Voice Smoke Detector -- HT45F24A

Voice Smoke Detector
HT45F24A
Characteristics
 Sensor : Optical Cavity Maze
 Operating voltage : 3V
 Operating current
◆
◆
Standby current (Typ.) : 2.8µA
Standby current (Max.) : 4.83µA
 Alarm operating current : < 35mA
 Low voltage voice alarm : 2.7V
 Adjustable volume using software : Voice alarm ‒ volume up to 85db / 3m
 Detector sensitivity : Meets UL 217 Standard, when the smoke particle
concentration value reaches 3.2% per foot, the detecor will react
 Operating temperature : -10°C ~ 50°C
PA2
Programming Pin
Second Stage
OPA Output
HT45F24A
IR Transmit
Synchronisation Signal
Programming Pins Starting
from top : VDD RESB PA0 GND
Operation Description
 The test key function description :
When the battery voltage is normal, the voice is “System normal”.
When the low battery voltage is detected, the voice is “Please change the
battery”.
 When the smoke is deteced and the smoke detector alarms, the voice is “Fire”,
the LED flashes 3 times for 50ms. The alarm time will last for 10s. If the test
key is pressed during alarm, the alarm is cancelled.
 The smoke detecor will detect low voltage per 4s, when the low voltage is
detected, 3 steps are as follows :
◆
Step 1. Play the voice “Please change the battery” once per 4s when the
low voltage is detected, and play twice in total.
◆
Step 2. The LED will flash 3 times for 50ms per 8s, a total of 8 cycles.
◆
Step 3. Play “Bi” warning tone for 3 times per 4s, jump to Step 1.
Note: If the test key is pressed during low voltage, only the function in Step
2 is excuted.
 Enter the test mode : long press the test key when power on, the system can
enter the test mode, which mainly is used to measure the second stage OPA
stability and sensitivity.
Application Circuit