bays.
The Main and Supplemental Power Bays are equipped with six (6) Rectifier Module
Mounting Shelves, each of which houses up to six (6) Rectifier Modules. Each
Power Bay can be equipped with up to thirty-six (36) Rectifier Modules. Refer to
PD588705000 for Rectifier Shelf and Rectifier
Module information. The PD can be accessed via
the CD (Electronic Documentation Package)
furnished with your system.
Each Power Bay contains a Monitor and Control
Panel. In the Main Power Bay, this panel houses
the Meter-Control-Alarm (MCA) assembly. This
panel in the Main Power Bay also houses the LMS
Main CPU circuit card of the integrated LMS
Monitoring System. In a Supplemental Power Bay,
this panel can be equipped with an optional LMS
Expansion CPU circuit card. (The LMS Monitoring
System provides a higher level of monitoring and
controlling capabilities to the power system.)
The Monitor and Control Panel in both Main and
Supplemental Power Bays contain a seven-slot
card cage to house MCA alarm relay circuit cards,
optional MCA input/output (I/O) circuit cards, and
optional LMS I/O circuit cards. (If a Supplemental
Power Bay is to be equipped with optional LMS I/O
circuit cards, it must also be equipped with the LMS
Expansion CPU circuit card.)
•
Rectifier Modules
The Rectifier Modules provide load power, battery
float current, and battery recharge current during
normal operating conditions. Refer to the rectifier
User Instructions for Rectifier Module information.
The document can be accessed via the CD
(Electronic Documentation Package) furnished with
your system.
Main Bay
Page 1 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
•
Home
MCA (Meter-Control-Alarm)
The MCA controls the operation of the Rectifier Modules and provides power system
control, metering, monitoring, and alarm functions.
MCA Local Control Panel: This panel is located on the front of the Main Power Bay
and contains a keypad, display, and indicators for local MCA user interface.
MCA Relay Circuit Card: Each MCA relay circuit card provides six (6) sets of
Form-C relay contacts for customer external alarms. These relays are user
programmable for various power system alarms. The MCA can interface with up to
sixteen (16) MCA relay circuit cards.
MCA I/O Circuit Cards: The MCA I/O circuit cards provide analog inputs/outputs
and binary inputs. The MCA can interface with up to sixteen (16) MCA I/O circuit
cards.
•
Integrated LMS Monitoring System
The LMS Monitoring System consists of an LMS Main CPU circuit card, optional LMS
Expansion CPU circuit card, optional LMS I/O circuit cards, optional LMS Expansion
Cabinets, and optional LMS Expansion Assemblies.
The LMS Main CPU circuit card is mounted in the
Main Power Bay. The 582126100 List 11
Customized Main Bay is factory equipped with one
(1) LMS 4-input analog circuit card (586505500 List
20), two (2) LMS 8-input binary circuit cards
(586505500 List 31), and three (3) LMS 4-output
relay circuit cards (586505500 List 40). The
582126100 List 13 Main Bay comes with (2) 514348
6-output Form C relay cards. If a Supplemental
Power Bay is to be equipped with optional LMS I/O
circuit cards, it must contain an LMS Expansion
CPU circuit card. LMS Expansion Cabinets and
LMS Expansion Assemblies are available that
mount into customer racks and equipment.
The LMS Monitoring System is factory integrated
within each Power Bay, and requires no additional
customer interconnections within the Power Bay.
Simple cable connections between Power Bays
complete the interbay connections required.
Separate analog, binary, and relay circuit cards do
not have to be supplied for power system
monitoring. Analog, binary, relay, and temperature
circuit cards can be provided to monitor equipment
external to the power system.
The LMS input circuit cards monitor a variety of
analog, binary, and temperature points external to
the system. An LMS relay output circuit card is also
available which provides programmable relays.
These relays may be used for external alarms, or to
control other equipment.
The LMS Monitoring System can be accessed via a
local port, a modem port, an optional TL1 port, and
an Ethernet port (for Telnet access, Web access,
SNMP access, optional TL1 access, and Email
Supplemental Bay
Page 2 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
Home
alarm reporting).
The LMS Monitoring System collects data from the power system and the
input circuit cards monitoring external points. The data collected is used for alarm
processing and reporting, and to provide statistics.
The LMS Monitoring System is capable of reporting alarm conditions to a remote
terminal, pager, Email address, via SNMP traps over Ethernet, or via TL1 (over
Ethernet) when the 'TL1 over Ethernet' option is ordered. TL1 is also available via a
serial connection in 'direct mode'. For remote terminal or pager notification, the LMS
Main CPU circuit card is equipped with a modem. Two types of alarm reporting
mechanisms are provided, System Alarm Reporting and Individual User Alarm
Reporting.
Refer to SAG586505000/SAG586505500 for further LMS information. The SAG can
be accessed via the CD (Electronic Documentation Package) furnished with your
system.
•
Bulk DC Output Panel
The Bulk DC Output Panel provides landing points for connection of customer power
leads.
•
Applications
The NETSURE™ 702NBDB Power Bay is capable of interfacing with NETSURE™
801NL-B Distribution Bays (Spec. No. 582140001).
®
The NETSURE™ 702NBDB Power Bay is capable of interfacing with Vortex Power
Systems (VPS).
The NETSURE™ 702NBDB is capable of interfacing with legacy power systems.
Refer to the wiring diagrams in the Installation Instructions (Section 6027). Refer
also to Dual MCA Option Cable in the ACCESSORY DESCRIPTION section.
Page 3 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
Home
Family:
NETSURE™
Spec. No.:
582126100
Model:
702NBDB
Power Bay Input Voltage
The power bay requires twelve (12) nominal 208/240 volts AC, three
phase, 50/60 Hz, inputs. Each input supplies three (3) single-phase
rectifier modules.
Rectifier Input Voltage
Nominal 208/240 volts AC, single phase, 50/60 Hz, with an operating
range of 176 to 264 volts. Acceptable input frequency range is 45 to
65 Hz.
Output Voltage:
-48 Volts DC, adjustable
Output Capacity:
System:
Power Bay:
Rectifier Module (PCU)
10,000 Amperes, maximum
2,000 Amperes, maximum
1R483200 and 1R483200e: 55.2A @ -58VDC to 66.6A @ -48VDC
Agency Approval:
Listed UL 1950
Framework Type:
7’ x 23” Relay Rack, Seismic Zone 4
Mounting Width:
23 Inches, nominal
Mounting Depth:
17.50 Inches
Access:
Front Access for Installation, Operation, and Maintenance.
Supplemental Bay(s) Available:
Four (4)
Control:
Microprocessor
Color:
Bay and Rectifier Module Faceplates:
Textured Gray (Spec. M500-147)
Rectifier Shelf and Rectifier Modules Bodies:
Bright Zinc Plating (Spec. M500-53)
Environment:
-40°C to +40°C (-40°F to +104°F)
Page 4 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
Home
582126100
Power Bay Diagram
Top Mount AC Input
Termination Panels
(P/O List 11, 12 and 13)
Bulk Output Panel
(P/O List 11, 12
and 13)
(See Monitor and
Control Diagram)
List 11: Customized Main Power Bay
List 12: Supplemental Power Bay
Rectifier Module
Mounting Shelf
(P/O List 11, 12 and 13)
List 13: Main Power Bay
Rectifier Module
See Also
System Overview
Table of Contents
List Descriptions
Accessory Descriptions
Specifications
Physical Size Information
Related Documentation
Front View
Page 5 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
Home
582126100
Power Bay Monitor and Control Diagram
P/O List 11:
MCA/ROUTER Circuit Card
(Main Power Bay)
P/O List 12: ROUTER Circuit Card
(Supplemental Power Bay)
Battery Charge Temperature
Compensation Probe Connector
P/O List 13: MCA/ROUTER Circuit Card
(Main Power Bay, Customizable)
POWER
FA
* ETHERNET
* Main
Bay
Only
3A 3A 3A
CAN BUS
* RS-485
ECH 1
ECH 2
* TEMP
ECH 3
L D
M S
S M
F1 F2
M
C
A
F3
Front View
LMS Main CPU Circuit Card
(P/O List 11, Customized Main
Power Bay),
(P/O List 13, Main Power Bay)
or
Optional LMS Expansion CPU
Circuit Card (Supplemental Power
Bay)
Available MCA Input/Output (I/O) Circuit Cards
MCA Customer Alarm Relay Circuit
Card (Six [6] Form-C Contacts)
MCA Analog Input/Output and
Binary Input Circuit Card
Refer to
SAG586505000/SAG586505500
Page 6 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
TABLE OF CONTENTS
System
Overview
Picture
List
Descriptions
Accessory
Descriptions
Specifications
Physical Size
Information
Related
Documentation
SYSTEM OVERVIEW................................................................................................................................................. 1
582126100 Power Bay Diagram .......................................................................................................................... 5
582126100 Power Bay Monitor and Control Diagram ...................................................................................... 6
TABLE OF CONTENTS ............................................................................................................................................. 7
LIST DESCRIPTIONS ................................................................................................................................................ 9
List 11: Main Power Bay, Customized ............................................................................................................ 9
List 12: Supplemental Power Bay ................................................................................................................. 10
List 13: Main Power Bay ............................................................................................................................... 11
ACCESSORY DESCRIPTIONS ............................................................................................................................... 12
Rectifier Module, High-Efficiency (P/N 1R483200E)....................................................................................... 12
Rectifier Module (P/N 1R483200) ..................................................................................................................... 12
Rectifier Module Mounting Position Blank Cover Panel (P/N 21140440)..................................................... 12
Distribution Bays (P/N 58214000116) .............................................................................................................. 12
Main Battery Termination Bars (MBTB’s) ....................................................................................................... 13
Optional Battery Charge Temperature Compensation Probe (P/Ns 107021 and 106824).......................... 13
Optional LMS Expansion CPU Circuit Card (Supplemental Power Bays) (P/N 506153) ............................ 14
Optional MCA Six (6) Output Form-C Relay Circuit Card (P/N 514348) ....................................................... 14
Optional MCA Analog Input/Output and Binary Input Circuit Card (P/N 524550) ....................................... 14
LMS Options ...................................................................................................................................................... 15
Replacement/Additional MCA Network Cable ................................................................................................ 15
Replacement/Additional LMS Network Cable ................................................................................................. 15
Dual MCA Option Cable .................................................................................................................................... 16
Replacement Control Fuses ............................................................................................................................. 17
Replacement Components ............................................................................................................................... 17
Wiring Notes ...................................................................................................................................................... 18
DC Output Connections ................................................................................................................................. 18
AC Input Connections .................................................................................................................................... 18
Relay Rack Frame Grounding Connections .................................................................................................. 20
External Alarm, Reference, and Control Connections ................................................................................... 20
Wiring Illustrations ............................................................................................................................................ 21
DC Output Connections ................................................................................................................................. 21
AC Input Connections .................................................................................................................................... 22
Relay Rack Frame Grounding Connections .................................................................................................. 23
External Alarm, Reference, and Control Connections ................................................................................... 24
SPECIFICATIONS.................................................................................................................................................... 25
1. System ........................................................................................................................................................... 25
1.1 Environmental Ratings ............................................................................................................................. 25
1.2 Compliance Information ........................................................................................................................... 25
1.3 Local Controls and Indicators ................................................................................................................... 25
2. MCA ................................................................................................................................................................ 25
2.1 Standard Features .................................................................................................................................... 25
3. Rectifier Module, high efficiency (Model R48-3200e, Spec. No. 1R483200e) ......................................... 39
4. Rectifier Module (Model R48-3200, Spec. No. 1R483200) ......................................................................... 39
5. LMS Monitoring System ............................................................................................................................... 39
PHYSICAL SIZE INFORMATION ............................................................................................................................ 40
Overall Dimensions - Main and Supplemental Power Bays .......................................................................... 40
Page 7 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
Overall Dimensions - Optional Digital Battery Charge Temperature Compensation Probes P/N
107021 (25 feet) and P/N 106824 (100 feet) ..................................................................................................... 41
RELATED DOCUMENTATION ................................................................................................................................ 42
REVISION RECORD ................................................................................................................................................ 43
Page 8 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
Home
LIST DESCRIPTIONS
List 11: Main Power Bay, Customized
Features
♦
Provides common equipment for one (1) Main Power Bay rated for up to 2000 amperes.
♦
Mounted in a 7'H x 23"W seismic rated (Zone 4) relay rack (P/N 543160).
♦
Provides six (6) 58870500003 Rectifier Module Mounting Shelves.
♦
Provides thirty-six (36) Rectifier Module mounting positions.
♦
Provides pre-wired top mounted AC input termination panels that accept twelve (12) three-phase AC
input branch circuits, one (1) per three Rectifier Module mounting positions. AC input termination panels
accept (12) 3/4" conduit fittings (six per side).
♦
Provides the MCA/Router Assembly and Local MCA Control Panel.
♦
Provides the LMS Main CPU circuit card equipped with dual MCA (586505500 List 78), WEB Interface
(586505500 List 81), LMS Rectifier Sequencing (586505500 List 82), and SNMP Option (586505500 List
89).
♦
Provides a seven-slot card cage for mounting MCA customer alarm relay circuit cards, optional MCA I/O
circuit cards, and/or optional LMS I/O circuit cards. The 582126100 List 11 Bay is factory equipped with
one (1) LMS 4-input analog circuit card (586505500 List 20), two (2) LMS 8-input binary circuit cards
(586505500 List 31), and three (3) LMS 4-output relay circuit cards (586505500 List 40).
♦
Provides the LMS Modem Assembly (586505500 List 70).
♦
Provides a digital temperature compensation probe, P/N 107021.
♦
Provides custom software configuration. Refer to drawing C58212610011 for detail.
Restrictions
Only one (1) Main Power Bay per power system required.
Ordering Notes
1) Order up to thirty-six (36) Rectifier Modules per bay, P/N 1R483200 or P/N 1R483200e, as described in
the ACCESSORY DESCRIPTIONS section.
2) If desired, order a Rectifier Module Mounting Position Blank Cover Panel, P/N 21140440, for each empty
rectifier module mounting position in the system, as described in the ACCESSORY DESCRIPTIONS
section.
3) Order optional MCA customer alarm relay circuit card(s) as required, P/N 514348, as described in the
ACCESSORY DESCRIPTIONS section.
4) Order optional MCA Analog Input/Output and Binary Input circuit card(s) as required, P/N 524550, as
described in the ACCESSORY DESCRIPTIONS section.
5) Order LMS options as required, as described in the ACCESSORY DESCRIPTIONS section and per
SAG586505000/SAG586505500.
6) Refer to DC Output Connections, AC Input Connections, and Relay Rack Frame Grounding Connections
in the ACCESSORY DESCRIPTIONS section’s “Wiring Notes” and “Wiring Illustrations” for wiring
requirements.
7) If the system is to be connected to an existing Vortex system with an MCA, order a Dual MCA Option
Cable as described in the ACCESSORY DESCRIPTION section.
Page 9 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
Home
List 12: Supplemental Power Bay
Features
♦
Provides common equipment for one (1) Supplemental Power Bay rated for up to 2000 amperes.
♦
Mounted in a 7'H x 23"W seismic rated (Zone 4) relay rack (P/N 543160).
♦
Provides six (6) 58870500003 Rectifier Module Mounting Shelves.
♦
Provides thirty-six (36) Rectifier Module mounting positions.
♦
Provides pre-wired top mounted AC input termination panels that accept twelve (12) three-phase AC
input branch circuits, one (1) per three Rectifier Module mounting positions. AC input termination panels
accept (12) 3/4" conduit fittings (six per side).
♦
Includes a Router Assembly for bay communication to the MCA in the Main Power Bay.
♦
Provides mounting for optional LMS Expansion CPU circuit card.
♦
Provides a seven-slot card cage for mounting MCA customer alarm relay circuit cards, optional MCA I/O
circuit cards, and/or optional LMS I/O circuit cards.
♦
MCA Network bay interconnect cable provided (Qty. 1 P/N 524726).
Restrictions
The system supports up to four (4) Supplemental Power Bays.
Ordering Notes
1) Order up to thirty-six (36) Rectifier Modules per bay, P/N 1R483200 or P/N 1R483200e, as described in
the ACCESSORY DESCRIPTIONS section.
2) If desired, order a Rectifier Module Mounting Position Blank Cover Panel, P/N 21140440, for each empty
rectifier module mounting position in the system, as described in the ACCESSORY DESCRIPTIONS
section.
3) Order optional MCA customer alarm relay circuit card(s) as required, P/N 514348, as described in the
ACCESSORY DESCRIPTIONS section.
4) Order optional MCA Analog Input/Output and Binary Input circuit card(s) as required, P/N 524550, as
described in the ACCESSORY DESCRIPTIONS section.
5) Order optional LMS Expansion CPU circuit card, P/N 506153, and LMS options as required, as described
in the ACCESSORY DESCRIPTIONS section and per SAG586505000/SAG586505500. Also order
additional LMS Network cables as required per Replacement/Additional LMS Network Cables.
6) Refer to DC Output Connections, AC Input Connections, and Relay Rack Frame Grounding Connections
in the ACCESSORY DESCRIPTIONS section’s “Wiring Notes” and “Wiring Illustrations” for wiring
requirements.
7) If a different length LMS and/or MCA Network cable is required, order per Replacement/Additional LMS
Network Cables and/or Replacement/Additional MCA Network Cables. Refer to the Installation
Instructions (Section 6027) for Network cabling requirements.
Page 10 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
Home
List 13: Main Power Bay
Features
♦
Provides common equipment for one (1) Main Power Bay rated for up to 2000 amperes.
♦
Mounted in a 7'H x 23"W seismic rated (Zone 4) relay rack (P/N 543160).
♦
Provides six (6) 58870500003 Rectifier Module Mounting Shelves.
♦
Provides thirty-six (36) Rectifier Module mounting positions.
♦
Provides pre-wired top mounted AC input termination panels that accept twelve (12) three-phase AC
input branch circuits, one (1) per three Rectifier Module mounting positions. AC input termination panels
accept (12) 3/4" conduit fittings (six per side).
♦
Provides the MCA/Router Assembly and Local MCA Control Panel.
♦
Provides the LMS Main CPU circuit card equipped with WEB Interface (586505500 List 81), and SNMP
Option (586505500 List 89).
♦
Provides a seven-slot card cage for mounting MCA customer alarm relay circuit cards, optional MCA I/O
circuit cards, and/or optional LMS I/O circuit cards. The 582126100 List 13 Main Bay comes with (2)
514348 6-output Form C relay cards.
Restrictions
Only one (1) Main Power Bay per power system required.
Ordering Notes
1) Order up to thirty-six (36) Rectifier Modules per bay, P/N 1R483200 or P/N 1R483200e, as described in
the ACCESSORY DESCRIPTIONS section.
2) If desired, order a Rectifier Module Mounting Position Blank Cover Panel, P/N 21140440, for each empty
rectifier module mounting position in the system, as described in the ACCESSORY DESCRIPTIONS
section.
3) Order optional MCA customer alarm relay circuit card(s) as required, P/N 514348, as described in the
ACCESSORY DESCRIPTIONS section.
4) Order optional MCA Analog Input/Output and Binary Input circuit card(s) as required, P/N 524550, as
described in the ACCESSORY DESCRIPTIONS section.
5) Order LMS options as required, as described in the ACCESSORY DESCRIPTIONS section and per
SAG586505000/SAG586505500.
6) Order a Battery Charge Temperature Compensation Probe as required per Optional Battery Charge
Temperature Compensation Probe in the ACCESSORY DESCRIPTIONS section.
7) Refer to DC Output Connections, AC Input Connections, and Relay Rack Frame Grounding Connections
in the ACCESSORY DESCRIPTIONS section’s “Wiring Notes” and “Wiring Illustrations” for wiring
requirements.
8) If the system is to be connected to an existing Vortex system with an MCA, order a Dual MCA Option
Cable as described in the ACCESSORY DESCRIPTION section. The system should also be equipped
with the dual MCA software option (586505500 List 78).
Page 11 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
Home
ACCESSORY DESCRIPTIONS
Rectifier Module, High-Efficiency (P/N 1R483200E)
Features
♦
Model R48-3200e, Spec. No. 1R483200E, 3200 watt / 48 volt high-efficiency
rectifier module.
♦
Refer to the rectifier User Instructions (UM1R483500E) for Rectifier Module
specifications.
Restrictions
For use in Spec. No. 588705000 Rectifier Module Mounting Shelf(s).
Ordering Notes
1) Order as required. Each bay can be equipped with up to thirty-six (36) Rectifier Modules.
Rectifier Module (P/N 1R483200)
Features
♦
Model R48-3200, Spec. No. 1R483200, 3200 watt / 48 volt rectifier module.
♦
Refer to the rectifier User Instructions (UM1R483500E) for Rectifier Module
specifications.
Restrictions
For use in Spec. No. 588705000 Rectifier Module Mounting Shelf(s).
Ordering Notes
1) Order as required. Each bay can be equipped with up to thirty-six (36) Rectifier Modules.
Rectifier Module Mounting Position Blank Cover Panel (P/N 21140440)
Features
♦
Covers one (1) unused Rectifier Module mounting position.
Ordering Notes
1) If desired, order a Rectifier Module Mounting Position Blank Cover Panel, P/N 21140440, for each empty
rectifier module mounting position in the system.
Distribution Bays (P/N 58214000116)
Ordering Notes
♦
When DC Load Distribution is required, order Distribution Bay 58214000116. Refer to SAG582140001
for information.
Page 12 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
Home
Main Battery Termination Bars (MBTB’s)
Ordering Notes
1) Plant is designed for centralized configuration with customer supplied Main Battery Termination Bars
(MBTB’s). Emerson Network Power Services has standard MBTB’S in 4000, 6000, 10000, and 16000
ampere capacities. The ultimate plant capacity is determined by the capacity of the MBTB’S. Refer to
the EA3434-41xx Series MBTB’s drawings.
Optional Battery Charge Temperature Compensation Probe (P/Ns 107021 and 106824)
Note: The P/N 107021 probe is factory provided with the 582126100 List 11 bay.
Features
♦
This system can be used with a Battery Charge Temperature Compensation Probe. This probe must be
mounted near the battery to sense battery ambient temperature. The probe connects to and allows the
MCA to automatically increase or decrease the output voltage of the system to maintain battery float
current as battery ambient temperature decreases or increases, respectively. Battery life can be
extended when an optimum charge voltage to the battery with respect to temperature is maintained. See
"Overall Dimensions - Optional Digital Battery Charge Temperature Compensation Probes P/N 107021
and P/N 106824" under PHYSICAL SIZE INFORMATION for a dimensional drawing.
♦
Allows Rectifier Module Battery Charge Temperature Compensation.
♦
Temperature Curve: Refer to Figure 1.
Decreasing
Voltage
Increasing
MAX W/T
Adjustable from
Float to 58.0V max.*
SLOPE
Adjustable from 0.0 V / °C
to 0.2 V / °C
FLOAT
Determines Float Mode
Output Voltage at 25°C.
Adjustable from 46.0V
to 57.0V max.*
MIN W/T
Adjustable from
Float to 44V
* Maximum setting is automatically
limited to 1.0 volt less than HVSD setting.
Decreasing
Temperature
Increasing
+25°C
(+77°F)
Figure 1
Typical Float Charge Thermal Characteristics
Using Optional Battery Charge Digital Temperature Compensation Probe
(Indicated parameters are user-adjustable via the associated MCA.)
Ordering Notes
1) Order one Battery Charge Temperature Compensation Probe per power system, as required. Two
probes are available. P/N 107021 has a 25-foot long cord and P/N 106824 has a 100 foot-long cord.
Page 13 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
Optional LMS Expansion CPU Circuit Card (Supplemental Power Bays)
(P/N 506153)
Home
Features
♦
Allows LMS I/O cards to be installed in Supplemental Power Bays.
Restrictions
The LMS Monitoring System Expansion CPU circuit cards are mounted in Supplemental Power Bays
(required only if LMS I/O circuit cards are to be installed in the same bay).
Ordering Notes
1) Order the LMS Expansion CPU circuit card for Supplemental Power Bays that are to be equipped with
LMS I/O circuit cards, P/N 506153.
2) Also order an LMS Network cable P/N 514640 per Replacement/Additional LMS Network Cables.
Optional MCA Six (6) Output Form-C Relay Circuit Card (P/N 514348)
Features
♦
Provides six relays each with one set of Form-C relay contacts.
♦
These relays are used for alarm applications and can be programmed by the user.
♦
Refer to the "Specifications" section of this document for further information.
♦
Plugs into any slot in 7-position card cage in Main and Supplemental Power Bays.
♦
User maps relay to any or multiple programmable alarm functions.
Restrictions
Relay contacts rated for 2A at 30 volts DC.
The system may contain up to sixteen (16) MCA Relay circuit cards.
Ordering Notes
1) Order one (1) MCA Relay Circuit Card P/N 514348 for every six (6) sets of Form-C relay contacts to be
provided by the MCA for customer external alarms.
Optional MCA Analog Input/Output and Binary Input Circuit Card (P/N 524550)
Features
♦
Provides 1 analog input, 1 analog output (for remote plant output current monitoring), and 4 binary inputs.
♦
Refer to the "Specifications" section of this document for further information.
♦
Plugs into any slot in 7-position card cage in Main and Supplemental Power Bays.
Restrictions
The system may contain up to sixteen (16) MCA I/O circuit cards.
Only one (1) P/N 524550 card can be installed per bay.
Analog input and output rating = 0-50mv DC.
Binary input rating = dry contact.
Analog inputs should be protected by a 49.9 ohm resistor.
Page 14 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
Recommended to use current limiting resistors to protect binary input wiring.
Home
Ordering Notes
1) Order optional MCA Analog Input/Output and Binary Input Circuit Card P/N 524550 as required.
LMS Options
Features
♦
The LMS provides software options and I/O cards.
Restrictions
Note that the LMS WEB Interface (586505500 List 81), LMS Rectifier Sequencing (586505500 List 82), and
SNMP Option (586505500 List 89) are factory provided with List 11. 586505500 List 81 and List 89 are
provided with List 13.
Ordering Notes
1) Refer to SAG586505000/SAG586505500 for ordering.
Replacement/Additional MCA Network Cable
Features
♦
MCA bay-to-bay interconnect cable. Connects between bay expansion ports located on the bay's
MCA/Router (Main Power Bay) and Router (Supplemental Power Bays) circuit cards.
♦
Cable identification color is yellow.
Restrictions
Maximum combined cable length must not exceed 125 feet.
Ordering Notes
1) For a replacement or additional cable, order the proper length cable from those listed below.
P/N 524726 (15 feet) (factory provided with List 12)
P/N 514645 (25 feet)
P/N 514646 (50 feet)
P/N 514647 (100 feet)
Replacement/Additional LMS Network Cable
Features
♦
LMS bay-to-bay interconnect cable. Connects between the bay's LMS Echelon expansion ports. Also
connects the LMS System to LMS Expansion Cabinets and Assemblies, if furnished.
♦
Cable identification color is blue.
Restrictions
Refer to SAG586505000/SAG586505500 (LMS System Application Guide) for maximum LMS network
cabling length.
Ordering Notes
1) For a replacement or additional cable, order the proper length cable from those listed below.
Page 15 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
P/N 514640 (25 feet) (required when LMS Expansion CPU Card installed in Supplemental Power Bay)
P/N 514641(150 feet)
Dual MCA Option Cable
Features
♦
This system can be connected to systems with an existing MCA as described in the Installation
Instructions (Section 6027) and also the LMS documentation.
Restrictions
Connections to systems with an existing MCA require that the LMS Dual MCA Software Option be installed.
Refer to SAG586505000/SAG586505500.
Ordering Notes
1) To connect the two MCAs (via the LMS), order a proper length Dual MCA Option Cable from those listed
below.
P/N 526842 (25 feet)
P/N 526843 (50 feet)
2) The existing Vortex system MCA must be equipped with the RS485 option, or the LMS1000 in the Vortex
system must be equipped with the expansion CPU option. Refer to the Vortex and/or LMS1000 system
documentation for information.
Page 16 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
Home
Replacement Control Fuses
Features
♦
Control fuses are located on the fuseblock mounted in the ‘Monitor and Control’ section of the bay.
These fuses are not available for customer connected loads.
Ordering Notes
1) Order replacement fuses as required per the following table.
Desig.
Function
Size
(Amperes)
Type
Part No.
3
SAN-O AX-1
248609200
--
--
--
LMS CPU
Circuit Card
Input Power
--
F1
F2
F3
MCA/Router
Circuit Card
Input Power
3
SAN-O AX-1
248609200
--
Safety Fuse Cover
--
SAN-O SAX-1
248898600
Table 1
Replaceable Control Fuses
Replacement Components
Ordering Notes
1) Refer to the following table.
Item
Part Number
Rectifier Module
1R483200
eSure Rectifier Module, High-Efficiency
1R483200e
MCA/Router Circuit Card
(Main Power Bay)
509478
Router Circuit Card
(Supplemental Power Bay)
509509
LMS Primary CPU Circuit Card
(Main Power Bay)
545558
LMS Expansion CPU Circuit Card
(Supplemental Power Bay)
506153
MCA Customer Alarm
Relay Circuit Card
514348
MCA Analog Input/Output and Binary Input Circuit Card
524550
Temperature Probes
107021 (25’)
106824 (100’)
Table 2
Replaceable Components
Page 17 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
Home
Wiring Notes
Refer also to the next section, Wiring Illustrations.
DC Output Connections
Features
♦
3/8-16 captive fasteners on 1" centers are provided for installation of customer provided DC output cables
terminated in two-hole lugs. These are accessed from the front of each Power Bay.
♦
Refer to DC Output Connections under WIRING ILLUSTRATIONS for a diagram.
Restrictions
DC output cable size varies depending on power requirements, therefore no specific information is provided
for cable size. Refer to the current edition of the American National Standards Institute (ANSI) approved
National Fire Protection Association's (NPFA) National Electrical Code (NEC), applicable local codes, and
your specific site requirements.
All lugs for customer connections must be ordered separately.
Customer needs to supply lug mounting bolts and hardware.
Maximum size of wire to be connected to a single lug position is 750 kcmil.
Maximum lug width is 1.88 inches.
AC Input Connections
Features
♦
Pre-wired top mounted AC input termination panels are provided that accept twelve (12) three-phase AC
input branch circuits, one (1) per three Rectifier Module mounting positions. The AC input termination
panels accepts (12) 3/4" conduit fittings (six per side).
♦
Refer to AC Input Connections under WIRING ILLUSTRATIONS for a diagram.
Restrictions
Each power bay requires twelve (12) nominal 208/240 volts AC, three phase, 50/60 Hz, inputs. Each input
supplies three (3) single-phase rectifier modules.
Page 18 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
Home
Ordering Notes
1) Refer to the following table for recommended wire sizes and branch circuit protection.
AC INPUT (to Top Mount AC Input Termination Panels)
Connection Points for Two 3-Phase AC Input Feeds per Shelf are Provided
Operating
Ambient
(1)
Temperature
Recm
Branch Circuit
(2, 3)
Protection
Recm 90°C
(1)
Wire Size
Capacity
Type
30°C
40 Amperes,
3-Pole
8 AWG
6 to 14 AWG
Screw Clamp
40°C
AC Input Terminals
AC INPUT GROUND (to Top Mount AC Input Termination Panels)
A Ground Bar is Provided in each AC Input Termination Panel
Operating
Ambient
(1)
Temperature
Ground Bar Terminals
(4)
Recm 90°C
(5)
Wire Size
Capacity
Type
10 AWG
10 to 14 AWG
Screw Clamp
30°C
40°C
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI)
approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table
310-16 for copper wire at 90°C conductor temperature, operating in ambients of 30°C and 40°C was
used. For operation in other ambients, apply derating factors listed in Table 310-16 of the NEC. For
operation in countries where the NEC is not recognized, follow applicable codes.
2
The AC input branch circuit protective device should be of the time-delay or high inrush type.
3
Recommendations based on Nominal Line Full Load Input Current of 29.3 Amperes.
4
Equipment grounding conductors must be provided with the AC input conductors supplied to the
panel. Frame ground terminals must be connected to earth ground, not power system neutral.
5
Equipment grounding conductor size based on recommendations of the NEC Table 250-122 for
copper wire. If aluminum or copper clad aluminum grounding conductor is used, refer to Table
250-122 for increased conductor size. For operation in countries where the NEC is not recognized,
follow applicable codes.
Table 3
Recommended AC Input Branch Circuit Protection and Wire Size
Page 19 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
Home
Relay Rack Frame Grounding Connections
Features
♦
At the top of the relay rack is a set of 1/4” clearance holes on 5/8" centers for installation of a customer
grounding lead terminated in a two-hole lug.
♦
Refer to Relay Rack Frame Grounding Connections under WIRING ILLUSTRATIONS for a diagram.
Restrictions
For relay rack grounding requirements, refer to the current edition of the American National Standards
Institute (ANSI) approved National Fire Protection Association's (NPFA) National Electrical Code (NEC),
applicable local codes, and your specific site requirements.
All lugs for customer connections must be ordered separately.
Customer needs to supply lug mounting bolts and hardware.
External Alarm, Reference, and Control Connections
Features
♦
External Alarm, Reference, and Control connections are made to TB1 on the MCA circuit card and TB1
on the MCA Customer Alarm Relay circuit cards.
♦
External Alarm, Reference, and Control connections are also made to the optional LMS I/O circuit cards
installed in the system.
♦
Refer to External Alarm, Reference, and Control Connections under WIRING ILLUSTRATIONS for a
diagram.
Restrictions
Refer to the system’s Installation Instructions (Section 6027) for MCA circuit card and MCA Customer Alarm
Relay Circuit Card connection details.
Refer to the LMS Installation Instructions (Section 5879) or the separate LMS I/O circuit card instructions
(Section 5944) for LMS I/O circuit card connection details.
Ordering Notes
1) Refer to the following table for recommended wire sizes.
Terminals
Capacity
Type
28 to 16
AWG
Screw Clamp
Recm
Wire Size
22 AWG for Loop Lengths Up to 200 ft.
18-20 AWG for Loop Lengths Over 200 ft.
Table 4
Recommended Alarm, Reference, and Control Wire Size
(TB1 on MCA Circuit Card)
(TB1 on MCA Customer Alarm Relay Circuit Card)
Page 20 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
Home
Wiring Illustrations
DC Output Connections
DC Output
Positive BusBar (+)
(Ground Return Bus)
Front
DC Output
Negative BusBar (-)
(Supply -48V Bus)
Bulk DC Output Panel
(details removed in
illustration for clarity)
3/8-16 Captive Fastener
on 1” Centers, 14 Places
Front
Page 21 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
Home
AC Input Connections
Front
Rectifier Shelves are Numbered
from 1 to 6, from Top to Bottom.
Cover removed in
illustration for clarity
Rectifier Slots are numbered from 1 to 6,
from left to right as viewed from the front.
The rectifier slot position numbers are
not related to the rectifier identification
numbers provided by the MCA.
Page 22 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
Home
Relay Rack Frame Grounding Connections
1/4" clearance holes
on 5/8" centers are
provided for installation
of customer provided
two-hole lug.
Top of
Relay Rack
Page 23 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
Home
External Alarm, Reference, and Control Connections
MCA/Router Circuit Card
(Main Power Bay)
MCA Customer Alarm Relay Circuit Cards
and/or LMS Input/Output (I/O Circuit Cards)
TB1
1
10
MCA/Router
Circuit Card
P/N 509478
(Main Power Bay)
NC
K3 COM
NO
18
9
NC
COM K6
NO
NC
K2 COM
NO
NC
COM K5
NO
NC
K1 COM
NO
NC
COM K4
NO
1
10
TB1
MCA Customer Alarm
Relay Circuit Card P/N 514348
(Main and/or Supplemental Power Bays)
Page 24 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
Home
SPECIFICATIONS
Note: For Rectifier Shelf specifications, refer to PD588705000.
For Rectifier Module specifications, refer to UM1R483500E (Rectifier User Instructions).
For LMS Monitoring System specifications, refer to SAG586505000/SAG586505500.
1. SYSTEM
1.1
Environmental Ratings
1.1.1
Operating Ambient Temperature Range: -40°C to +40°C (-40°F to +104°F).
1.1.2
Storage Ambient Temperature Range: -40°C to +85°C (-40°F to +185°F).
1.1.3
Humidity: This Power System is capable of operating in an ambient relative humidity range of
0% to 95%, non-condensing.
1.1.4
Altitude: See PD588705000.
1.1.5
Mounting: This equipment is intended only for installation in a Restricted Access Location on
or above a non-combustible surface. Clearance requirements are:
(A) Recommended minimum aisle space clearance for the front of the relay rack is 2' 6".
(B) Recommended minimum aisle space clearance for the rear of the relay rack is that which
is specified for proper Rectifier Mounting Shelf ventilation. Refer to Rectifier Mounting
Shelf Power Data Sheet PD588705000 for ventilation spacing requirements.
Note: Minimum spacing specified for ventilation may not permit replacement of certain
components such as busbars or Rectifier Mounting Shelves.
1.1.6
1.2
Heat Dissipation: 402.6 watts per square foot / foot. Special equipment room cooling may be
required.
Compliance Information
(A) Safety Compliance: This unit meets the requirements of UL 60950, Standard for
Information Technology Equipment, and is UL Listed as a power supply for use in
Telephone, Electronic Data Processing or Information Processing Equipment.
1.3
Local Controls and Indicators
1.3.1
MCA Component Identification Indicator: Each MCA component (i.e. Bay Router Circuit
Card, MCA Relay Circuit Card) contains an ID LED Indicator. The ID indicator illuminates Green
when the component is OK, Red when the component has failed, and flashing yellow when the
component is identified by the MCA.
1.3.2
See also ‘Local Status and Alarm Indicators’ in the MCA section of this document.
1.3.3
Refer to the "Operating Procedures" chapter in the Power System User Instructions (Section
6028) for a complete description of the Controls and Indicators.
2. MCA
2.1
Standard Features
2.1.1
MCA Interface: A User can access the MCA locally via the MCA Control Panel located on the
outside of the Main Power Bay.
A User can also access the MCA via the LMS.
Note: Option switches are provided to lockout changing adjustment/configuration/calibration
settings via the MCA control panel and/or via the LMS.
2.1.2
Float Charging Output Mode: In this mode of operation, system output voltage is constant
and output current does not exceed the current limit setting. During normal operation, the
battery is not required to furnish load current and remains in a fully charged condition.
Page 25 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
Note: If the current demanded by the load exceeds the current limit setting of the system, the
battery is required to furnish the difference in load current and begins discharging.
Note: If the system is used with a digital battery charge temperature compensation probe or
TXM, the MCA automatically adjusts system output. This ensures proper voltage to the
battery as battery ambient temperature fluctuates.
2.1.3
Test/Equalize Charging Output Mode: This mode of operation is used if higher output voltage
is required for equalizing the charge on all battery cells of a conventional flooded cell battery, or
for recharging the battery following a commercial power failure.
If the installation site does not require system equalize mode of operation, the equalize feature
can be used as a test feature. System equalize voltage can be adjusted to a test voltage value.
Placing the system into the test/equalize mode causes system output voltage to increase or
decrease to this test voltage value.
Note: If the system is used with a battery charge digital temperature compensation probe or
TXM, typical equalize mode of operation is not used.
2.1.4
Output Mode of Operation Selection: There are four methods of placing the system from the
float mode to the test/equalize mode.
(A) Method 1 (Manual Test/Equalize): A user manually places the system into the
test/equalize mode via the MCA interface. A user must manually return the system to the
float mode via the MCA interface.
(B) Method 2 (Manually Initiated Timed Test/Equalize): A user manually places the system
into the test/equalize mode via the MCA interface. The system automatically returns to the
float mode after a preset programmable time period (1-99 hours, in increments of one hour).
(C) Method 3 (Automatic Test/Equalize):
THE AUTOMATIC EQUALIZE FEATURE IS INTENDED FOR USE ONLY WITH WET CELL
BATTERIES. USING THIS FEATURE WITH VALVE REGULATED BATTERIES IS NOT
RECOMMENDED.
This feature can be enabled or disabled by a user via the MCA. The default state is
disabled.
The Automatic Equalize feature is a time based function that is controlled by a customer
selectable multiplier and by the Battery On Discharge (BOD) alarm setpoint. The MCA’s
default setting is for a multiplier of zero, which disables the Automatic Equalize feature.
When the Automatic Equalize feature is enabled, if system voltage drops to less than the
BOD alarm setpoint, the MCA initiates a timing cycle to measure the discharge time period.
The MCA requires at least 15 minutes of continuous BOD alarm in order to prevent nuisance
equalization cycles. When system voltage rises to above the BOD alarm setpoint, the MCA
ends the discharge timing cycle and (assuming a minimum of 15 minutes has elapsed)
places the Rectifier Modules into the equalize mode for a customer selectable multiple of the
discharge time period (the discharge time period includes the initial 15 minutes).
The equalize time period can be set for 0 to 15 times the discharge time period, up to a
maximum of 300 hours. A zero (0) setting disables the feature.
(D) Method 4 (External Test/Equalize): A user (or external equipment) places the system into
the test/equalize mode by applying an external signal to the system. The system returns to
the float mode when the external signal is removed. This method overrides the other three
methods.
2.1.5
MCA Local Display: Provides digital metering of system load voltage and current, individual
Rectifier Module output, and individual load shunts. Also displays system alarm messages and
adjustment information, as detailed in Paragraph 2.1.13 (MCA Display).
2.1.6
MCA Meter Accuracy: ±0.01 V, ±0.005% / °C
Page 26 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
2.1.7
MCA Remote Sense Maximum Voltage Drop Compensation: The maximum voltage
drop that the Remote Sense can compensate is 400mV for 48V systems and 200mV
for 24V systems.
2.1.8
MCA Universal Adjustment Circuit: Provides single point control of float output voltage,
test/equalize output voltage, high voltage shutdown, and current limit adjustments.
Home
Note: If the MCA should fail, the Rectifier Modules remember the float and high voltage
shutdown settings last delivered by the MCA. The current limit setting of each Rectifier
Module goes to 66 amperes.
Provides adjustments for all MCA alarm and control circuits. Adjustment ranges and factory
settings as follows.
All adjustments can be performed locally via the MCA Control Panel, and most can be performed
remotely via the LMS.
(A) Rectifier Module Output Voltage
(1) Without Battery Charge Temperature Compensation: Float voltage is adjustable
from 47.00 to 58.00 volts DC. Test/equalize voltage is adjustable from 44.00 to 58.00
volts DC. The output voltage temperature coefficient does not exceed 0.01% per
degree centigrade from -40°C to +65°C. Float voltage is factory set at 52.80 volts,
unless otherwise specified. Equalize voltage is factory set at 53.50 volts, unless
otherwise specified.
(2) With Battery Charge Digital Temperature Compensation Probe: With an optional
battery charge digital temperature compensation probe installed, the MCA automatically
increases or decreases the output voltage as battery ambient temperature decreases or
increases, respectively. The float and test/equalize voltage range is the same as
without battery charge digital temperature compensation. Float voltage is factory set at
52.80 volts, at 25°C battery ambient.
Using battery and equipment manufacturers’ recommendations, the user selects the
following temperature compensation curve parameters via the MCA. Refer to the
Temperature Compensation Probe Curve provided in Figure 1.
a) The temperature compensation slope in volts/°C. Adjustable from zero to 200
millivolts/°C. Factory set at 0V/°C (DIGITAL TC OFF).
b) The maximum voltage limit in volts DC. Adjustable from float up to 58.00 volts DC,
but automatically limited to 1.0 volt below the High Voltage Shutdown setting.
Factory set at 56.50 volts.
c) The minimum voltage limit in volts DC. Adjustable from float down to 44.00 volts
DC, but automatically limited to 1.0 volt above the Low Voltage Disconnect
Reconnect setting. Factory set at 52.00 volts.
(B) Rectifier Module Current Limit: Adjustable from 10% to 121% of total system rated
capacity at maximum rated output voltage. Factory set at 100% of rated capacity, unless
otherwise specified.
The MCA automatically adjusts the current limit circuit on each Rectifier Module so that this
value is not exceeded. If a Rectifier Module fails, the MCA automatically resets each
remaining Rectifier Module's current limit point to maintain this value. The MCA also insures
that the current limit circuit on any Rectifier Module is not set above 121% of its capacity.
The default current limit setting is the sum of each installed Rectifier Modules output rating.
If an additional Rectifier Module is added to the system, the system current limit is
automatically increased by the rating of the new Rectifier Module and the new current limit
value is displayed.
Page 27 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
(C) Rectifier Module High Voltage Shutdown: Adjustable from 48.00 to 59.00 volts
DC. Factory set at 56.00 volts, unless otherwise specified.
Home
(D) System High Voltage #1 Alarm: Adjustable from 48.00 to 59.00 volts DC. Factory set at
53.30 volts, unless otherwise specified.
(E) System High Voltage #2 Alarm: Adjustable from 48.00 to 59.00 volts DC. Factory set at
54.00 volts, unless otherwise specified.
(F) Battery On Discharge Alarm: Adjustable from 40.00 to 56.00 volts DC. Factory set at
52.00 volts, unless otherwise specified.
(G) Very Low Voltage Alarm: Adjustable from 40.00 to 56.00 volts DC. Factory set at 47.00
volts, unless otherwise specified.
(H) Total Load Current Alarm: Adjustable from 0 to 60000 amperes. Factory set at 2000
amperes, unless otherwise specified.
(I) Distribution Group A Load Alarm: Adjustable from 0 to 60000 amperes. Factory set at
2000 amperes, unless otherwise specified.
(J) Distribution Group B Load Alarm: Adjustable from 0 to 60000 amperes. Factory set at
2000 amperes, unless otherwise specified.
(K) High Battery Ambient Temperature #1 Alarm (if battery charge digital temperature
compensation probe installed): Adjustable from -50°C to +99°C. You disable the feature
by selecting the setting above +99°C. Factory set to 40°C, unless otherwise specified.
(L) High Battery Ambient Temperature #2 Alarm (if battery charge digital temperature
compensation probe installed): Adjustable from -50°C to +99°C. You disable the feature
by selecting the setting above +99°C. Factory set to off, unless otherwise specified.
(M) Low Battery Ambient Temperature #1 Alarm (if battery charge digital temperature
compensation probe installed): Adjustable from -49°C to +100°C. You disable the
feature by selecting the setting below -49°C. Factory set to off, unless otherwise specified.
(N) Low Battery Ambient Temperature #2 Alarm (if battery charge digital temperature
compensation probe installed): Adjustable from -49°C to +100°C. You disable the
feature by selecting the setting below -49°C. Factory set to off, unless otherwise specified.
(O) Audible Alarm Cutoff Reset Feature: Adjustable from 0 to 15 minutes, in one minute
intervals. A zero setting disables the feature. Factory set to off (disabled), unless otherwise
specified.
(P) Rectifier Module Sequencing: The time delay between turning individual Rectifier Modules
on is adjustable from 1 to 20 seconds, or feature disabled. The Rectifier Module Sequencing
feature is factory set to 15 seconds.
(Q) Timed Test/Equalize Period (also enables/disables the manually initiated timed
test/equalize feature): Adjustable from 1 to 99 hours, in one hour intervals. When a value
is set, the feature is enabled. You disable the feature by selecting the setting above 99.
Factory set at 1 (one) hour, unless otherwise specified.
(R) Automatic Test/Equalize Period (also enables/disables the automatic test/equalize
feature): Adjustable from 0 to 15 times the discharge time period, up to a maximum of 300
hours. A zero (0) setting disables the feature. Factory set at zero (0), unless otherwise
specified.
(S) Relay Test Seconds: Adjustable from 5 to 120 seconds, in one second intervals. Factory
set at 45 seconds, unless otherwise specified.
2.1.9
MCA Audible Alarm and Audible Alarm Cutoff: The MCA contains an Audible Alarm, which is
located on the MCA Control Panel. The audible alarm sounds when any alarm condition
Page 28 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
monitored by the MCA occurs. The alarm can be manually silenced (cutoff) by pressing
a local pushbutton. A local indicator illuminates when the audible alarm has been
cutoff. The alarm remains silenced for the current alarm condition only. If another alarm
condition occurs, the audible alarm again sounds.
Home
A programmable audible alarm cutoff reset feature is provided. Once an audible alarm has been
cutoff, it automatically resets (and sounds if the alarm condition is still present) after the time
period programmed expires. If another alarm condition occurs, the audible alarm again sounds.
2.1.10 Load Sharing: Digital active load sharing circuitry in each Rectifier Module balances the load
proportionately among all rectifiers in a bay. The MCA provides a load sharing feature that
automatically balances the load among multiple bays.
2.1.11 MCA Load Share Alarm: If Rectifier Modules fail to share the load the MCA turns on a Load
Share Alarm. This alarm can be enabled or disabled by the customer. The factory default
setting is to have the MCA Load Share Alarm 'enabled'.
2.1.12 Remote On/Off (TR): The operation of any or all Rectifier Modules can be inhibited (TR) via the
MCA Control Panel or from the LMS. A Rectifier Module fail alarm is NOT issued.
2.1.13 MCA Alarm Logging: The MCA logs (with a date/time stamp) up to 500 recordable events.
2.1.14 Rectifier Module Sequencing: The MCA can be set to provide Rectifier Module Sequencing.
When the MCA senses an “AC Power is OFF to All Rectifier Modules” alarm, it turns off all
Rectifier Modules. When the “AC Power is OFF to All Rectifier Modules” alarm clears, the MCA
turns on Rectifier Module #1, then turns on the other Rectifier Modules starting with Rectifier
Module #2 every n seconds (n is user programmable from 1 to 20 seconds). If the MCA fails or
the communication link is broken during a Rectifier Module Sequencing routine, all Rectifier
Modules turn on immediately.
2.1.15 MCA Power Share Feature: The MCA Power Share feature allows you to connect the Spec.
No. 582126100 Power System to an existing DC power system instead of extending or
completely replacing the existing power system. The MCA Power Share feature provides for the
sharing of the total load in a controlled manner. When Power Share is programmed, the MCA in
the 582126100 Power System adjusts PCU output voltage per load demands to ensure proper
sharing between the two systems. For further information, request Application Note AN38.
2.1.16 MCA Alternate Current Limit Feature: The MCA Alternate Current Limit feature provides a
means to limit the output current of all rectifiers based on the state of an external signal. The
rectifiers output current is limited to a percentage of rectifier output capacity as configured by the
user. A binary input on an installed MCA I/O circuit card is used to monitor the external signal
that triggers the current limiting action.
Page 29 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
2.1.17 Local Controls: Refer to the "Operating Procedures" chapter in the Power System User
Instructions (Section 6028) for a complete description.
Location
MCA
Control
Panel
2.1.18
NAME / Description
Type
Function Select Up
Pushbutton Switch
Function Select Down
Pushbutton Switch
Function Set Enter / Move Left / Move Right Pushbutton Switch
Function Set Yes / + / i
Pushbutton Switch
Function Set No / -
Pushbutton Switch
Alarm Cutoff
Pushbutton Switch
Local Status and Alarm Indicators: Refer to the "Operating Procedures" chapter in the
Power System User Instructions (Section 6028) for a complete description.
Location
NAME / Description
Type
Message Display, Shows...
MCA
Control
Panel
•
Active Alarms or "SYSTEM OK"
•
Various Measurement Items and Values
•
Various Inventory Items
•
Various Adjustment Items and Values
•
Various Operation Items
---
• Various Configuration Items and Settings
See Paragraph 2.1.13 "MCA Display".
Alarm Cutoff
LED - yellow
Major
LED - flashing red
Minor
LED - red
AC
LED - green/red
Test/EQ
LED - yellow
Page 30 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
2.1.19
SAG582126100
Issue AH, July 4, 2012
MCA Numbering Scheme: The MCA identifies (numbers) the components of the
system as follows.
Home
MCA IDENTIFICATION NUMBER
COMPONENT
MCA NUMBERING
SCHEME (note
that each line
shown below is
separated with a
dash in the MCA
display)
NOTES
EXAMPLE
Main Power Bay
1
Bay #
MCA/Router
Main Power Bay is #1, other bays are numbered
consecutively, following the bay-to-bay cabling
scheme.
Second Bay
2
Fifth Bay
5
Bay #
Rectifier
(PCU)
MCA Relay
Circuit Card
MCA Rectifier ID#
within the Bay / # of
Rectifiers Installed
in System
Main Power Bay is #1, other bays are numbered
consecutively, following the bay-to-bay cabling
scheme.
Rectifiers are identified from 1 to 36, as they are
powered-up and recognized by the MCA.
Main Power Bay, First
Recognized Rectifier
(w/ 36 rectifiers
installed)
1-01/36
Second Power Bay,
Third Recognized
Rectifier (w/ 24
rectifiers installed)
2-03/24
Fifth Power Bay, Tenth
Recognized Rectifier
(w/ 12 rectifiers
installed)
5-10/12
Bay #
Main Power Bay is #1, other bays are numbered
consecutively, following the bay-to-bay cabling
scheme.
Card Position #
w/in Bay
Card #1 = left slot,
Card #7 = right slot.
Relay # w/in Card
Relay # (see External Alarm, Reference, and
Control Connections under WIRING
ILLUSTRATIONS)
Main Power Bay,
Relay Card in First
Slot, Relay One on
Card
1-1-1
Second Power Bay,
Relay Card in Third
Slot, Relay Four on
Card
2-3-4
Fifth Power Bay, Relay
Card in Seventh Slot,
Relay Six on Card
5-7-6
Page 31 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
MCA IDENTIFICATION NUMBER
COMPONENT
MCA NUMBERING
SCHEME (note
that each line
shown below is
separated with a
dash in the MCA
display)
Bay #
MCA I/O
Circuit Card
Card Position #
w/in Bay
NOTES
Main Power Bay is #1, other bays are numbered
consecutively, following the bay-to-bay cabling
scheme.
Card #1 = left slot,
Card #7 = right slot.
EXAMPLE
Main Power Bay, I/O
Card in First Slot
1-1
Second Power Bay,
I/O Card in Third Slot
2-3
Fifth Power Bay, I/O
Card in Seventh Slot
5-7
Fifth Bay, Top Left
Bus, Set for B
Designation
5-1B
Companion
Distribution
Bay’s
Distribution
Bus
(582140001)
Bay #
Main Power Bay is #1, other bays are numbered
consecutively, following the bay-to-bay cabling
scheme.
Distribution Bus #
w/in Bay (A or B
Designation)
Distribution Bus #1 = Top Left,
Distribution Bus #2 = Top Right,
Distribution Bus #3 = Bottom Left,
Distribution Bus #4 = Bottom Right,
A or B as set by jumper on MCA Distribution
Bus Monitoring Circuit Card.
Sixth Bay, Top Right
Bus, Set for B
Designation
6-2B
Seventh Bay, Bottom
Left Bus, Set for B
Designation
7-3B
Seventh Bay, Bottom
Right Bus, Designation
Not Set
7-4
Companion
Distribution
Bay’s
Distribution
Device
(582140001)
Type
Type = Breaker or Fuse or MISC 50-73.
Bay #
Main Power Bay is #1, other bays are numbered
consecutively, following the bay-to-bay cabling
scheme.
Distribution Point #
w/in Bay
Distribution Point =
1-12 (bottom - top, Top Left Bus, Bus #1).
13-24 (top - bottom, Top Right Bus, Bus #2).
25-36 (bottom - top, Bottom Left Bus, Bus #3).
37-48 (top - bottom, Bottom Right Bus, Bus #4).
Note that distribution components may take
more than one mounting position, designation
number is the left most mounting position.
Fifth Bay, Circuit
Breaker Mounted in
Position One, Bus 1
Set for A Designation
Breaker 5-01A
Sixth Bay, Fuse
Mounted in Position
Thirteen, Bus 2
Designation Not Set
Fuse 6-13
Note: The optional bullet-device fuse panel is
displayed as MISC 50-73.
Page 32 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
Home
2.1.20 MCA Display: Presented next are illustrations from the MCA Menu Tree (Section
5886). Refer to the latest version of Section 5886 for the most recent MCA Menu Tree.
Refer to the Power System User Instructions (Section 6028) for a complete description of menu
items.
Page 33 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
The User navigates Lines 3 and 4 of the MCA Display using the Keypad on the MCA Control Panel.
(The following indicates the actual text shown on each line of Lines 3 and 4 of the MCA Display, Line
4 also displays applicable navigation key codes, see previous page for explanation of codes.)
MAIN ALARM MENU
INITIALIZATION MENU
############ WAIT ##
1
A
V###########
2
2A
B
CHECK VALUES BEFORE
STARTING
C
FLOAT SETPOINT
= vv.vvV
D
TEST/EQUALIZE
= vv.vvV
E
HI VOLTAGE SHUTDOWN
= vv.vvV
F
PCU CURRENT LIMIT
= aaaaaA
or
PCU CURRENT LIMIT
POWER SHARE
or
PCU CURRENT LIMIT
ALT. LIMIT
G
H
I
J
SYSTEM HI VOLTAGE #1
= vv.vvV
L
DISTRIBUTION GROUP A
= aaaaaA
M
DISTRIBUTION GROUP B
= aaaaaA
N
HIGH TEMPERATURE #1
= ttt°C/F
or
NO HIGH TEMPERATURE
#1 ALARM
O
HIGH TEMPERATURE #2
= ttt°C/F
or
NO HIGH TEMPERATURE
#2 ALARM
Q
R
S
T
U
LOW TEMPERATURE #1
= ttt°C/F
or
NO LOW TEMPERATURE
#1 ALARM
LOW TEMPERATURE #2
= ttt°C/F
or
NO LOW TEMPERATURE
#2 ALARM
AUDIBLE SILENT TIME
= mm MINUTES
or
AUDIBLE ALARMS STAY
SILENCED
PCU SEQUENCING IS
DISABLED
or
PCU SEQUENCING DELAY
= ss SECONDS
TEST EQUALIZE IS DISABLED
or
MANUAL TEST/EQUALIZE
= hh HOURS
or
TEST/EQUALIZE STOP
IS MANUAL
or
TURN OFF POWER SHARE
or
TURN OFF ALTERNATIVE
CURRENT LIMIT
AUTO EQUALIZE IS
DISABLED
or
AUTO EQUALIZE FOR ##
x DISCHARGE
or
TURN OFF POWER SHARE
or
TURN OFF ALTERNATIVE
CURRENT LIMIT
V
4
SYSTEM BATTERY IS ON
DISCHARGE
5
SYSTEM HIGH VOLTAGE
#1 ALARM
6
SYSTEM HIGH VOLTAGE
#2 ALARM
7
1 SYSTEM BREAKER OR
FUSE ALARM
or
### SYSTEM BREAKER &
FUSE ALARMS
12
BATTERY ON DISCHARGE
= vv.vvV
VERY LOW VOLTAGE
= vv.vvV
K
P
SYSTEM VOLTAGE IS
VERY LOW
11
NO TEMPERATURE
COMPENSATION
or
TEMPERATURE SLOPE
= 0.vvvV/ °C/F
or
TURN OFF POWER SHARE
or
TURN OFF ALTERNATIVE
CURRENT LIMIT
40
55
66
AC POWER IS OFF TO
ALL PCUs
1 PCU
HAS FAILED
or
### PCUs
HAVE FAILED
or
NO PCUs ARE
IN INVENTORY
1 DIST. PANEL
HAS FAILED
or
## DIST. PANELS
HAVE FAILED
or
NO DIST. PANELS ARE
IN INVENTORY
1 I/O BOARD
HAS FAILED
or
## I/O BOARDS
HAVE FAILED
or
NO I/O BOARDS ARE
IN INVENTORY
1 ROUTER
HAS FAILED
or
## ROUTERS
HAVE FAILED
or
NO ROUTERS ARE
IN INVENTORY
8
9
10
13
14
67
PCU B#-ID#/N#
ON STANDBY
29
PCU B#-ID#/N#
THERMAL LIMIT
52
DIST. PANEL B#-P#A/B
NO RESPONSE
30
PCU B#-ID#/N#
THERMAL STOP
53
GO TO DISTRIBUTION
ALARM MENU
PCU B#-ID#/N#
HIGH AMBIENT
PCU B#-ID#/N#
LOAD SHARE
54
GO BACK TO MENU TREE
BEGINNING
34
GO TO MAIN ALARM
MENU
35
GO BACK TO MENU TREE
BEGINNING
36
I/O BOARD ALARM MENU
I/O BOARD B#-P#
FAILURE
ROUTER ALARM MENU
ROUTER B#
FAILURE
GO BACK TO MENU TREE
BEGINNING
95
96
MONITORING DOES NOT
RESPOND
GO BACK TO MENU TREE
BEGINNING
28
PCU ALARM MENU
PCU B#-ID#/N#
FAILURE
### REMOTE PCUS
HAVE FAILED
GO TO MAIN ALARM
MENU
MONITORING
INFORMATION
or
Monitoring Info
LED Messages
X
DIST. PANEL B#-P#A/B
A/B CHANGED
51
69
94
GO TO FUNCTION MENU
DIST. PANEL B#-P#A/B
LVD FAILURE
50
68
MINOR MONITORING
ALARM(S)
or
Monitoring Minor
LED Messages
104
48
DIST. PANEL B#-P#A/B
PROCESSOR
DIST. PANEL B#-P#A/B IS
DUPLICATED
PCU B#-ID#/N#
1 FAN SPEED
PCU B#-ID#/N#
2+ FANS SPEED
PCU B#-ID#/N#
NO VOLT SENSE
PCU B#-ID#/N#
DUPLICATED
37
PCU B#-ID#/N#
NO RESPONSE
38
GO TO PCU ALARM MENU
39
GO BACK TO MENU TREE
BEGINNING
I/O BOARD ALARM DETAIL MENU
93
MINIMUM COMPENSATION
= vv.vvV
F/CB/PI B#-P#A/B
OVER CURRENT
PCU B#-ID#/N#
INHIBITED
GO BACK TO MENU TREE
BEGINNING
MAJOR MONITORING
ALARM(S)
or
Monitoring Major
LED Messages
W
POSITION B#-P#A/B
TYPE UNKNOWN
47
27
58
TEMPERATURE SENSOR
NO SIGNAL
101
46
PCU B#-ID#/N#
POWER FACTOR
PCU B#-ID#/N#
DC/DC CONV.
GO BACK TO MENU TREE
BEGINNING
GO TO MAIN ALARM
MENU
92
DISTRIBUTION GROUP B
LOAD ALARM
PCU B#-ID#/N#
AC PHASE LOST
49
57
LOW TEMPERATURE #2
ALARM
DISTRIBUTION GROUP A
LOAD ALARM
POSITION B#-P#A/B
NOT FOUND
or
POSITION NOT FOUND
PANEL B#-P#A/B
PCU B#-ID#/N#
FUSE/BREAKER
33
56
45
26
DISTRIBUTION ALARM MENU
DIST. PANEL B#-P#A/B
41 FAILURE
43
DISTRIBUTION ALARM DETAIL MENU
DIST. PANEL B#-P#A/B
DISCONNECTED
or
44
DIST. PANEL B#-P#A/B
RECONNECT?
GO TO MAIN ALARM
MENU
32
91
100
25
GO BACK TO MENU TREE
BEGINNING
LOW TEMPERATURE #1
ALARM
TOTAL LOAD CURRENT
ALARM
24
17
90
99
PCU B#-ID#/N#
AC LINE HIGH
23
16
80
CONTROLLER FAILURE
####
THE CONTROLLER IS
INITIALIZING
22
31
HIGH TEMPERATURE #2
ALARM
98
PCU B#-ID#/N#
AC LINE OFF
PCU B#-ID#/N#
AC LINE LOW
GO TO MAIN ALARM
MENU
42
PCU B#-ID#/N#
H.V. SHUTDOWN
21
1 REMOTE PCU
HAS FAILED
89
97
FUSE ALARM MENU
F/CB/PI B#-P#A/B
IS OPEN
PCU ALARM DETAIL MENU
PCU B#-ID#/N#
EMERG. STOP
20
15
88
THE DISPLAY DOES NOT
RESPOND
IT IS NOW hh:mm:ss
dd-mon-yy
ALARM LIMIT vv.vvV
NOW AT vv.vvV
HIGH TEMPERATURE #1
ALARM
102
READY TO START THE
SYSTEM NOW?
3A, 4A, 5A, 6A
79
78
103
Z
19
1 RELAY BOARD
HAS FAILED
or
## RELAY BOARDS
HAVE FAILED
or
NO RELAY BOARDS ARE
IN INVENTORY
MAXIMUM COMPENSATION
= vv.vvV
Y
18
HI VOLTAGE SHUTDOWN
INPUT ACTIVE
ALTERNATE CURRENT
LIMIT ACTIVE
3
SYSTEM HI VOLTAGE #2
= vv.vvV
TOTAL LOAD CURRENT
= aaaaaA
EMERGENCY STOP
INPUT ACTIVE
59
60
61
62
81
RELAY ALARM MENU
RELAY BOARD B#-P#
FAILURE
GO TO MAIN ALARM
MENU
GO BACK TO MENU TREE
BEGINNING
63
I/O BOARD B#-P#
NO RESPONSE
64
GO TO I/O BOARD
ALARM MENU
65
GO BACK TO MENU TREE
BEGINNING
88A, 89A, 90A, 91A
70
ALARM LIMIT ttt°C/F
NOW AT ttt°C/F
Binary Input Customer
Text Messages
I/O BOARD B#-P#
OVER CURRENT
I/O BOARD B#-P#
PROCESSOR
I/O BOARD B#-P# IS
DUPLICATED
ROUTER ALARM DETAIL MENU
ROUTER B# REMOTE
SENSE OPEN
71
ROUTER B# INTERNAL
SENSE OPEN
72
ROUTER B# PROCESSOR
73
ROUTER B# REPORTS AN
ILLEGAL NODE
74
ROUTER B# IS
DUPLICATED
75
ROUTER B#
NO RESPONSE
76
GO TO ROUTER ALARM
MENU
77
GO BACK TO MENU TREE
BEGINNING
RELAY ALARM DETAIL MENU
RELAY B#-P#-R# IS
STUCK
RELAY BOARD B#-P#
83
PROCESSOR
RELAY BOARD B#-P# IS
84
DUPLICATED
82
99A, 100A, 101A
ALARM LIMIT aaaaaA
NOW AT aaaaaA
85
86
87
RELAY BOARD B#-P#
NO RESPONSE
GO TO RELAY ALARM
MENU
GO BACK TO MENU TREE
BEGINNING
NORMAL DISPLAY MENU
or
REPLACE ### PCUs?
AUTO IN ###
A
to
(Sheet 2 of 4)
Page 34 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
from
(Sheet 1 of 4)
A
FUNCTION MENU
(cont'd on next page)
105
VIEW THE SYSTEM
MEASUREMENTS
FLOAT MODE IS ACTIVE
SET TEST/EQ?
or
TEST/EQ MODE ACTIVE
SET FLOAT?
133
134
or
TEST/EQUALIZE INPUT
IS ACTIVE
or
TURN OFF POWER SHARE
or
TURN OFF ALTERNATE
CURRENT LIMIT
SAG582126100
Issue AH, July 4, 2012
ROUTER VOLTAGE MENU
MEASUREMENT MENU
106
SYSTEM OUTPUT SENSE
vv.vvV (REM)
or
SYSTEM OUTPUT SENSE
vv.vvV (AVG)
107
108
ROUTER B# REMOTE
SENSE vv.vvV
ROUTER B# INTERNAL
SENSE vv.vvV
118
GO TO MEASUREMENT
MENU
GO BACK TO MENU TREE
BEGINNING
120
GO TO SYSTEM LOAD
MENU
121
GO BACK TO MENU TREE
BEGINNING
DISTRIBUTION LOAD MENU
DIST. PANEL B#-P#A/B
LOAD aaaaaA
I/O BOARD B#-P#
LOAD aaaaaA
TOTAL SYSTEM
LOAD aaaaaA
TOTAL PCU OUTPUT
aaaaaA
or
TOTAL PCU/RECTIFIER
aaaaaA
109
130
TEMPERATURE SENSOR
ttt°C/F
112
131
GO TO FUNCTION MENU
TOTAL DISTRIBUTION
LOAD aaaaaA
or
TOTAL AUXILIARY
LOAD aaaaaA
132
GO BACK TO MENU TREE
BEGINNING
113
DISTRIBUTION GROUP A
LOAD aaaaaA
122
F/CB/PI B#-P#A/B
LOAD aaaaaA
114
DISTRIBUTION GROUP B
LOAD aaaaaA
123
GO TO DISTRIBUTION
LOAD MENU
REMOTE SYSTEM
LOAD aaaaaA
GO TO MEASUREMENT
MENU
124
GO BACK TO MENU TREE
BEGINNING
111
125
INVENTORY MENU
135
VIEW THE SYSTEM
INVENTORY
B
to
(Sheet 3 of 4)
149
150
161
171
181
191
192
199
200
1 PCU IS
REPORTING
or
### PCUs ARE
REPORTING
or
NO PCUs ARE
INSTALLED
1 PCU POSITION
IS EMPTY
or
### PCU POSITIONS
ARE EMPTY
or
NO PCU POSITIONS
ARE EMPTY
or
TOTAL PCU POSITIONS
= ###
1 DIST. PANEL IS
REPORTING
or
## DIST. PANELS ARE
REPORTING
or
NO DIST. PANELS ARE
INSTALLED
1 I/O BOARD IS
REPORTING
or
## I/O BOARDS ARE
REPORTING
or
NO I/O BOARDS ARE
INSTALLED
1 ROUTER IS
REPORTING
or
## ROUTERS ARE
REPORTING
or
NO ROUTERS ARE
INSTALLED
1 RELAY BOARD IS
REPORTING
or
## RELAY BOARDS ARE
REPORTING
or
NO RELAY BOARDS ARE
INSTALLED
TEMPERATURE SENSOR
REPORTING
or
NO TEMPERATURE
SENSOR
MONITORING IS
REPORTING
or
NO MONITORING IS
INSTALLED
SENSE VOLTAGE IS
REMOTE INPUT
or
SENSE VOLTAGE IS
AVERAGED
CONTROLLER ASSEMBLY
############
210
UPDATE THE INVENTORY
211
GO TO FUNCTION MENU
212
GO BACK TO MENU TREE
BEGINNING
110
SYSTEM LOAD MENU
115
116
119
DISTRIBUTION LOAD DETAIL MENU
PCU INVENTORY DETAIL MENU
117
GO BACK TO MENU TREE
BEGINNING
139
PCU CURRENT MENU
140
126
PCU B#-ID#/N#
aaaaaA
127
128
129
B#-ID#/N# SERIAL
#####################
B#-ID#/N# BOOT
#####################
RECTIFIER OUTPUT
aaaaaA
GO TO MEASUREMENT
MENU
143
GO BACK TO MENU TREE
BEGINNING
144
PSC B#-ID# SERIAL #
#####################
145
PSC B#-ID# BOOTCODE
#####################
146
PSC B#-ID# SOFTWARE
#####################
PCU INVENTORY MENU
136
141
B#-ID#/N# ASSY.
#####################
PCU B#-ID#/N#
RATED aaaaaA
142
B#-ID#/N# SW VER
#####################
PSC B#-ID# ASSEMBLY
#####################
137
GO TO INVENTORY MENU
138
GO BACK TO MENU TREE
BEGINNING
147
GO TO PCU
INVENTORY
DISTRIBUTION INVENTORY MENU
148
GO BACK TO MENU TREE
BEGINNING
151
PANEL B#-P#A/B INCLUDES
1 POINT
or
PANEL B#-P#A/B INCLUDES
## POINTS
DISTRIBUTION INVENTORY DETAIL MENU
154
POINT B#-P#A/B IS A
F/CB/PI
152
GO TO INVENTORY MENU
155
PANEL B#-P#A/B ASSEMBLY
############
153
GO BACK TO MENU TREE
BEGINNING
156
PANEL B#-P#A/B SERIAL #
############
I/O BOARD INVENTORY MENU
157
PANEL B#-P#A/B BOOTCODE
############
158
PANEL B#-P#A/B SOFTWARE
############
159
GO TO DISTRIBUTION
INVENTORY
160
GO BACK TO MENU TREE
BEGINNING
162
I/O BOARD B#-P# IS
INSTALLED
163
GO TO INVENTORY MENU
164
GO BACK TO MENU TREE
BEGINNING
ROUTER INVENTORY MENU
172
ROUTER B# IS
INSTALLED
173
GO TO INVENTORY MENU
174
GO BACK TO MENU TREE
BEGINNING
RELAY INVENTORY MENU
182
RELAY BOARD B#-P# IS
INSTALLED
183
GO TO INVENTORY MENU
I/O BOARD INVENTORY DETAIL MENU
165
BOARD B#-P# ASSEMBLY
############
166
BOARD B#-P# SERIAL #
############
167
BOARD B#-P# BOOTCODE
############
168
BOARD B#-P# SOFTWARE
############
GO BACK TO MENU TREE
BEGINNING
169
GO TO I/O BOARD
INVENTORY
MONITORING INVENTORY DETAIL MENU
170
GO BACK TO MENU TREE
BEGINNING
MONITORING ASSEMBLY
#####################
MONITORING SERIAL #
#####################
175
184
193
194
ROUTER INVENTORY DETAIL MENU
ROUTER B# ASSEMBLY
############
195
MONITORING BOOTCODE
#####################
196
MONITORING SOFTWARE
#####################
177
197
GO TO INVENTORY MENU
178
GO BACK TO MENU TREE
BEGINNING
ROUTER B# SOFTWARE
############
198
179
GO TO ROUTER
INVENTORY
180
GO BACK TO MENU TREE
BEGINNING
176
CONTROLLER INVENTORY DETAIL MENU
201
202
203
204
205
CONTROLLER SERIAL #
#####################
CONTROLLER BOOTCODE
#####################
CONTROLLER SOFTWARE
#####################
DISPLAY ASSEMBLY
#####################
DISPLAY SERIAL #
#####################
206
DISPLAY BOOTCODE
#####################
207
DISPLAY SOFTWARE
#####################
208
GO TO INVENTORY MENU
209
GO BACK TO MENU TREE
BEGINNING
ROUTER B# SERIAL #
############
ROUTER B# BOOTCODE
############
RELAY INVENTORY DETAIL MENU
BOARD B#-P# ASSEMBLY
############
185
186
BOARD B#-P# SERIAL #
############
186
BOARD B#-P# BOOTCODE
############
188
BOARD B#-P# SOFTWARE
############
189
GO TO RELAY BOARD
INVENTORY
190
GO BACK TO MENU TREE
BEGINNING
Page 35 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
from
(Sheet 2 of 3)
B
FUNCTION MENU
(cont'd from previous page)
ADJUST THE SYSTEM
213
VOLTS & AMPS
225
239
226
227
ADJUST THE ALARM
SETPOINTS
228
TURN PCUs ON OR OFF
240
243
323
CHANGE CONFIGURATION
PARAMETERS
VERIFY TEST, ESTOP,
& HVS INPUTS
or
TEST SHUTDOWN INPUT
IS ON
or
EMERGENCY STOP INPUT
IS ON
or
HI VOLTAGE SHUTDOWN
INPUT IS ON
324
VIEW THE ALARM LOG
437
PCU B#-ID#/N#
RECOGNIZED
or
DSM B#-P#A/B
RECOGNIZED
or
I/O B#-P#
RECOGNIZED
or
CRM B#
RECOGNIZED
or
RCB B#-P#
RECOGNIZED
438
241
GO TO FUNCTION MENU
242
GO BACK TO MENU TREE
BEGINNING
229
230
244
251
252
253
CHANGE I/O BOARD
PARAMETERS
AUDIBLE SILENT TIME
= mm MINUTES
or
AUDIBLE ALARMS STAY
SILENCED
to
(Sheet 4 of 4)
255
310
311
315
317
318
319
320
320A
264
236
237
238
262
265
266
267
268
269
270
271
272
273
GO TO FUNCTION MENU
GO BACK TO MENU TREE
BEGINNING
274
275
AUTO EQUALIZE IS
DISABLED
or
AUTO EQUALIZE FOR ##
x DISCHARGE
or
END AUTO EQUALIZE IN
hhh.hh HOURS
245
246
247
or
TURN OFF POWER SHARE
or
TURN OFF ALTERNATIVE
CURRENT LIMIT
DEFINE RELAY
FUNCTIONS
START RELAY FUNCTION
TEST
or
TIME PER FUNCTION
= hh:mm:ss
or
TIME PER FUNCTION
NO TIMEOUT
or
AUTOMATICALLY TEST
ALL FUNCTIONS
or
TEST RELAY FUNCTION
A#
or
STOP RELAY FUNCTION
TEST
or
TESTING FUNCTION A#
= hh:mm:ss
or
TESTING FUNCTION A#
NO TIMEOUT
ASSIGN RELAYS TO
FUNCTIONS
248
I/O BOARD
CONFIGURATION MENU
ANALOG INPUT B#-P# IS
DISTRIBUTION
or
ANALOG INPUT B#-P# IS
AUXILIARY
276
277
278
279
ANALOG INPUT B#-P#
50mV = aaaaaA
ANALOG OUTPUT B#-P#
50mV = aaaaaA
BINARY INPUT B#-P#-I#
ALARM = CLOSED
or
BINARY INPUT B#-P#-I#
ALARM = OPEN
280
281
282
283
249 GO TO CONFIGURE MENU
250
GO BACK TO MENU TREE
BEGINNING
RELAY FUNCTION MENU
256
DEFINE RELAY
FUNCTION A#
257
GO TO CONFIGURE MENU
258
290
RELAY ASSIGNMENT MENU
291
312
ASSIGN RELAY B#-P#-R#
FUNCTION A#
292
313
GO TO CONFIGURE MENU
314
GO BACK TO MENU TREE
BEGINNING
293
294
295
296
297
298
299
to
D
300
(This sheet)
301
MAXIMUM COMPENSATION
= vv.vvV
MINIMUM COMPENSATION
= vv.vvV
NOW DISPLAYING °C/F
SET TO °C/F?
IT IS NOW hh:mm:ss
dd-mon-yy
from
E
(This sheet)
302
303
304
to
ERASE THE ALARM LOG
PCU MAPPING MENU
(NS702/801 ONLY)
CHANGE NETWORK
ADDRESSES
ARRANGE PCU ORDER
321A
BAY ##
322
GO TO FUNCTION MENU
321B
GO TO CONFIGURE MENU
321C
GO BACK TO MENU TREE
BEGINNING
GO BACK TO MENU TREE
BEGINNING
/_1 ROUTER FAILURE
289
NO TEMPERATURE
COMPENSATION
or
TEMPERATURE SLOPE
= 0.vvvV/°C/F
F
(This sheet)
from
G
(This sheet)
/_1 PCU FAILURE
'MAJOR' TYPE
/_2+ PCU FAILURES
'MAJOR' TYPE
/_1 PCU FAILURE
'MINOR' TYPE
/_2+ PCU FAILURES
'MINOR' TYPE
/_NO PCUs ARE
IN INVENTORY
/_1 DIST. PANEL
FAILURE
/_2+ DIST. PANEL
FAILURES
/_NO DIST. PANELS
IN INVENTORY
/_1 I/O BOARD
FAILURE
/_2+ I/O BOARD
FAILURES
/_NO I/O BOARDS ARE
IN INVENTORY
/_2+ ROUTER FAILURES
288
305
306
307
308
309
214
215
/_EMERGENCY STOP
INPUT ACTIVE
/_HI VOLTAGE SHUTDOWN
INPUT ACTIVE
/_ALTERNATE CURRENT
LIMIT ACTIVE
/_SYSTEM VOLTAGE IS
VERY LOW
/_SYSTEM BATTERY ON
DISCHARGE
/_SYSTEM HIGH VOLTAGE
#1 ALARM
/_SYSTEM HIGH VOLTAGE
#2 ALARM
/_1 SYSTEM BREAKER OR
FUSE ALARM
/_2+ SYSTEM BREAKER &
FUSE ALARMS
/_AC POWER IS OFF TO
1 PCU
/_AC POWER IS OFF TO
2+ PCUs
/_AC POWER IS OFF TO
ALL PCUs
/_1 PCU FAILURE
ANY TYPE
/_2+ PCU FAILURES
ANY TYPE
284
287
GO BACK TO MENU TREE
BEGINNING
CHECKED CONDITIONS
DE-ENERGIZE
or
CHECKED CONDITIONS
ENERGIZE
285
286
321
322A
261
261A
263
or
TURN OFF POWER SHARE
or
TURN OFF ALTERNATIVE
CURRENT LIMIT
316
260
HIGH TEMPERATURE #1
= ttt°C/F
or
NO HIGH TEMPERATURE
#1 ALARM
HIGH TEMPERATURE #2
= ttt°C/F
or
NO HIGH TEMPERATURE
#2 ALARM
LOW TEMPERATURE #1
= ttt°C/F
or
NO LOW TEMPERATURE
#1 ALARM
LOW TEMPERATURE #2
= ttt°C/F
or
NO LOW TEMPERATURE
#2 ALARM
or
TURN OFF POWER SHARE
or
TURN OFF ALTERNATIVE
CURRENT LIMIT
254
BATTERY ON DISCHARGE
= vv.vvV
VERY LOW VOLTAGE
= vv.vvV
TOTAL LOAD CURRENT
= aaaaaA
DISTRIBUTION GROUP B
= aaaaaA
235
TEST EQUALIZE IS DISABLED
or
MANUAL TEST/EQUALIZE
= hh HOURS
or
TEST/EQUALIZE STOP
IS MANUAL
or
END TEST/EQUALIZE IN
hh.hh HOURS
259
232
234
PCU SEQUENCING IS
DISABLED
or
PCU SEQUENCING DELAY
= ss SECONDS
SYSTEM HI VOLTAGE #2
= vv.vvV
DISTRIBUTION GROUP A
= aaaaaA
233
SYSTEM ADJUSTMENT MENU
RELAY FUNCTION DEFINITION MENU
231
CONFIGURE MENU
GO BACK TO MENU TREE
BEGINNING
C
PCU ENABLE MENU
PCU B#-ID#/N# ON
TURN IT OFF?
or
PCU B#-ID#/N# OFF
TURN IT ON?
ALARM ADJUSTMENT MENU
SYSTEM HI VOLTAGE #1
= vv.vvV
/_NO ROUTERS ARE
IN INVENTORY
/_1 RELAY BOARD
FAILURE
/_2+ RELAY BOARD
FAILURES
/_NO RELAY BOARDS ARE
IN INVENTORY
/_HIGH TEMPERATURE #1
ALARM
/_HIGH TEMPERATURE #2
ALARM
/_LOW TEMPERATURE #1
ALARM
/_LOW TEMPERATURE #2
ALARM
/_TEMPERATURE SENSOR
NO SIGNAL
/_MAJOR MONITORING
ALARM(S)
/_MINOR MONITORING
ALARM(S)
/_All Monitoring LED
Messages
/_MONITORING DOES NOT
RESPOND
/_CONTROLLER FAILURE
216
217
218
218A
219
FLOAT SETPOINT
= vv.vvV
TEST/EQUALIZE
= vv.vvV
POWER SHARE IS OFF
TURN IT ON?
or
POWER SHARE IS ON
TURN IT OFF?
or
ALT. LIMIT IS OFF
TURN IT ON?
or
ALT. LIMIT IS ON
TURN IT OFF?
or
TURN OFF POWER SHARE
or
TURN OFF ALTERNATIVE
CURRENT LIMIT
or
TURN OFF TEMPERATURE
COMPENSATION
PS INITIAL CAPACITY
LIMIT = ###%
PS VOLTAGE OFFSET
= v.vV
ALTERNATE CURRENT
LIMIT = ###%
HI VOLTAGE SHUTDOWN
= vv.vvV
TEST H.V. SHUTDOWN
= vv.vvV
220
LOSS IS POSSIBLE. GO
AHEAD ANYWAY?
221
PCU CURRENT LIMIT
= aaaaaA
or
PCU CURRENT LIMIT
ALT. LIMIT
or
PCU CURRENT LIMIT
POWER SHARE
222
100% PCU CURRENT IS
aaaaaA
223
GO TO FUNCTION MENU
224
GO BACK TO MENU TREE
BEGINNING
NETWORK ADDRESS MENU
from
D
(This sheet)
320B
320C
320D
to
E
(This sheet)
from
320E
###.###.###.###
GATEWAY
320F
VALIDATE THE ADDRESS
CHANGES?
or
UPDATE/RESTART LMS
WITH CHANGES?
or
THE CHANGES WERE
REJECTED
320G
GO TO CONFIGURE MENU
320H
GO BACK TO MENU TREE
BEGINNING
F
(This sheet)
321D
321E
to
G
(This sheet)
##.##.##.##.##
MAC ADDRESS
###.###.###.###
IP ADDRESS
###.###.###.###
NET MASK
SN# IN SLOT
POSITION ##
SAVE PCU MAPPING
or
DUPLICATE MAPPING
DETECTED
321F
GO TO CONFIGURE MENU
321G
GO BACK TO MENU TREE
BEGINNING
/_THE CONTROLLER IS
INITIALIZING
/_TOTAL LOAD CURRENT
ALARM
/_DIST. GROUP A
LOAD ALARM
/_DIST. GROUP B
LOAD ALARM
/_THE DISPLAY DOES
NOT RESPOND
/_TEST/EQUALIZE MODE
IS ACTIVE
/_THE AUDIBLE ALARM
IS ACTIVE
/_AUDIBLE ALARMS ARE
SILENCED
GO TO RELAY FUNCTION
MENU
GO BACK TO MENU TREE
BEGINNING
Page 36 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
from
(Sheet 3 of 5)
E
MCA ALARM
LOG DETAIL MENU
ALARM LOG MENU
325
356
dd-mon-yy hh:mm:ss /
CONTROLLER
326
PCU ALARM
LOG DETAIL MENU
dd-mon-yy hh:mm:ss /
B#-SN#
384
dd-mon-yy hh:mm:ss /
PANEL B#-P#A/B
400
dd-mon-yy hh:mm:ss /
I/O B#-P#
411
dd-mon-yy hh:mm:ss /
ROUTER B#
DISTRIBUTION ALARM
LOG DETAIL MENU
385
386
425
dd-mon-yy hh:mm:ss /
RELAY B#-P#
435
GO TO FUNCTION MENU
436
GO BACK TO MENU TREE
BEGINNING
387
388
389
391
412
413
414
415
416
417
418
419
420
421
422
ROUTER ALARM
LOG DETAIL MENU
ROUTER B#
NO ALARMS
ROUTER B# REMOTE
SENSE OPEN
ROUTER B# INTERNAL
SENSE OPEN
ROUTER B# PROCESSOR
FAILURE
ROUTER B# REPORTS AN
ILLEGAL NODE
ROUTER B# IS
DUPLICATED
423
GO TO ALARM LOG MENU
424
GO BACK TO MENU TREE
BEGINNING
426
RELAY ALARM
LOG DETAIL MENU
RELAY BOARD B#-P#
NO ALARMS
RELAY B#-P#-R# IS
STUCK
DIST. PANEL B#-P#A/B
LVD FAILURE
392
DIST. PANEL B#-P#A/B
A/B CHANGED
394
395
ROUTER B# DOES NOT
RESPOND
ROUTER B# REMOTE
SENSE vv.vvV
ROUTER B# INTERNAL
SENSE vv.vvV
SYSTEM OUTPUT SENSE
vv.vvV
TOTAL LOAD CURRENT
aaaaaA
428
429
430
431
432
359
360
361
362
363
364
365
366
367
SYSTEM OUTPUT SENSE
vv.vvV
397
TOTAL LOAD CURRENT
aaaaaA
398
GO TO ALARM LOG MENU
399
GO BACK TO MENU TREE
BEGINNING
368
369
370
371
372
373
374
I/O BOARD ALARM
LOG DETAIL MENU
401
402
403
405
406
407
RELAY BOARD B#-P#
PROCESSOR
408
RELAY BOARD B#-P# IS
DUPLICATED
RELAY BOARD B#-P#
NO RESPONSE
SYSTEM OUTPUT SENSE
vv.vvV
375
I/O BOARD B#-P#
NO ALARMS
376
I/O BOARD B#-P#
BINARY I#
I/O BOARD B#-P#
OVER CURRENT
I/O BOARD B#-P#
PROCESSOR
I/O BOARD B#-P#
IS DUPLICATED
377
378
I/O BOARD B#-P#
NO RESPONSE
379
SYSTEM OUTPUT SENSE
vv.vvV
TOTAL LOAD CURRENT
aaaaaA
380
409
GO TO ALARM LOG MENU
410
GO BACK TO MENU TREE
BEGINNING
PCU B#-SN#
H.V. SHUTDOWN
PCU B#-SN#
AC LINE OFF
PCU B#-SN#
AC LINE LOW
PCU B#-SN#
AC LINE HIGH
PCU B#-SN#
AC PHASE LOST
PCU B#-SN#
POWER FACTOR
PCU B#-SN#
DC/DC CONV.
PCU B#-SN#
FUSE/BREAKER
PCU B#-SN#
INHIBITED
PCU B#-SN#
ON STANDBY
PCU B#-SN#
THERMAL LIMIT
PCU B#-SN#
THERMAL STOP
PCU B#-SN#
HIGH AMBIENT
PCU B#-SN#
LOAD SHARE
PCU B#-SN#
1 FAN SPEED
PCU B#-SN#
2+ FANS SPEED
PCU B#-SN#
NO VOLT SENSE
PCU B#-SN#
DUPLICATED
PCU B#-SN#
NO RESPONSE
PCU B#-SN#
TURNED ON
or
PCU B#-SN#
TURNED OFF
PCU B#-SN#
aaaaaA
SYSTEM OUTPUT SENSE
vv.vvV
327
328
328A
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
HI VOLTAGE SHUTDOWN
INPUT ACTIVE
ALTERNATE CURRENT
LIMIT ACTIVE
SYSTEM VOLTAGE IS
VERY LOW
SYSTEM BATTERY IS ON
DISCHARGE
SYSTEM HIGH VOLTAGE
#1 ALARM
SYSTEM HIGH VOLTAGE
#2 ALARM
NO PCUs ARE
IN INVENTORY
NO DIST. PANELS ARE
IN INVENTORY
NO ROUTERS ARE
IN INVENTORY
NO RELAY BOARDS ARE
IN INVENTORY
HIGH TEMPERATURE #1
ALARM
HIGH TEMPERATURE #2
ALARM
LOW TEMPERATURE #1
ALARM
LOW TEMPERATURE #2
ALARM
TEMPERATURE SENSOR
NO SIGNAL
MAJOR MONITORING
ALARM(S)
MINOR MONITORING
ALARM(S)
Monitoring LED
Messages
MONITORING DOES NOT
RESPOND
CONTROLLER FAILURE
####
THE CONTROLLER IS
INITIALIZING
TOTAL LOAD CURRENT
ALARM
GROUP A LOAD CURRENT
ALARM
GROUP B LOAD CURRENT
ALARM
THE DISPLAY DOES NOT
RESPOND
SYSTEM OUTPUT SENSE
vv.vvV
TOTAL LOAD CURRENT
aaaaaA
381
TOTAL LOAD CURRENT
aaaaaA
382
GO TO ALARM LOG MENU
353
383
GO BACK TO MENU TREE
BEGINNING
354
GO TO ALARM LOG MENU
355
GO BACK TO MENU TREE
BEGINNING
352
TOTAL LOAD CURRENT
aaaaaA
433
GO TO ALARM LOG MENU
434
GO BACK TO MENU TREE
BEGINNING
439
358
DIST. PANEL B#-P#A/B
PROCESSOR
DIST. PANEL B#-P#A/B IS
DUPLICATED
DIST. PANEL B#-P#A/B
NO RESPONSE
396
404
427
DIST. PANEL B#-P#A/B
NO ALARMS
DIST. PANEL B#-P#A/B
DISCONNECTED
POSITION B#-P#A/B
IS OPEN
POSITION B#-P#A/B
NOT FOUND
or
POSITION NOT FOUND
PANEL B#-P#A/B
POSITION B#-P#A/B
TYPE UNKNOWN
POSITION B#-P#A/B
OVER CURRENT
391
393
357
PCU B#-SN#
NO ALARMS
PCU B#-SN#
EMERG. STOP
SYSTEM CONTROLLER
NO ALARMS
EMERGENCY STOP
INPUT ACTIVE
PCU REPLACEMENT
MENU
REPLACE ### PCUs?
AUTO IN ###
440
REPLACE ### PCUs
MANUALLY?
444
REPOPULATE ### SLOTS?
AUTO IN ### ?
MANUAL PCU
REPLACEMENT MENU
(NS702/801 only)
441
BAY ###
442
REPLACE PCU B#-P#
443 REPLACE PCU B#-P# W/
SN#
Page 37 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
2.1.21
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
Home
External Control Circuits
(A) Remote Test/Equalize: All Rectifiers can be placed into the test/equalize mode by
applying a loop closure signal. The Rectifiers operate in the float mode when the loop
closure signal is absent.
(B) Remote High Voltage Shutdown: The high voltage shutdown circuit on all Rectifiers, as
described in PD588705000, can be activated by applying a loop closure signal.
(C) Rectifier Emergency Shutdown and Fire Alarm Disconnect: The Rectifiers can be
inhibited by applying a loop closure signal. Manual restart is required.
(D) External "System Voltage" Meter Reading: Leads can be extended from the MCA to an
external voltage source. This is the voltage source the MCA monitors for system alarms
and displays as "System Output Voltage".
(E) Test Input: The High Voltage Shutdown and/or Rectifier Emergency Stop circuits can be
tested without affecting the system by applying a test loop closure signal before applying
the Remote High Voltage Shutdown or Rectifier Emergency Shutdown loop closure signal.
2.1.22 Optional MCA Relay Circuit Card, P/N 514348: Each circuit card adds six (6) Form-C external
alarm relay contacts to the system. Plugs into seven-slot card cage provided in each bay for
optional MCA and LMS I/O cards.
(A) Contact Rating: 2A at 30 VDC.
(B) Description of Operation: The MCA provides 25 programmable function channels.
Program each function channel to alarm for selected conditions, then program each external
alarm relay to activate if a specific function channel alarms.
MCA relays can also be programmed to activate if an LMS LED channel activates.
2.1.23 Optional MCA Input/Output (I/O) Circuit Card, P/N 524550: This I/O card provides capability
for monitoring of external shunts and binary signals. Plugs into seven-slot card cage provided in
each bay for optional MCA and LMS I/O cards. Provides 1 analog input, 1 analog output (for
remote plant output current monitoring), and 4 binary inputs.
(A) One analog input with a range of 0-50mV can be used to provide monitoring of additional
load shunt or a plant load shunt.
(B) Four binary inputs can be used to monitor dry contact closures. When the “Alternate Current
Limit” feature is used, binary input #4 is assigned to monitor the signal used to trigger the
MCA to place the rectifiers in the Alternate Current Limit mode.
(C) One analog output with a 50mV full scale output provides a value to indicate the “Total Load
Current” parameter of the NPS system.
The reading displayed for the NPS system parameter “Total Load Current” is derived from
one of two algorithms using multiple data sources. The algorithm and its data sources used
are determined by the presence and configuration of CAN I/O card(s) in the system.
1) Algorithm #1: This source is used when there are no CAN I/O cards installed OR when
the configuration of all installed CAN I/O cards is set to “Distribution” mode.
“Distribution” Mode Operation:
“Total Load Current” =
NPS bay distribution node current readings,
+ CAN I/O card analog input readings,
+ LMS function channel 63 reading.
The VPS ‘Total System Current’ reading (LMS channel A9002) will be passed to the
NPS through LMS function channel sixty-three. The function channel configuration
will default to provide the reading of the associated LMS channel for the VPS Total
Page 38 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
System Current. The NPS controller will include the value of LMS function
channel sixty-four when summing the distribution load currents to determine
its Total Load Current reading to display. (associated LMS channel A9903).
Home
Channel F63 program line is ‘F63 = A9002’ (Vortex Total Load Current).
2) Algorithm #2: This source is used when the configuration of at least one installed CAN
I/O card is set to “Auxiliary” mode.
“Auxiliary” Mode Operation:
“Total Load Current” =
Sum of CAN I/O card analog input readings (only input readings of cards
configured for “Auxiliary” operation are summed),
+ LMS function channel 63 reading.
The reading displayed for the NPS system parameter “Total Auxiliary Load” is
derived from the sum of all analog input readings of CAN I/O cards configured for
“Auxiliary” mode operation
3. RECTIFIER MODULE, HIGH EFFICIENCY (MODEL R48-3200E, SPEC. NO. 1R483200E)
Refer to UM1R483500E.
4. RECTIFIER MODULE (MODEL R48-3200, SPEC. NO. 1R483200)
Refer to UM1R483500E.
5. LMS MONITORING SYSTEM
Refer to SAG586505000/SAG586505500
Page 39 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
Home
PHYSICAL SIZE INFORMATION
Overall Dimensions - Main and Supplemental Power Bays
Refer to PD588705000 for Rectifier Module Mounting Shelf dimensions.
Notes:
1. All dimensions are in inches,
unless otherwise specified.
2. Weight in LBS.
(including relay rack)
Net:
Shipping:
3. Finish: Textured Gray (M500-147), except
Rectifier Shelf and Rectifier Module
Bodies are Bright Zinc Plating
(M500-53).
4. See PD588705000 for Rectifier Module
Mounting Shelf dimensions.
17.50
Top View
17.50
6.00
8.00
25.00
10.38
84.00
12RU = 21.00
Left Side View
Front View
Right Side View
Page 40 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
Home
Overall Dimensions - Optional Digital Battery Charge Temperature
Compensation Probes P/N 107021 (25 feet) and P/N 106824 (100 feet)
0.25 (6.35) DIA.
0.75
(19.05)
3.00 (76.2)
0.75 (19.05)
2.25 (57.15)
300 (7,620)
or
1200 (30,480)
0.35 (8.89)
Note: All dimensions are in inches and (millimeters).
Part No. 107021 (25 foot)
Part No. 106824 (100 foot)
Page 41 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582126100
Issue AH, July 4, 2012
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
Home
RELATED DOCUMENTATION
Power Data Sheets:
PD588705000 (Model PSS4850-23GV Rectifier Module Mounting Shelf,
includes all Rectifier Module data)
Schematic Diagrams:
SD582126100 (NETSURE™ Power System)
SD588705000 (Model PSS4850-23GV Rectifier Module Mounting Shelf)
Wiring Diagrams:
T582126100 (NETSURE™ Power System)
T588705000 (Model PSS4850-23GV Rectifier Module Mounting Shelf)
Color MCA Menu Tree:
Section 5886
Instructions:
Section 6027, System Installation Instructions
(NETSURE™ Power System, Spec. No. 582126100)
Section 6028, System User Instructions
(NETSURE™ Power System, Spec. No. 582126100)
UM1R483500E, Rectifier User Instructions
(NetSure™ Rectifiers, Spec. No. 1R3200 and 1R3200E)
Load and Battery
Lug Detail Drawings:
031110100
031110200
031110300
LMS Monitoring System
Section 5879, Installation Instructions
(Spec. No. 586505000/586505500)
Section 5847, User Instructions
(Spec. No. 586505000/586505500)
SAG586505000/SAG586505500
(System Application Guide)
Section 5944, LMS I/O Circuit Cards Instructions
520538, LMS I/O Circuit Card Label Sheet
SD507606, LMS Expansion Assembly Schematic Diagram
Page 42 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582126100 (Model 702NBDB)
SAG582126100
Issue AH, July 4, 2012
Home
REVISION RECORD
Issue
Change
Number
(ECO)
AA
LLP212061
New
03/18/09
John Jasko
AB
LLP213103
MCA and LMS default configuration values
updated.
10/19/09
John Jasko
AC
LLP213309
Drawings of redesigned AC box updated.
1R483200e Rectifier Module added as option.
List 3 added.
01/25/09
Shanon Ravacio
AD
LLP213082
Updates for LMS Firmware 9.1 and MCA version
2.2.
04/12/10
John Jasko
AE
LLP214969
Added 1R483500e rectifier to the existing power
system of 582126000. Added and updated charts
for rectifier specifications.
01/04/11
Khristebelle
Ilagan
AF
LLP215410
Update drawings to show new location of AC
boxes on the system. Reflect new system part
numbers.
05/23/11
Shanon Ravacio
11/3/11
John Kirkpatrick
07/04/12
Shanon Ravacio
John Jasko
July 09 2012
Shanon Ravacio
July 10 2012
Description of Change
Date
Approved
Updated for MCA version 2.3.0.5 (PCU mapping menu
added). Adding compatibility information for
AG
LLP214855
AH
LLP216994
1R483500e rectifiers in systems with older
software. Added references to rectifier User
Manual UM1R483500E. Added MCA
specifications formerly in PD588705000.
Removed references to R48-3500e rectifier
Emerson Network Power, Energy Systems, North America, Inc.
4350 Weaver Parkway, Warrenville, IL 60555
Toll Free: 800-800-1280 (USA and Canada)
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems
EnergyNet: Secure.EmersonNetworkPower.com
Page 43 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.