Square Body DIN 43 655

Bussmann®
Square Body – DIN 43 653
1000V (IEC/U.L.)
Size
2
Rated
Voltage
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
250-800A
Electrical Characteristics
I2t (A2s)
Rated
Clearing
Current
at Rated
RMS-Amps
Pre-arc
Voltage
250
315
350
400
450
500
550
630
700
800
315
6750
13500
16500
26000
35500
49500
66000
93500
130000
195000
9200
40000
81500
99000
155000
210000
295000
390000
555000
770000
1200000
54500
R
®
Ordering Information
Watts
Loss
-KN/110
Type K
Indicator for
Micro
-TN/110
Type T
Indicator for
Micro
65
75
80
85
90
95
100
110
115
125
90
170M5966
170M5967
170M5968
170M5969
170M5970
170M5971
170M5972
170M5973
170M5974
170M5975
170M8614
170M5981
170M5982
170M5983
170M5984
170M5985
170M5986
170M5987
170M5988
170M5989
170M5990
170M8629
Curves
Carton
Qty.
Carton
Weight
(kg)
See Page
or
(Datasheet)
3
2.7
Page 75
or
(720060)
1 kg = 2.2 lbs. 1 lb = 0.45 kg
I Interrupting rating 150kA (Estimated 300kA) RMS Symmetrical.
I Watts loss provided at rated current.
I Microswitch ordered separately.
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition
uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications.
Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the
right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible
applications.
2-25-02
SB01407
Form No. 170M
Page 1 of 4
BIF Doc #720060
Bussmann®
Square Body – DIN 43 653
1000V (IEC/U.L.)
250-800A
R
®
Electrical Characteristics
Total clearing I2t
Arc Voltage
Power Losses
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as
a function of applied working voltage,
Eg, (RMS).
This curve gives the peak arc voltage,
UL, which may appear across the fuse during its operation as a function of the
applied working voltage Eg, (RMS) at a
power factor of 15%.
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current. The correction factor, Kp,
is given as a function of the RMS load
current, Ib, in % of the rated current.
3
UL
2,5
2
1,8
1,6
1,4
1,2
103
1,0
*Rated voltage 900V
1,5
K
*
1,0
0,5
0,3
0,3
0,2
0,15
4
0,2
Eg
600
700
800
900
Eg
3
1000
Kp
0,4
8
7
6
5
0,4
500
0,8
0,7
0,6
0,5
500
600
700
800
900
1000
0,1
30
Ib
40
50
60
70
80
90 100%
Dimensions
DIN 43 653 Type –KN/110 and –TN/110
Size
1*KN/110
1KN/110
2KN/110
3KN/110
A
80
80
80
81
B
138
138
138
139
C Max D1
108
61
108
69
108
77
108
92
E
43
51
59
74
G
6
6
6
6
H
22
25
25
30
I
11
11
11
11
Size
A
B
C Max D2
1*TN/110
80
138 108
61
1TN/110
80
138 108
69
2TN/110
80
138 108
75
3TN/110
81
139 108
90
Dimensions in mm
1 mm = 0.0394”
1” = 25.4 mm
E
43
51
59
74
G
6
6
6
6
H
22
25
25
30
I
11
11
11
11
KN/110
2-25-02
TN/110
SB01407
Form No. 170M
Page 2 of 4
BIF Doc #720060
BIF Document
Semiconductor Fuse
250-800A, 1000 Volts
720060
2
Size
104
The partial dotted curves
are for fuses designed to
give part range protection
(aR protection). Loading
or operation above the
curve indicated at A on
the curves must in general be avoided. Please see
technical guidance
170K…
for further information.
Curves that are not dotted
are for fuses designed to
give full range protection.
103
10
1s
700A
550A
450A
350A
250A
10-1
800A
630A
500A
400A
315A
Virtual Pre-arcing Time In Seconds
102
10-2
10-3
10-4
102
103
104
105
Prospective Current In Ampere RMS
Pre-Arcing
Time-Current Characteristic Curves
TYPOWER ZILOX
2-25-02
SB01407
BUSSMANN
P.O. Box 14460
St. Louis, MO 63178-4460
U.S.A.
Phone: 636-394-2877
Fax:
800-544-2570
Int’l Fax: 636-527-1413
Approved:
PK
Rev. Date:
NOV-01
BUSSMANN U.K.
Burton-on-the-Wolds
Leicestershire LE12 5TH
England
Phone: 44-1509-882737
Fax:
44-1509-882786
Page
Pub. Date:
BUSSMANN DENMARK
5 Literbuen
DK-2740 Skovlunde
Copenhagen, Denmark
Phone: 45-4485-0900
Fax:
45-4485-0901
Bussmann reserves the right without notice to change design and/or discontinue distribution of this product.
3 of 4
NOV-01
BIF Document
Semiconductor Fuse
250-800A, 1000 Volts
720060
2
Size
Peak Let-Through Current In Amperes
105
800A
630A
500A
400A
315A
700A
550A
450A
350A
250A
104
103
2x102
102
103
104
105
Amp
106
Prospective Short-Circuit Current symmetrical RMS
Peak Let-Through
Cut-Off Current Characteristic Curves
TYPOWER ZILOX
2-25-02
SB01407
Approved:
PK
Rev. Date:
NOV-01
Page
Pub. Date:
4 of 4
NOV-01
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this BIF document are by definition
uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann
reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to
change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.