2380-27-01 (J130S)

Features
■
C
UL
®
US
Listed per UL 497 (File: E53117)
■ Quick response
■ Industry standard footprint
Model 2380-27-01 (J130S) is obsolete
and not recommended for new
designs. Model 2378-35-HS
(155HS) is the recommended
alternative.
Model J130S Solid State Station Protector
Bourns® J130-type Solid State Station Protectors are designed to provide primary protection against lightning surges, power-cross
conditions and ground potential rises on conductors serving customer premises. Protectors are UL Listed in accordance with UL
Standard 497.
Bourns® J130S modules provide protection from each line (stud) to ground with lower voltage clamping levels than ever before
achieved. Clamping occurs within nanoseconds. This ensures lower equipment failure rates, higher systems reliabilty and longer
life of connected equipment.
Characteristics
Voltage Limiting (-40 °C to +65 °C)
60 Hz Breakover Voltage ................................................................................................................. 270 V Typ., 400 V max.
100 V/µs Breakover Voltage ............................................................................................................ 270 V Typ., 400 V max.
Impulse Reset (-40 °C to +65 °C)
52 Vdc, 260 mA; Initiation: 25 A, 10/1000 µs ................................................................................... 20 ms
135 Vdc, 200 mA; Initiation: 25 A, 10/1000 µs ................................................................................. 20 ms
Leakage Current (25 °C) ....................................................................................................................... 1 µA @ 250 V
Off-state Capacitance @ 1 MHz, 1 Vrms, 0 Vdc Bias (-40 °C to +65 °C) ............................................. 200 pF max.
Surge Capability, L-G, (-20 °C to +65 °C)
10/1000 µs Current Pulse ................................................................................................................ ±150 A min.
8/20 ms Current Pulse (Fail Short) .................................................................................................. 20 kA
60 Hz, 1 second burst (without failure) ............................................................................................ 10 A
Failsafe, Power Cross & Sustained 60 Hz Current Capability @ 1000 Vrms open-circuit voltage
30 Arms each line simultaneously to ground ................................................................................... 15 minutes, min.
60 Arms one line to ground .............................................................................................................. 3 seconds
120 Arms one line to ground ............................................................................................................ 0.6 seconds
350 Arms one line to ground ............................................................................................................ 0.04 seconds
Operating Temperature.......................................................................................................................... -55 to +85 °C
E
T
E
L
O
S
B
O
Specifications are subject to change without notice.
Customers should verify actual device performance in their specific applications.
Model J130S Solid State Station Protector
Product Dimensions
2380-27-01
36.83
(1.45)
24.13
(.95)
11.94
(.47)
18.29
(.72)
5.59
(.220)
15.24
(.60)
GROUND CLIP
TIN PLATED
HOUSING
PLASTIC
10-32 UNF-2A
THREAD
2 PLCS.
E
T
E
L
O
S
B
O
29.46
(1.16)
3.05 15.75
(.12) (.62)
1.78
(.07)
11.43
(.45)
DIMENSIONS:
2372-02 Ground Mounting Stud (order separately)
5.59
(.22)
J
16.26
(.64)
16.26
(.64)
10-32 UNF-2A
THREAD
4.98
(.196)
41.91
(1.65)
33.37
(1.55)
4.57
(.18)
17.78
(.70)
15.75
(.62)
31.75
(1.25)
REV. H 01/13
Specifications are subject to change without notice.
Customers should verify actual device performance in their specific applications.
13.97
(.55)
MM
(INCHES)
38.10