Flyer GIS 8DN8 bis 170 kV englisch (103 kB)

www.siemens.com/energy
Gas-insulated switchgear
Type 8DN8, 170 kV, 63 kA, 4000 A
A new dimension in compactness
highest technical ratings in its class
economic efficiency
M
M
high reliability
long service life
safe encapsulation
very high degree of gas-tightness
low life cycle and maintenance costs
easy access and ergonomic design
M
high availability
reliable operation even under extreme
environmental conditions
Answers for energy.
Technical data
Switchgear type
Rated voltage
8DN8
up to
170 kV
Rated frequency
50/60 Hz
Rated power frequency withstand
voltage (1 min)
325 kV
Rated lightning impulse withstand
voltage (1.2/50 µs)
750 kV
Rated normal current busbar
up to
4,000 A
Rated normal current feeder
up to
4,000 A
Rated short-circuit breaking current / break time
up to
63 kA
Rated peak withstand current
up to
170 kA
Rated short-time withstand current (3 s)
up to
63 kA
Leakage rate per year and gas compartment
≤ 0.5 %
routine test
≤ 0.1 % type test
Bay width
1,000 mm
depending on
bay arrangements
Height, depth
Driving mechanism of circuit-breaker
stored-energy spring
Rated operating sequence
O-0.3 s-CO-3 min-CO
CO-15 s-CO
Rated supply voltage
110–250 V DC
Expected lifetime
> 50 years
Ambient temperature range
–30 °C to +40 °C
Standards
IEC/IEEE/GOST
Other values on request
Siemens AG
Energy Sector
Freyeslebenstrasse 1
91058 Erlangen, Germany
Power Transmission Division
Dispo 30000, c4bs-Nr. 7460
Order No. E50001-G620-A141-V1-4A00 | Printed in Germany |
fb 5092 WÜ 470086 WS 07122.0 | © 07.2012, Siemens AG
www.siemens.com/energy