Time-Delay Fuses SC

Bussmann®
Time-Delay Fuses
SC
Class G – 600 Volt, ⁄Ω™ - 20 Amps
480 Volt, 25 - 60 Amps
Dimensional Data
A
(Length)
.41"
(10.3mm)
Fuse (Amps)
Catalog Symbol: SC
Current-Limiting
Ampere Rating: ⁄Ω™ to 60A (fast-acting),
7 to 60A (time-delay)
Voltage Ratings:
SC ⁄Ω™ to 20
600Vac, 170Vdc
SC 25 to 60
480Vac, 300Vdc
Interrupting Rating: 100,000A RMS Sym. AC, 10,000A dc
Agency Information:
UL Listed, Std. 248-5, Class G, Guide JDDZ, File E4273
CSA Certified, C22.2 No. 248.5, Class 1422-01, File 53787
Catalog Numbers
SC-⁄Ω™
SC-6
SC-25
SC-1
SC-7
SC-30
SC-1⁄Ω™
SC-8
SC-35
SC-2
SC-9
SC-40
SC-2⁄Ω™
SC-10
SC-45
SC-3
SC-12
SC-50
SC-4
SC-15
SC-60
SC-5
SC-20
—
Carton Quantity and Weight
Catalog
Number
Weight†
Carton
Qty.
Lbs.
Kg.
⁄Ω™–15
4
0.060
0.0272
20
4
0.064
0.029
25–30
2
0.040
0.018
35–60
2
0.075
0.0340
†Weight per carton.
4-01-04
SB04105
A
SC-⁄Ω™ to 15
1.31∑
SC-20
1.41∑
SC-25 to 30
1.62∑
SC-35 to 60
2.25∑
General Information:
• Compact branch-circuit units with high interrupting rating
and current-limitation.
• With 600V rating, they can be used in 120/208, 120/240
and 277/480V circuits.
• Length variations relative to case size make the “rejection”
type fuses.
• In general, SC fuses are about ⁄Ω£ the size of the 600V NEC
fuse type.
• SC fuses with ampere ratings above 6A have a
degree of overload time-delay which permits them to pass
temporary overloads. At 200% load, they have a minimum
opening time of 12 seconds.
Recommended fuseblocks/fuseholders for
Class G fuses
See Data Sheets listed below
• Open fuseblocks - 1106
• In-line fuseholders - 1123, 1124
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
Form No. SC
Page 1 of 3
Data Sheet: 1024
Bussmann®
Time-Delay Fuses
SC
Class G – 600 Volt, ⁄Ω™ - 20 Amps
480 Volt, 25 - 60 Amps
Peak Let-Through Curves
B
60
30
20
15
AMPERE
RATING
INSTANTANEOUS PEAK LET-THROUGH
CURRENT IN AMPS
10,000
1,000
A
100,000
10,000
1,000
100
100
RMS SYMMETRICAL CURRENTS IN AMPERES
A–B=ASYMMETRICAL AVAILABLE PEAK (2.3 X SYMM RMS AMPS)
4-01-04
SB04105
Form No. SC
Page 2 of 3
Data Sheet: 1024
Bussmann®
Time-Delay Fuses
SC
Class G – 600 Volt, ⁄Ω™ - 20 Amps
480 Volt, 25 - 60 Amps
60A
1A
1-1/2A
2A
2-1/2A
3A
4A
5A
6A
8A
10A
12A
15A
20A
30A
1/2A
Time-Current Characteristic Curves– Total Clearing
300
TIME IN SECONDS
100
10
1
.1
.01
.7 1
10
100
1,000 2,000
CURRENT IN AMPERES
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
4-01-04
SB04105
Form No. SC
Page 3 of 3
Data Sheet: 1024