Design & Dimensions (Sensor/covers)
Wiring diagram
1: Sensor connection of DALIeco Control
2: Connection cable
3: Sensor DALIeco LS/PD LI
4: Y-Connector
Technical data
Designation:
DALIeco LS/PD LI
Operating range light sensor:
20 … 800 lux (directly at sensor)
Sensor connection:
4p4c, max. cable length in total: 25m (in total to all sensors)
Ambient temperature:
-20 °C …+ 50°C (in operation)
Type of protection/protection class:
IP 20 / II
Presence detection angle
Installation height = 2,0m:
40° … 90° (adjustable via sensor shutter)
Installation height = 3,0m:
Detection area: ~ Ø 2,0m … 6,0m
Installation height 3,5m… 5,0m(max):
Max. detection area: ~Ø 7,0m
CE requirements:
EMV complies with EN 61547
Low voltage complies with EN 60928
Detection area: ~Ø 1,5m … 4,0m (adjustable via shutter)