PDF version

Product Information
Bipolar Switch Hall-Effect IC Basics
Introduction
There are four general categories of Hall-effect IC devices
that provide a digital output: unipolar switches, bipolar
switches, omnipolar switches, and latches. Bipolar switches
are described in this application note. Similar application
notes on unipolar switches, omnipolar switches, and latches
are provided on the Allegro™ website.
Bipolar sensor ICs are designed to be sensitive switches.
(Note that the term “bipolar” refers to magnetic polarities,
and is not related to bipolar semiconductor chip structures.)
A bipolar switch has consistent hysteresis, but individual
units have switchpoints that occur in either relatively
more positive or more negative ranges. These devices find
application where closely-spaced, alternating north and
south poles are used, resulting in minimal required magnetic
signal amplitude, ΔB, because the alternation of magnetic
field polarity ensures switching, and the consistent hysteresis ensures periodicity.
Applications for detecting the position of a rotating shaft,
such as in a brushless dc motor (BLDC) are shown in figure 1. The multiple magnets are incorporated into a simple
structure referred to as a “ring magnet,” which incorporates
alternating zones of opposing magnetic polarity. The IC
package adjacent to each ring magnet is the Hall bipolar
switch device. When the shaft rotates, the magnetic zones
are moved past the Hall device. The device is subjected to
Hall ICs
Figure 1. Two bipolar device applications using ring magnets. The ring magnets have alternating N (north)
and S (south) polarity zones, which are rotated past the Hall devices, causing them to turn on and off.
27705-AN
the nearest magnetic field and is turned-on when a south field is
opposite, and turned-off when a north field is opposite. Note that
the branded face of the device is toward the ring magnet.
Magnetic Switchpoint Terms
The following are terms used to define the transition points, or
switchpoints, of Hall switch operation:
• B − The symbol for Magnetic Flux Density, the property of
a magnetic field used to determine Hall device switchpoints.
Measured in gauss (G) or tesla (T). The conversion is
1 G = 0.1 mT.
B can have a north or south polarity, so it is useful to keep in
mind the algebraic convention, by which B is indicated as a
negative value for north-polarity magnetic fields, and as a positive value for south-polarity magnetic fields. This convention
allows arithmetic comparison of north and south polarity values,
where the relative strength of the field is indicated by the absolute value of B, and the sign indicates the polarity of the field.
For example, a −100 G (north) field and a 100 G (south) field
have equivalent strength, but opposite polarity. In the same way,
a −100 G field is stronger than a −50 G field.
• BOP − Magnetic operate point; the level of a strengthening
magnetic field at which a Hall device switches on. The resulting state of the device output depends on the individual device
electronic design.
• BRP − Magnetic release point; the level of a weakening magnetic field at which a Hall device switches off (or for some types of
Hall devices, the level of a strengthening negative field given a
positive BOP ). The resulting state of the device output depends
on the individual device electronic design.
• BHYS − Magnetic switchpoint hysteresis. The transfer function of a Hall device is designed with this offset between the
switchpoints to filter out small fluctuations in the magnetic field
that can result from mechanical vibration or electromagnetic
noise in the application. BHYS = | BOP − BRP |.
Typical Operation
Bipolar switches usually have a positive BOP and negative BRP ,
but these switchpoints occur at field strength levels that are not
precisely symmetrical with respect to the neutral level, B = 0 G.
This characteristic is allowed so bipolar switches can provide
greater sensitivity and narrower BHYS than latching switches
(bipolar switches were originally conceived as a lower-cost alter-
Figure 2. The Hall effect refers to the measurable voltage present when an
applied current is influenced by a perpendicular magnetic field.
27705-AN
Allegro MicroSystems, LLC
115 Northeast Cutoff
Worcester, Massachusetts 01615-0036 U.S.A.
1.508.853.5000; www.allegromicro.com
2
native to early latches). A small percentage (≈10%) of bipolar
switches have switchpoint ranges entirely in the positive (south)
polarity range or entirely in the negative (north) polarity range.
All of these characteristic ranges can be reliably operated using
alternating positive (south) and negative (north) polarity fields.
Turn-off will usually occur when the magnetic field is removed,
but to ensure release, a field reversal is required.
An example of a bipolar switch would be a device with a maximum operate point, BOP(max), of 45 G, a minimum release point,
BRP(min), of –40 G, and a minimum hysteresis, BHYS(min), of 15
G. However, the minimum operate point, BOP(min), could be as
low as –25 G, and the maximum release point, BRP(max), could
be as high as 30 G. Figure 3 shows these characteristics for units
of a hypothetical device with those switchpoints. At the top of
figure 3, trace “Minimum ΔB” demonstrates how small an amplitude can result in reliable switching.
B
7.5
–7.5
Magnetic Flux Density, B (G)
VOUT
45
30
7.5
–7.5
–25
–40
Figure 3 illustrates the variances between the three general operating modes of bipolar switches:
• “latch mode” describes any bipolar switch unit with a positive
BOP and negative BRP , behaving like a Hall latching switch by
requiring both magnetic fields to be present for complete operation (but without actual latching of the device state)
• “unipolar mode” describes any bipolar switch unit with both
BOP and BRP in the positive (south) range
• “negative unipolar mode” (sometimes referred to as “negative
switch” mode) describes any bipolar switch unit with both BOP
and BRP in the negative (north) range
The release point flux density becomes less important because,
if the Hall switch has not switched when the pole has passed and
the flux density approaches the neutral level, B = 0 G, the switch
will certainly turn off when the following pole increases the flux
density in the opposite polarity. Bipolar Hall switches take advan-
BOP
BHYS(min)
BRP
Minimum ∆B
Minimum ∆B
BOP(max)
BHYS(min) Unipolar mode unit
BRP(max)
BOP
BHYS(min) Latch mode unit
BRP
BOP(min)
BHYS(min) Negative unipolar mode unit
BRP(min)
VOUT
Unipolar mode unit
VOUT
Latch mode unit
VOUT
Negative unipolar mode unit
Figure 3. Demonstration of possible switchpoint ranges for a bipolar switch, for
use with low magnetic flux amplitude, narrow pitch alternating pole targets.
27705-AN
Allegro MicroSystems, LLC
115 Northeast Cutoff
Worcester, Massachusetts 01615-0036 U.S.A.
1.508.853.5000; www.allegromicro.com
3
duty cycle will still be close to 50% on and 50% off. For motor
commutation this is ideal, resulting in high efficiency. Units
having unipolar mode turn on and off with the south pole and
do nothing as the north pole passes. Units in this mode will have
a duty cycle of perhaps 40% on and 60% off. Units in negative
unipolar mode turn off and on with the north pole and do nothing
as the south pole passes. Units in this mode will have a duty cycle
of perhaps 60% on and 40% off.
tage of this extra margin in release-point flux values to achieve
lower operate-point flux densities, a definite advantage in ring
magnet applications.
As can be seen in the VOUT traces at the bottom of figure 3, for
each of these modes, switching at each pole alternation is reliable,
with the duty cycle of the output differing somewhat according to
the operating mode. A bipolar device operating in latch mode has
nearly symmetrical switchpoints. This tends to set the duty cycle
to near perfection when working with equally-spaced ring magnet
poles. Having said that, even if the switchpoints were skewed, the
The three panels of figure 4 show the transfer characteristics of
the operating modes of bipolar sensor ICs.
BRP BOP
BHYS
VCC
VOUT
Switch to Low
Switch to High
VOUT(off)
VOUT(on)(sat)
0
B–
0
B+
Magnetic Flux Density, B (G)
Figure 4A. Latch mode characteristic. Note that the switchpoint hysteresis
zone, BHYS , includes the neutral flux density level, B = 0 G.
1. For purposes of explanation of figure 4A, assume the device powers-on with the magnetic flux density at the far
left, where the magnetic flux (B, on the horizontal axis) is more negative than BRP or BOP. Here the device is off,
and the output voltage (VOUT , on the vertical axis) is high.
2. Following the arrows toward the right, the magnetic field becomes increasingly positive. When the field is more
positive than BOP , the device turns on. This causes the output voltage to change to the opposite state, low.
3. While the magnetic field remains more positive than BRP , the device remains turned-on, and the output state
remains unchanged. This is true even if B becomes slightly less positive than BOP , within the built-in zone of
switching hysteresis, BHYS .
4. Following the arrows back toward the left, the magnetic field becomes less positive and then more negative.
When the magnetic field again drops below BRP , the device turns off. This causes the output to change back to
the original state, high.
27705-AN
Allegro MicroSystems, LLC
115 Northeast Cutoff
Worcester, Massachusetts 01615-0036 U.S.A.
1.508.853.5000; www.allegromicro.com
4
BRP BOP
BHYS
VCC
VOUT
Switch to Low
Switch to High
VOUT(off)
VOUT(on)(sat)
0
B– 0
B+
Magnetic Flux Density, B (G)
Figure 4B. Unipolar mode characteristic. Note that the switchpoint hysteresis zone, BHYS, is entirely more
magnetically south than the neutral flux density level, B = 0 G. A north magnetic field has no effect on the
device, although it can aid switching by dissipating any flux remaining after a south field has passed.
1. For purposes of explanation of figure 4B, assume the device powers-on with the magnetic flux density at the far
left, where the magnetic flux (B, on the horizontal axis) is less positive than BRP or BOP . Here the device is off,
and the output voltage (VOUT , on the vertical axis) is high.
2. Following the arrows toward the right, the magnetic field becomes increasingly positive. When the field is more
positive than BOP , the device turns on. This causes the output voltage to change to the opposite state, low.
3. While the magnetic field remains more positive than BRP , the device remains turned-on, and the output state
remains unchanged. This is true even if B becomes slightly less positive than BOP , within the built-in zone of
switching hysteresis, BHYS .
4. Following the arrows back toward the left, the magnetic field becomes less positive. When the magnetic field
again drops below BRP , the device turns off. This causes the output to change back to the original state, high.
BRP BOP
BHYS
VCC
VOUT
Switch to Low
Switch to High
VOUT(off)
VOUT(on)(sat)
0
B–
0 B+
Magnetic Flux Density, B (G)
Figure 4C. Negative unipolar (negative switch) mode characteristic. Note that the switchpoint
hysteresis zone, BHYS , is entirely more magnetically north than the neutral flux density level, B = 0 G.
A south magnetic field has no effect on the device, although it can aid switching by dissipating any flux
remaining after a north field has passed.
1. For purposes of explanation of figure 4C, assume the device powers-on with the magnetic flux density at the
far left, where the magnetic flux (B, on the horizontal axis) is more negative than BRP or BOP . Here the device is
off, and the output voltage (VOUT , on the vertical axis) is high.
2. Following the arrows toward the right, the magnetic field becomes less negative. When the field is less negative
than BOP, the device turns on. This causes the output voltage to change to the opposite state, low.
3. While the magnetic field remains less negative than BOP , the device remains turned-on, and the output state
remains unchanged. This is true even if B becomes slightly less positive than BOP , within the built-in zone of
switching hysteresis, BHYS .
4. Following the arrows back toward the left, the magnetic field becomes less positive. When the magnetic field
again drops below BRP , the device turns off. This causes the output to change back to the original state, high.
27705-AN
Allegro MicroSystems, LLC
115 Northeast Cutoff
Worcester, Massachusetts 01615-0036 U.S.A.
1.508.853.5000; www.allegromicro.com
5
Magnets
Power-On State
Individual magnets may be used to provide the two opposing
magnetic polarities, however, it is usually more cost effective
to use ring or strip magnet material. Ring and strip magnets are
magnetized with alternating poles with specified spacing. A ring
magnet is a toroid- or disc-shaped assembly (see figure 1) with
alternating radially- or axially-magnetized poles. A strip magnet
is a flat strip with alternating magnetic poles. Ring magnets are
available in a variety of materials including ceramic, rare earth,
and flexible materials. Strip magnets nearly always utilize flexible materials such as Nitrile rubber binder containing oriented
barium ferrite, or higher energy rare-earth materials.
A bipolar device powers-on in a valid state only if the magnetic
field strength either exceeds BOP or is less than BRP when power
is applied. If the magnetic field strength is in the hysteresis band,
that is between BOP and BRP , the device can assume either an
on or off state initially, and then attains the correct state at the
first excursion beyond a switchpoint. Devices can be designed
with power-on logic that sets the device off until a switchpoint is
reached.
Ring magnets normally are specified as having a number of poles
while strip magnets are normally specified in poles-per-inch. A
four-pole ring magnet contains two north and two south oriented
alternating poles (N-S-N-S) while an 11 pole-per-inch strip magnet has alternating poles spaced on 0.0909-in. centers. A variety
of pole spacings are available from magnet manufacturers.
Power-On States
Sensor IC Type
Power-On State (0 G Field)
Unipolar Switch
Off
Latch
Either state1,2
Negative Switch
On2
1Unless
power-on logic is incorporated in the design.
2Unless power-on of the device occurs while the magnetic field is
inside the specified magnetic hysteresis of the device.
Pull-Up Resistor
A pull-up resistor must be connected between the positive supply
and the output pin (see figure 4). Common values for pull-up
resistors are 1 to 10 kΩ. The minimum pull-up resistance is a
function of the sensor IC maximum output current (sink current) and the actual supply voltage. 20 mA is a typical maximum
output current, and in that case the minimum pull-up would be
VCC / 0.020 A. In cases where current consumption is a concern,
the pull-up resistance could be as large as 50 to 100 kΩ.
Caution: With large pull-up values it is possible to invite external
leakage currents to ground, which are high enough to drop the
output voltage even when the device is magnetically off. This
is not a device problem but is rather a leakage that occurs in the
conductors between the pull-up resistor and the sensor ICs output
pin. Taken to the extreme, this can drop the sensor IC output voltage enough to inhibit proper external logic function.
V+
VCC
CBYPASS
0.1 μF
RPULLUP
Hall Device
VOUT
GND
Use of Bypass Capacitors
Output
CBYPASS
0.1 μF
Refer to figure 5 for a layout of bypass capacitors. In general:
• For designs without chopper stabilization − It is recommended
that a 0.01 μF capacitor be placed the output and ground pins
and between the supply and ground pins.
• For designs with chopper stabilization − A 0.1 μF capacitor must be placed between the supply and ground pins, and
a 0.01 μF capacitor is recommended between the output and
ground pins.
27705-AN
Figure 5. Typical application diagram.
Allegro MicroSystems, LLC
115 Northeast Cutoff
Worcester, Massachusetts 01615-0036 U.S.A.
1.508.853.5000; www.allegromicro.com
6
Power-On Time
Q: Can I approach the device back side with the magnet?
Power-on time depends to some extent on the device design.
Digital output sensor ICs, such as the bipolar device, reach stability on initial power-on in the following times.
A: Yes, however bear this in mind: if the poles of the magnet
remain oriented in the same direction, then the orientation of
the flux field through the device remains unchanged from the
front-side approach (for example, if the south pole was nearer
the device in the front-side approach, then the north pole would
be nearer the device in the back-side approach). The north pole
would then generate a positive field relative to the Hall element,
while the south pole would generate a negative field.
Device type
Power-on time
Without chopper-stabilization
<4 μs
With chopper-stabilization
<25 μs
Basically, this means that prior to this elapsed time after providing power, device output may not be in the correct state, but after
this time has elapsed, device output is guaranteed to be in the
correct state.
Power Dissipation
Total power dissipation is the sum of two factors:
• Power consumed by the sensor IC, excluding power dissipated
in the output. This value is VCC times the supply current. VCC
is the device supply voltage and the supply current is specified
on the datasheet. For example, given VCC = 12 V and Supply
current = 9 mA. Power dissipation = 12 × 0.009, or 108 mW.
• Power consumed in the output transistor. This value is V(on)(sat)
times the output current (set by the pull-up resistor). If V(on)(sat)
is 0.4 V (worst case) and the output current is 20 mA (often
worst case), the power dissipated is 0.4 × 0.02 = 8 mW. As you
can see, because of the very low saturation voltage the power
dissipated in the output is not a huge concern.
Total power dissipation for this example is 108 + 8 = 116 mW.
Take this number to the derating chart in the datasheet for the
package in question and check to see if the maximum allowable
operational temperature must be reduced.
A: Yes. A “cleaner” signal is available when approaching from
the package front side, because the Hall element is located closer
to the front side (the package branded face) than to the back side.
For example, for the “UA” package, the chip with the Hall element is 0.50 mm inside the branded face of the package, and so
approximately 1.02 mm from the back-side face. (The distance
from the branded face to the Hall element is referred to as the
“active area depth.”)
Q: Can a very large field damage a Hall-effect device?
A: No. A very large field will not damage an Allegro Hall-effect
device nor will such a field add additional hysteresis (other than
the designed hysteresis).
Q: Why would I want a chopper-stabilized device?
A: Chopper-stabilized sensor ICs allow greater sensitivity with
more-tightly controlled switchpoints than non-chopped designs.
This may also allow higher operational temperatures. Most new
device designs utilize a chopped Hall element.
Possible Applications
Frequently Asked Questions
• Brushless dc motor rotation
Q: How do I orient the magnets?
A: The magnet poles are oriented towards the branded face of the
device. The branded face is where you will find the identification
markings of the device, such as partial part number or date code.
27705-AN
Q: Are there trade-offs to approaching the device back side?
• Speed sensing
• Pulse counters, encoders
• Automotive
Allegro MicroSystems, LLC
115 Northeast Cutoff
Worcester, Massachusetts 01615-0036 U.S.A.
1.508.853.5000; www.allegromicro.com
7
Suggested Devices
Allegro bipolar devices are listed in the selection guides on the company website, at
http://www.allegromicro.com/en/Products/Categories/Sensors/bipolar.asp.
Application Notes on Related Device Types
• Latching switches (latches) − http://www.allegromicro.com/en/Products/Design/latching/index.asp
• Omnipolar switches − http://www.allegromicro.com/en/Products/Design/omnipolar/index.asp
• Unipolar switches − http://www.allegromicro.com/en/Products/Design/unipolar/index.asp
Copyright ©2010-2013, Allegro MicroSystems, LLC
The information contained in this document does not constitute any representation, warranty, assurance, guaranty, or inducement by Allegro to the
customer with respect to the subject matter of this document. The information being provided does not guarantee that a process based on this information will be reliable, or that Allegro has explored all of the possible failure modes. It is the customer’s responsibility to do sufficient qualification
testing of the final product to insure that it is reliable and meets all design requirements.
For the latest version of this document, visit our website:
www.allegromicro.com
27705-AN
Allegro MicroSystems, LLC
115 Northeast Cutoff
Worcester, Massachusetts 01615-0036 U.S.A.
1.508.853.5000; www.allegromicro.com
8