100A

AC1100 • 100 Amp Current Transformer
Low Cost 50/60Hz Current Transformers
Applications
• Sensing Overload Current
• Ground fault detection
• Metering
• Analog to Digital Circuits
• Competitive pricing due to high volume
production
• Manufactured in an ISO-9001:2000,
TS-16949:2002 and ISO-14001:2004
certified Talema facility
• Fully RoHS compliant
Electrical Specifications @ 20°C ambient
E lectrical S p ecificatio n s
Primary Current
100A nom., 250A max.
Turns Ratio
1000:1 nominal
Volt per Amp Ratio at 100A for 100 ohm load
0.100 V/A
Volt per Amp Ratio at 10A for 100 ohm load
0.0986 V/A
DC Resistance at 20°C
21.3 ohms
Dielectric Withstanding Voltage (Hi-pot)
4KVrms
Mechanical Specifications
E n viro n men tal S p ecificatio n s
Polycarbonate
Epoxy
Conforms to UL94-VO
Pins Ø 1.0mm
Marking
TALEMA
Date Code (W/Y)
AC1100, Dot at start pin
Approximate Weight
Tolerance
Storage Temperature
Insulation Resistance
10000
80 grams
±0.2mm
Output Volts vs Input Current
For various ohmic loads
5K 2K
1K
1000
100
10
500
0
200
400
600
800
1000
1200
1400
1600
Percent ratio error in %
10
200
Typical Excitation Curve
(AC1100)
100
100
50
1
10
100
1000
Input Current in Amps
Dimensions
14.30
44.50
Sec RMS Exciting Voltage in Volts
Output Voltage in Volts
100
Infinity
10K
-55° to +130°C
100 megohms min.
%RE vs RL at Rated primary current
(AC1100)
Load Resistance RL in ohms
C a se
Encapsulant
Flammibility
Terminals
10
1
0.1
0.01
44.50
TALEMA INDIA
W/Y
AC1100
5±1mm
Ø19.05
2
3
35.56
1
0.1
1
10
100
Sec RMS Exciting Current in mA
Ø 1.016
Notes:
1) Unless requested, the terminating resistor and the one-turn
primary are not supplied
2) Pin 3: Normally for mechanical support only but will be
used on center tapped designs
1
2.07
10.16
I - Turn
Primary 100A
3
100mA
RL
1W
10V
100 ohms