POWR-GARD® Fuse Datasheet CLASS T – JLLN / JLLS SERIES FUSES 300/600 VAC • Fast-Acting • 1-1200 A Ordering Information 1 2 3 6 10 15 20 Description JLLN / JLLS fuses are less than 1/3 the size of comparable Class R fuses and are typically used for short circuit protection of drives and surge sensitive components. When rated in accordance with the NEC®, JLLN / JLLS fuses provide fast-acting overload and short circuit protection for non-inductive circuits and equipment. AMPERE RATINGS 70 175 80 200 90 225 100 250 110 300 125 350 150 400 450 500 600 700 800 900* 1000 1100 1200 *JLLS only Part Numbering System Features/Benefits JLLN xxxx V — • Extremely current-limiting Options Series Amperage • Compact design • 200 kA Interrupting Rating Blank = Standard Non-Plated XP = Premium Plated XL = Leaded† XV = Vertical Mount† XLS = Solder Lead† Package Quantity • JLLN 35-60A available with PCB mounts T = 10 (1-60 A) V = 5 (70-100 A) X = 1 (110-1200 A) Applications • Variable speed drive protection • Compact mains switches Specifications Voltage Ratings AC: 3 00 V (JLLN) 600 V (JLLS) DC: 125 V (JLLN 70 – 1200 A) 160 V (JLLN 1 – 60 A) 300 V (JLLS) Interrupting Ratings AC: 200 kA rms symmetrical DC: 20 kA (JLLN 35-1200 A only) Ampere Range 1 – 1200 A Approvals AC: S tandard 248-15, Class T UL Listed (File: E81895): JLLN (1 – 1200 A) JLLS (1 – 1200 A) CSA Certified (File: LR29862) JLLN/JLLS (1 – 600 A) DC: UL Listed (File: E81895): JLLN (35 – 1200 A) Littelfuse self-certified JLLN (1 – 30 A) JLLS (1 – 1200 A) Material JLLN: 1-30 A: Melamine body, Bronze caps 35-1200 A: Melamine body, Copper caps JLLS: 1 -30 A: Melamine body, Copper caps 35-60 A: Melamine body, Bronze caps 70-1200 A: Melamine body, Copper caps EnvironmentalRoHS Compliant littelfuse.com 25 30 35 40 45 50 60 1 of 4 PLATING SERIES AMP PACK SIZE SUFFIX JLLS 6 T – JLLN 35 V – JLLN 100 V XP MOUNT SUFFIX – XL† – CATALOG NUMBER JLLS006 JLLN035L JLLN100P ORDERING NUMBER JLLS006.T JLLN035.VXL JLLN100.VXP Option is available for JLLN 35-60 A only. Premium plating is standard † Web Resources Download TC Curves, CAD drawings and other technical information: littelfuse.com/jlln littelfuse.com/jlls Recommended Fuse Holders LFT30 Series LFT60 Series LSCR Series for 70-800 A Dimensions Please refer to the Class T and JLLN 35-60A PCB mount dimensions on page 4 © 2015 Littelfuse POWR-GARD® Products Rev: 040815 POWR-GARD® Fuse Datasheet CLASS T – JLLN / JLLS SERIES FUSES Peak Let-Thru Curve and Current-Limiting Effects of JLLN (300 V) Fuses 1,000,000 1200A 800A 600A - 100,000 400A 200A - PEAK LET- THRU IN AMPERES 100A 60A 30A - 10,000 1,000 100 100 1,000 10,000 100,000 AVAILABLE FAULT CURRENT SYMMETRICAL R.M.S. AMPERES TIME CONSTANT/POWER FACTOR: TEST VOLTAGE: 300V FUSE CATALOG NUMBER: JLLNP 30A - 1200A BASIS FOR DATA: DRAWN BY: LLL DATE: 01/21/2014 REVISION: A LITTELFUSE, INC. CHICAGO,RMS IL. USA SYMMETRICAL CURRENT FOR APPARENT SHORT CURVES VARIOUS FUSE RATINGSFCC05-JLLNP CIRCUIT PEAK LET-THRU CHARACTERISTIC CURRENT* 30 A 60 A 100 A 200 A 400 A 600 A 800 A 1200 A DRAWING NO.: SHEET 2 OF 2 - DATA GENERATED IN EXCEL - 5,000 700 775 1,100 1,650 3,500 4,000 5,000 5,000 10,000 900 1,000 1,400 2,100 4,400 5,100 6,750 8,250 10,000 15,000 1,000 1,100 1,600 2,400 5,000 5,900 7,750 20,000 1,100 1,250 1,800 2,700 5,500 6,500 8,750 11,000 25,000 1,230 1,300 1,950 2,900 6,000 7,000 9,500 12,000 30,000 1,300 1,475 2,050 3,100 6,400 7,500 10,000 12,500 35,000 1,330 1,575 2,150 3,300 6,750 7,750 10,500 13,500 40,000 1,430 1,600 2,300 3,500 7,000 8,000 11,000 14,000 50,000 1,500 1,750 2,400 3,700 7,500 8,750 12,000 15,000 12,500 16,000 60,000 1,700 1,900 2,700 4,000 8,000 9,500 80,000 1,850 2,100 2,800 4,400 9,000 10,500 14,000 17,500 100,000 2,000 2,250 3,150 4,800 9,750 11,500 15,000 18,500 150,000 2,300 2,600 3,600 5,500 11,000 13,000 17,500 22,000 200,000 2,600 2,800 3,900 6,000 12,000 14,500 19,500 24,000 *Prospective RMS Symmetrical Amperes Short-Circuit Current Note: Data Derived from Peak Let-Thru Curves littelfuse.com 2 of 4 © 2015 Littelfuse POWR-GARD® Products Rev: 040815 POWR-GARD® Fuse Datasheet CLASS T – JLLN / JLLS SERIES FUSES Peak Let-Thru Curve and Current-Limiting Effects of JLLS (600 V) Fuses 1,000,000 1,000,000 100,000 800A - 1200A - 600A - 1100A 1000A - 400A - 100,000 100A - 900A - PEAK LET- THRU IN AMPERES PEAK LET- THRU IN AMPERES 200A - 60A 30A - 10,000 10,000 1,000 100 100 1,000 10,000 1,000 1,000 100,000 TIME CONSTANT/POWER FACTOR: TEST VOLTAGE: 600V FUSE CATALOG NUMBER: TEST VOLTAGE: 600V JLLS 30A - 1200A BASIS FOR DATA: CHICAGO, RMS IL. USA SYMMETRICAL CURRENT FOR APPARENT SHORT PEAK LET-THRU CHARACTERISTIC CURVES VARIOUS FUSE RATINGSFCC05-JLLS CIRCUIT CURRENT* 30 A 60 A 100 A 200 A 400 A 600 A 800 A 1200 A DRAWING NO.: SHEET 2 OF 3 - DATA GENERATED IN EXCEL - 5,000 10,000 15,000 750 1,225 1,810 945 2,500 4,600 5,000 TIME CONSTANT/POWER FACTOR: 100,000 5,000 5,000 10,000 1,525 2,300 3,150 6,000 8,500 9,400 1,050 1,700 2,610 3,600 6,600 9,750 10,500 13,000 10,500 11,000 14,750 20,000 1,150 1,900 2,900 3,950 7,250 25,000 1,300 2,050 3,100 4,250 8,000 11,500 12,500 15,500 30,000 1,375 2,150 3,300 4,500 8,250 12,000 13,750 16,500 35,000 1,400 2,250 3,500 4,750 8,500 13,000 14,000 17,000 40,000 1,425 2,400 3,650 4,950 8,700 14,000 14,750 18,000 50,000 1,600 2,450 3,900 5,350 9,500 14,500 16,000 20,000 60,000 1,650 2,625 4,150 5,650 10,000 15,500 17,300 21,000 80,000 1,825 2,800 4,570 6,250 11,000 17,000 18,750 23,000 100,000 2,000 3,100 4,950 6,700 12,000 18,000 20,000 25,000 150,000 2,250 3,400 5,650 7,700 13,000 21,000 23,000 28,500 200,000 2,450 3,800 6,200 8,450 15,000 23,000 25,000 31,000 FUSE CATALOG NUMBER: JLLS 30A - 1200A BASIS FOR DATA: DRAWN BY: LLL DATE: 01/28/2014 REVISION: A LITTELFUSE, INC. 10,000 AVAILABLE FAULT CURRENT SYMMETRICAL R.M.S. AMPERES AVAILABLE FAULT CURRENT SYMMETRICAL R.M.S. AMPERES DRAWN BY: LLL DATE: 01/28/2014 REVISION: A LITTELFUSE, INC. CHICAGO, IL. USA PEAK LET-THRU CHARACTERISTIC CURVES DRAWING NO.: FCC05-JLLS SHEET 3 OF 3 - DATA GENERATED IN EXCEL - *Prospective RMS Symmetrical Amperes Short-Circuit Current Note: Data Derived from Peak Let-Thru Curves littelfuse.com 3 of 4 © 2015 Littelfuse POWR-GARD® Products Rev: 040815 POWR-GARD® Fuse Datasheet CLASS T – JLLN / JLLS SERIES FUSES Dimensions Inches (mm) C D B D C A A Fig. 1 AMPERES G B REFER TO FIG. NO. 1 – 30 1 35 – 60 1 2 70 – 100 3 110 – 200 3 225 – 400 3 450 – 600 3 700 – 800 3 900 – 1200 3 C F F E A Fig. 2 SERIES JLLN JLLS JLLN JLLS JLLN JLLS JLLN JLLS JLLN JLLS JLLN JLLS JLLN JLLS JLLN JLLS D Fig. 3 DIMENSIONS INCHES (mm) A B C D E F G .875 (22.2) 1.500 (38.1) .875 (22.2) 1.562 (39.7) 2.156 (54.8) 2.953 (75.0) 2.437 (61.9) 3.250 (82.6) 2.750 (69.9) 3.625 (92.1) 3.062 (77.8) 3.984 (101.2) 3.375 (85.7) 4.328 (109.9) 4.000 (101.6) 5.271 (133.9) — — — .812 (20.6) 1.562 (39.7) 2.352 (59.7) 1.687 (42.9) 2.507 (63.7) 1.843 (46.8) 2.718 (69.1) 2.031 (51.6) 2.953 (75.0) 2.218 (56.4) 3.171 (80.6) 2.531 (64.3) 3.801 (96.5) .281 (7.1) .281 (7.1) .281 (7.1) .406 (10.3) .750 (19.1) .750 (19.1) .875 (22.2) .875 (22.2) 1.000 (25.4) 1.000 (25.4) 1.250 (31.8) 1.250 (31.8) 1.750 (44.5) 1.750 (44.5) 2.000 (50.8) 2.000 (50.8) .406 (10.3) .562 (14.3) .562 (14.3) .994 (25.2) .812 (20.6) .828 (21.0) 1.062 (27.0) 1.078 (27.4) 1.312 (33.3) 1.593 (40.5) 1.593 (40.5) 2.062 (52.4) 2.062 (52.4) 2.500 (63.5) 2.500 (63.5) 2.625 (66.7) — — — .062 (1.6) .830 (21.1) 1.625 (41.3) .830 (21.1) 1.656 (42.1) .828 (21.0) 1.712 (43.5) .875 (22.2) 1.765 (44.8) .875 (22.2) 1.860 (47.2) 1.033 (26.2) 2.303 (58.5) — — — 1.094 (27.8) .281 (7.1) .281 (7.1) .343 (8.7) .343 (8.7) .406 (10.3) .406 (10.3) .484 (12.3) .484 (12.3) .546 (13.9) .546 (13.9) .609 (15.5) .609 (15.5) — — — — .125 (3.2) .125 (3.2) .187 (4.8) .187 (4.8) .250 (6.4) .250 (6.4) .312 (7.9) .312 (7.9) .375 (9.5) .375 (9.5) .437 (11.1) .437 (11.1) PCB Mounting Options (JLLN 35-60 A Only) Vertical Mount JLLN-V Leaded JLLN-L Solder JLLN-LS littelfuse.com 4 of 4 © 2015 Littelfuse POWR-GARD® Products Rev: 040815