1500

Features
Applications
■
■
■
■
■
■
■
■
■
■
■
■
GDT/TBU® High-Speed Protector technology
Low impulse let-through
High surge current rating
Available in isolated and grounded versions
10/100/1000 data compatibility
5 kV isolation
Listed per UL 497B (File: E153537)
Data communications
Highly exposed Ethernet
1000 Base-T Gigabit Ethernet
Indoor/controlled environment installations
Telecommunications and industrial
installations
1500 Series Gigabit Ethernet SPD
The 1500 Series Ethernet Surge Protective Device (SPD) incorporates multiple Bourns® circuit protection technologies. These technologies
are designed to work together to provide an unmatched level of surge protection for exposed Ethernet applications. The 1500 Series is
designed to meet key surge and AC power cross requirements of GR-1089-Core Issue 6. The isolated model is designed to withstand
voltages up to 5 kV.
The 1500 Series is available as a wall mount unit with optional DIN Rail hardware.
Characteristics
Test methods per UL 497B, GR-1089 Issue 6, and CSA C22.2.
Parameter
DC Breakdown Line to Line
DC Breakdown Line to Ground
Line Series Resistance (Loop)
Line Series Balance
Capacitance Line to Line @ 1 MHz
Time-to-block (tblock)
First Level Surge
1 kV – 10/1000 μs, 100 A
2.5 kV – 2/10 μs, 500 A
800 V – 1.2/50 μs, 8/20 μs Combo Wave
Second Level Surge
2.5 kV – 2/10 μs, 500 A, Inductive Kick
6 kV / 3 kA – 1.2/50 μs, 8/20 μs Combo Wave
First Level Power Fault
220 mA Below Protection Threshold
600 V / 1 A / 1 Second
1000 V / 1 A / 1 Second
425 V / 0.5 A / 4 Seconds
Second Level Power Fault
120 V / 25 A 1
425 V / 40 A / 1.5 Second 1
425 V / 7 A / 5 Seconds 1
425 V / 2.2 A
BER Performance Testing
10/100 Mbps
1 Gbps
Storage and Operating Temperature
Ground Connection
Isolated Version
Grounded Version
150 V Typical Input / 7 V Typical Output
N/A
150 V Typ.
12 Ω Typ.
0.5 Ω Typ. / 1.0 Ω Max
N/A
10 pF Typ.
<1 μs
>10 operations
>10 operations
>10 operations
> 1 operation
> 1 operation
15 minutes
> 60 operations
> 60 operations
> 1 operation
15 minutes
1 operation
1 operation
15 minutes
> 100 meters
Up to 100 meters
-40 to +65 °C
Screw Lug or DIN Rail Clip
Notes:
Isolated version does not require a ground connection.
1) Fuse may fail open and disconnect from circuit.
Asia-Pacific: Tel: +886-2 2562-4117 • Fax: +886-2 2562-4116
EMEA: Tel: +36 88 520 390 • Fax: +36 88 520 211
The Americas: Tel: +1-951 781-5500 • Fax: +1-951 781-5700
www.bourns.com
Specifications are subject to change without notice.
The device characteristics and parameters in this data sheet can and do vary in different applications and actual device performance may vary over time.
Users should verify actual device performance in their specific applications.
1500 Series Gigabit Ethernet SPD
Product Dimensions
DIN Rail Hardware Dimensions
65.10
(2.563)
25.12
(0.989)
107.01
(4.213)
15.75
(0.62)
40.64
(1.60)
46.48
(1.83)
DIMENSIONS:
MM
(INCHES)
16.25
(0.65)
How To Order
1500 - X Y - W
Model Number Designator
Configuration
1 = Isolated*
2 = Grounded
Hardware Options
S = Screw Lug
D = DIN Rail
Ground Wire (Optional)
W = #14 AWG Ground Wire, 3 Ft.
* Isolated unit requires no ground.
REV. C 04/15
“Bourns” is a registered trademark of Bourns, Inc. in the United States and other countries.
“TBU” is a registered trademark of Bourns, Inc. in the U.S. and other countries, except Japan. All references to TBU® in this document for use in Japan shall be deemed to be replaced
with Bourns® TBU™.
Specifications are subject to change without notice.
The device characteristics and parameters in this data sheet can and do vary in different applications and actual device performance may vary over time.
Users should verify actual device performance in their specific applications.