DALIeco LS/PD LI Technical information Edition:October 2012 Subject to change without any notice Design & Dimensions (Sensor/covers) Wiring diagram 1: Sensor connection of DALIeco Control 2: Connection cable 3: Sensor DALIeco LS/PD LI 4: Y-Connector Technical data Designation: DALIeco LS/PD LI Operating range light sensor: 20 … 800 lux (directly at sensor) Sensor connection: 4p4c, max. cable length in total: 25m (in total to all sensors) Ambient temperature: -20 °C …+ 50°C (in operation) Type of protection/protection class: IP 20 / II Presence detection angle Installation height = 2,0m: 40° … 90° (adjustable via sensor shutter) Installation height = 3,0m: Detection area: ~ Ø 2,0m … 6,0m Installation height 3,5m… 5,0m(max): Max. detection area: ~Ø 7,0m CE requirements: EMV complies with EN 61547 Low voltage complies with EN 60928 Detection area: ~Ø 1,5m … 4,0m (adjustable via shutter) SEE THE WORLD IN A NEW LIGHT