OC-2593 GBB spec sheet

1/4" x 1-1/4" Fuses
GBB Series Very Fast Acting, Ceramic Tube
Description
• Very fast-acting
• Optional axial leads available
• 1/4" x 1-1/4" (6.3mm x 32mm) physical size
• Ceramic tube, nickel-plated brass endcap construction
• 100pc-carton quantity weighs 1.0 lb (0.45 kg)
• UL recognized product meets standard 248-14
ELECTRICAL CHARACTERISTICS
Rated Current % of Amp Rating
Opening Time
100%
None
150%
2 minutes maximum
1 - 20A
250%
1 seconds maximum
400%
100%
None
150%
2 minutes maximum
25, 30A
250%
6 seconds maximum
400%
-
RoHS
2002/95/EC
Dimensions
mm
⁄(inches)
Agency Information
• UL Recognized Card: GBB 1-30A (JFHR2, E56412)
• CSA Component Certified Card
(Class 1422-01 File 53787)
Ordering
• Specify packaging, product, and option code
SPECIFICATIONS
Product Code
GBB-1
GBB-1-1/4
GBB-2
GBB-3
GBB-4
GBB-5
GBB-6
GBB-7
GBB-8
GBB-9
GBB-10
GBB-12
GBB-15
GBB-20
GBB-25
GBB-30
Voltage
Rating
AC
DC
250V
125V
250V
125V
250V
125V
250V
125V
250V
125V
250V
125V
250V
125V
250V
125V
250V
125V
250V
125V
250V
125V
250V
125V
250V
125V
250V
125V
250V
125V
250V
125V
AC Interrupting
Rating*
250V
125V
200A
10,000A
200A
10,000A
200A
10,000A
200A
10,000A
200A
10,000A
200A
10,000A
200A
10,000A
200A
10,000A
200A
10,000A
200A
10,000A
200A
10,000A
200A
10,000A
200A
10,000A
200A
200A
200A
200A
200A
200A
DC Interrupting
Rating*
125V
10,000A
10,000A
10,000A
10,000A
10,000A
10,000A
10,000A
10,000A
10,000A
10,000A
10,000A
10,000A
10,000A
200A
200A
200A
Typical DC Cold
Resistance
(ohms)**
0.17750
0.17900
0.06620
0.04475
0.03175
0.02125
0.01800
0.01550
0.01360
0.01070
0.00934
0.00620
0.00472
0.00330
0.00252
0.00206
Typical
Melt I2t †
AC
DC
-
Typical
Voltage
Drop (V)‡
0.17750
0.17900
0.07000
0.04475
0.03175
0.02125
0.01800
0.01550
0.01360
0.01070
0.00934
0.08620
0.00472
0.00365
0.00252
0.00206
* Interrupting ratings: Interrupting ratings for 1-15A at 125Vdc was measured at 10,000A, 3.5 ms maximum, with time constant. Ratings 20-30A at 125Vdc were measured at 200A, 0.5 ms
maximum, with time constant. Ratings 1-15A at 125Vac were measured at 10,000A, and 70% - 80% power factor. The interrupting ratings for 1-30A at 250Vac were measured at 90% 100% power factor.
** DC Cold Resistance (Measured at <10% of rated current)
† Typical Melting I2t (I2t was measured at listed interrupting rating and rated voltage) Interrupting ratings were measured at 70% to 80% power factor on AC.
‡ Typical Voltage drop (Voltage drop was measured at 25°C±3°C ambient temperature at rated current)
1/4" x 1-1/4" Fuses
GBB Series Very Fast Acting, Ceramic Tube
TIME CURRENT CURVE
2
3
5
6
7
8
9
10
12
15
20
25
30
TIME IN SECONDS
TIME IN SECONDS
1
1-1/4
CURRENT IN AMPERES
CURRENT IN AMPERES
PACKAGING CODE
Packaging Code
BK
BK1
Description
100 pieces of fuses packed into a cardboard carton
1,000 pieces of fuses packed into a cardboard carton
OPTION CODE
Option Code
B
V
-R
Visit us on the web at:
www.cooperbussmann.com
OC-2593 8/06
© Cooper Electronic
Technologies 2006
Description
Board Washable - Hermetically sealed to withstand aqueous cleaning
Axial leads - copper tinned wire with nickel plated brass overcaps
RoHS compliant version
North America
Cooper Electronic Technologies Cooper Bussmann
1225 Broken Sound Parkway NW P.O. Box 14460
Suite F
St. Louis, MO 63178-4460
Boca Raton, FL 33487-3533
Tel: 1-636-394-2877
Tel: 1-561-998-4100
Fax: 1-800-544-2570
Fax: 1-561-241-6640
Toll Free: 1-888-414-2645
Europe
Cooper Electronic Technologies Cooper Electronic Technologies
Cooper (UK) Limited
Avda. Santa Eulalia, 290
Burton-on-the-Wolds
08223
Leicestershire • LE12 5TH UK
Terrassa, (Barcelona), Spain
Tel: +44 (0) 1509 882 737
Tel: +34 937 362 812
Fax: +44 (0) 1509 882 786
+34 937 362 813
Fax: +34 937 362 719
Asia Pacific
Cooper Electronic Technologies
1 Jalan Kilang Timor
#06-01 Pacific Tech Centre
Singapore 159303
Tel: +65 278 6151
Fax: +65 270 4160