M3G084-GF06-42 Operating instructions ebm-papst Mulfingen GmbH & Co. KG Bachmühle 2 D-74673 Mulfingen Phone +49 (0) 7938 81-0 Fax +49 (0) 7938 81-110 [email protected] www.ebmpapst.com 1. SAFETY REGULATIONS AND INFORMATION Read these operating instructions carefully before starting work on the device. Observe the following warnings to prevent malfunctions or danger to persons. These operating instructions are to be regarded as part of the device. The device is only to be sold or passed on together with the operating instructions. These operating instructions may be duplicated and distributed to inform about potential dangers and their prevention. Translation of the original operating instructions CONTENTS 1. SAFETY REGULATIONS AND INFORMATION 1 1.1 Hazard levels for warnings 1.2 Staff qualifications 1.3 Basic safety rules 1.4 Voltage 1.5 Electromagnetic radiation 1.6 Mechanical movement 1.7 Hot surface 1.8 Transport 1.9 Storage 1 1 1 1 2 2 2 2 2 2. INTENDED USE 3 3. TECHNICAL DATA 4 3.1 Product drawing 3.2 Nominal data 3.3 Technical description 3.4 Mounting data 3.5 Transport and storage conditions 3.6 Electromagnetic compatibility 4 5 5 5 5 5 4. CONNECTION AND STARTUP 6 4.1 Mechanical connection 4.2 Electrical connection 4.3 Connection in terminal box 4.4 Factory settings 4.5 Connection diagram 4.6 Checking connections 4.7 Switching on the device 4.8 Switching off the device 6 6 7 8 9 10 10 10 1.2 Staff qualifications 5. INTEGRATED PROTECTIVE FEATURES 10 6. MAINTENANCE, MALFUNCTIONS, POSSIBLE CAUSES AND REMEDIES 10 The safety hazards associated with the device must be assessed again following installation in the final product. Note the following when working on the device: 6.1 Cleaning 6.2 Safety inspection 6.3 Disposal 11 11 11 1.1 Hazard levels for warnings These operating instructions use the following hazard levels to indicate potentially hazardous situations and important safety regulations: DANGER Indicates an imminently hazardous situation which will result in death or serious injury if the specified actions are not taken. Compliance with the instructions is imperative. WARNING Indicates a potentially hazardous situation which can result in death or serious injury if the specified actions are not taken. Exercise extreme caution while working. CAUTION Indicates a potentially hazardous situation which can result in minor or moderate injury or damage to property if the specified actions are not taken. NOTE A potentially harmful situation can occur and, if not avoided, can lead to property damage. The device may only be transported, unpacked, installed, operated, maintained and otherwise used by suitably qualified, trained and authorized technical staff. Only authorized specialists are permitted to install the device, to carry out a test run and to perform work on the electrical installation. 1.3 Basic safety rules ; Do not perform any modifications, additions or conversions on the device without the approval of ebm-papst. 1.4 Voltage ; Check the device's electrical equipment at regular intervals; see Chapter 6.2 Safety inspection. ; Replace loose connections and defective cables immediately. DANGER Electrically charged device Risk of electric shock → When working on an electrically charged device, stand on a rubber mat. WARNING Live terminals and connections even with device switched off Electric shock Item no. 50852-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 1 / 12 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com M3G084-GF06-42 Operating instructions → Wait five minutes after disconnecting the voltage at all poles before opening the device. CAUTION In the event of a fault, the rotor and the impeller will be energized The rotor and the impeller have basic insulation. → Do not touch the rotor and impeller once installed. CAUTION If control voltage or a stored speed set value is applied, the motor will restart automatically, e.g. after a power failure. Risk of injury → Keep out of the device danger zone. → When working on the device, switch off the line voltage and ensure that it cannot be switched back on. → After working on the device, remove any tools or other objects from the device. CAUTION The motor restarts automatically when operating voltage is applied, e.g. after a power failure. Risk of injury → Keep out of the motor's danger zone. → When working on the motor, switch off the line voltage and ensure that it cannot be switched back on. → Wait until the motor comes to a stop. 1.5 Electromagnetic radiation Interference from electromagnetic radiation is possible, e.g. in conjunction with open- and closed-loop control devices. If impermissible radiation levels occur following installation, appropriate shielding measures have to be taken by the user. 1.7 Hot surface CAUTION High temperature on electronics housing Risk of burns → Ensure sufficient protection against accidental contact. 1.8 Transport CAUTION Transporting the motor Crushing hazard → Wear safety shoes and cut-resistant safety gloves. → Transport the motor in its original packaging only. → Secure the device so it cannot slip, e.g. by using a lashing strip. 1.9 Storage ; Store the device, partially or fully assembled, in a dry and weatherproof manner in the original packaging in a clean environment. ; Protect the device against environmental effects and dirt until final installation. ; We recommend storing the device for no longer than one year in order to guarantee trouble-free operation and the longest possible service life. ; Even devices explicitly intended for outdoor use are to be stored as described prior to commissioning. ; Maintain the storage temperature, see Chapter 3.5 Transport and storage conditions. ; Make sure that all cable glands are fitted with dummy plugs. NOTE Electrical or electromagnetic interference after installing the device in customer equipment. → Verify that the entire setup is EMC-compliant. Translation of the original operating instructions 1.6 Mechanical movement WARNING Rotating device Long hair and dangling items of clothing, jewelry and the like can become entangled and be pulled into the device. Injuries can result. → Do not wear any loose-fitting or dangling clothing or jewelry while working on rotating parts.#Protect long hair with a cap. WARNING Ejected parts If the motor is operated with attached fan blades, missing protective devices may allow balancing weights or broken fan blades to be ejected and cause injuries. → Take appropriate safety measures such as installing guard grilles. → Keep out of the exhaust zone. Item no. 50852-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 2 / 12 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com M3G084-GF06-42 Operating instructions 2. INTENDED USE The device is designed exclusively for use as a drive motor. Any other usage above and beyond this does not conform with the intended purpose and constitutes misuse of the device. Customer equipment must be capable of withstanding the mechanical and thermal stresses that can arise from this product. This applies for the entire service life of the equipment in which this product is installed. Intended use also includes ● Using the device only in power systems with grounded neutral (TN/ TT power systems). ● Using the device within the permitted ambient temperature range; see Chapter 3.5 Transport and storage conditions and Chapter 3.2 Nominal data. ● Operating the device with all protective devices. ● Following the operating instructions. Improper use In particular, operating the device in the following ways is prohibited and could be hazardous: Opening the terminal box during operation. ● Conveying air that contains abrasive particles. ● Conveying highly corrosive air, e.g. salt spray. Exception: devices designed for salt spray and correspondingly protected. ● Conveying air with high dust content, e.g. suctioning off sawdust. ● Operating the device close to flammable materials or components. ● Operating the device in an explosive atmosphere. ● Using the device as a safety component or to perform safety-related functions. ● Operation with completely or partially disassembled or manipulated protective devices. ● In addition, all applications not listed among the intended uses. Translation of the original operating instructions ● Item no. 50852-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 3 / 12 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com M3G084-GF06-42 Operating instructions 3. TECHNICAL DATA 3.1 Product drawing Translation of the original operating instructions All dimensions in mm. 1 2 3 4 5 6 7 Direction of rotation counterclockwise, viewed toward shaft Through-hole for M8 screw Max. clearance for screw 10 mm Max. clearance for screw 12 mm Cable diameter min. 4 mm, max. 10 mm, tightening torque 2.5 ± 0.4 Nm Tightening torque 3.5±0.5 Nm Groove depth 3 mm Item no. 50852-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 4 / 12 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com Operating instructions M3G084-GF06-42 3.2 Nominal data Motor M3G084-GF Phase Nominal voltage / VAC Nominal voltage range / VAC Frequency / Hz 3~ 400 380 .. 480 Method of obtaining data Speed / min-1 Power consumption / W Power output / W Current draw / A Rated torque / Ncm Min. ambient temperature / °C Max. ambient temperature / °C ml 50/60 3000 750 630 1.4 200 -25 40 ml = Max. load · me = Max. efficiency · fa = Free air cs = Customer specification · ce = Customer equipment Subject to change Translation of the original operating instructions 3.3 Technical description Weight Fan size Electronics housing material Housing material Direction of rotation Degree of protection Insulation class Moisture (F) / Environmental (H) protection class Installation position Cooling hole/opening Mode Motor bearing Technical features Touch current according to IEC 60990 (measuring circuit Fig. 4, TN system) 7.7 kg 84 mm Die-cast aluminum Die-cast aluminum Clockwise, viewed toward shaft IP55 "B" F3-1 Any On rotor side S1 Ball bearing - Output 10 VDC, max. 10 mA - Output 20 VDC, max. 50 mA - Output for slave 0-10 V - Input for sensor 0-10 V or 4-20 mA - Alarm relay - Integrated PID controller - Motor current limitation - PFC, passive - RS-485 ebmBUS - Soft start - Control input 0-10 VDC / PWM - Control interface with SELV potential safely disconnected from the mains - Thermal overload protection for electronics/motor - Line undervoltage / phase failure detection <= 3.5 mA Electrical hookup Motor protection Protection class Conformity with standards Via terminal box Thermal overload protector (TOP) internally connected I (if protective earth is connected by customer to the housing's connection point) EN 61800-5-1; CE With regard to cyclic speed loads, note that the rotating parts of the device are designed for a maximum of one million load cycles. If you have special questions, consult ebm-papst for support. 3.4 Mounting data ; Secure the screws against unintentional loosening (e.g. use selflocking screws). Strength class of screws 8.8 Any further mounting data required can be taken from the product drawing. 3.5 Transport and storage conditions ; Use the device in accordance with its degree of protection. Max. permitted ambient temp. for motor (transport/ storage) Min. permitted ambient temp. for motor (transport/ storage) + 80 °C - 40 °C 3.6 Electromagnetic compatibility EMC immunity to interference EMC circuit feedback EMC interference emission According to EN 61000-6-2 (industrial environment) According to EN 61000-3-2/3 According to EN 61000-6-3 (household environment) If several devices are switched in parallel on the supply side so that the line current of the arrangement is in the range of 1675 A, then this arrangement conforms to IEC 61000-3-12 provided that the short-circuit power Ssc at the connection point of the customer system to the public power system is greater than or equal to 120 times the rated output of the arrangement. It is the responsibility of the installation engineer or operator/ owner of the device to ensure, if necessary after consultation with the network operator, that this device is only connected to a connection point with a Ssc value that is greater than or equal to 120 times the rated output of the arrangement. Item no. 50852-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 5 / 12 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com M3G084-GF06-42 Operating instructions NOTE Device malfunctions possible Route the device's control lines separately from the supply line. 4. CONNECTION AND STARTUP 4.1 Mechanical connection → Maintain the greatest possible clearance. Recommendation: clearance > 10 cm (separate cable routing) WARNING Hot motor housing Risk of fire NOTE Water ingress into wires or cables Water ingress at the customer end of the cable can damage the device. → Ensure that no combustible or flammable materials are located close to the motor. CAUTION Cutting and crushing hazard when removing motor from packaging → Make sure the end of the cable is connected in a dry environment. → Carefully remove the device from its packaging. Strictly avoid shocks. Only connect the device to circuits that can be switched off with an all-pole disconnection switch. → Wear safety shoes and cut-resistant safety gloves. ; Check the device for transport damage. Damaged devices are not to be installed. ; Install the undamaged device in accordance with your application. CAUTION Possible damage to the device If the device slips during installation, serious damage can result. → Ensure that the device is securely positioned at its place of installation until all fastening screws have been tightened. 4.2 Electrical connection DANGER Voltage on the device Electric shock → Always connect a protective earth first. → Check the protective earth. DANGER Faulty insulation Risk of fatal injury from electric shock Translation of the original operating instructions → Use only cables that meet the specified installation regulations for voltage, current, insulation material, capacity, etc. → Route cables so that they cannot be touched by any rotating parts. DANGER Electrical charge (>50 µC) between phase conductor and protective earth connection after switching off supply with multiple devices connected in parallel. Electric shock, risk of injury → Ensure sufficient protection against accidental contact. Before working on the electrical hookup, short the supply and PE connections. CAUTION Voltage The motor is a built-in component and has no disconnecting switch. 4.2.1 Requirements ; Check whether the data on the nameplate match the connection data. ; Before connecting the device, make sure the power supply matches the device voltage. ; Only use cables designed for the current level indicated on the nameplate. For determining the cross-section, note the sizing criteria according to EN 61800-5-1. The protective earth must have a cross-section equal to or greater than that of the phase conductor. We recommend the use of 105 °C cables. Ensure that the minimum cable cross-section is at least AWG 26 / 0.13 mm². Ground conductor contact resistance according to EN 61800-5-1 Compliance with the impedance specifications according to EN 61800-51 for the protective earth connection circuit must be verified in the end application. Depending on the circumstances of installation, it may be necessary to connect an additional protective earth conductor to the extra protective earth terminal on the device. The protective earth terminal is on the housing and has a ground conductor symbol and a bore hole. 4.2.2 Supply connection and fuses Assignment of supply cable cross-sections and their required fuses (line protection only, no equipment protection). Nominal voltage 3/PE AC 380-480 VAC Fuse VDE 16 A UL 15 A Automatic circuit breaker VDE C16A Cable crosssection mm² 1.5 2.5 Cable crosssection *AWG 16 * AWG = American Wire Gauge → Only connect the motor to circuits that can be switched off with an all-pole disconnection switch. → When working on the motor, secure the system/machine in which the motor is installed so as to prevent it from being switched back on. Item no. 50852-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 6 / 12 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com M3G084-GF06-42 Operating instructions 4.2.3 Reactive currents Because of the EMC filter integrated for compliance with EMC limits (interference emission and immunity to interference), reactive currents can be measured in the supply line even when the motor is at a standstill and the line voltage is switched on. ● The values are typically less than 250 mA. ● At the same time, the effective power in this operating state (operational readiness) is typically < 5 W. 4.2.4 Residual current circuit breaker (RCCB) Only universal residual current devices (type B or B+) are allowed. As with variable frequency drives, residual current devices cannot provide personal safety while operating the device. When the device's power supply is switched on, pulsed charging currents from the capacitors in the integrated EMC filter can lead to the residual current devices tripping without delay. We recommend the use of residual current circuit breakers with a trip threshold of 300 mA and delayed tripping (super-resistant, characteristic K). 4.3.2 Connecting wires to terminals WARNING Live terminals and connections even with device switched off Electric shock → Wait five minutes after disconnecting the voltage at all poles before opening the device. ; Remove the cap from the cable gland. Only remove caps where cables are fed in. ; Route the wire(s) (not included in scope of delivery) into the terminal box. ; First connect the "PE" (protective earth). ; Connect the wires to the corresponding terminals. Use a screwdriver to do so. When connecting, ensure that no wire ends fan out. 4.2.5 Leakage current For asymmetrical power systems or if a phase fails, the leakage current can increase to a multiple of the nominal value. 4.2.6 Locked-rotor protection Due to the locked-rotor protection, the starting current (LRA) is equal to or less than the nominal current (FLA). 4.3 Connection in terminal box 4.3.1 Preparing cables for connection Translation of the original operating instructions Only strip the cable as far as necessary, ensuring that the cable gland is sealed and there is no strain on the connections. For tightening torques, see Chapter 3.1 Product drawing. NOTE Tightness and strain relief are dependent on the cable used. → This must be checked by the user. Fig. 2: Connecting wires to terminals ; Seal the terminal box. 4.3.3 Cable routing Water must be prevented from reaching the cable gland along the cable. When routing the cable, make sure that the cable glands are located at the bottom. The cables must always be routed downward. Fig. 1: Recommended stripped lengths in mm (inside terminal box) Legend: CL = control lines Item no. 50852-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 7 / 12 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com Operating instructions M3G084-GF06-42 Fig. 3: Cable routing for fans installed upright. 4.4 Factory settings Factory settings made for the device by ebm-papst. PWM control 1 1 100 0 No Analog Positive (heating) Translation of the original operating instructions Mode Group address Fan/device address Max. PWM / % Min. PWM / % Save set value to EEPROM Set value requirement Direction of action Item no. 50852-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 8 / 12 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com M3G084-GF06-42 Operating instructions 4.5 Connection diagram Translation of the original operating instructions Drawing preliminary! No. PE KL1 KL2 KL2 Conn. 1, 2, 3 1 2 Designation PE L1, L2, L3 NC COM KL2 KL3 3 1 NO OUT KL3 KL3 2, 8 3, 7 GND 0-10 V KL3 4 +10 V KL3 5 +20 V KL3 KL3 KL3 6 9, 11 10, 12 4-20 mA RSB RSA Function/assignment Protective earth terminal Power supply 50/60 Hz Floating status contact, break for failure floating status contact, changeover contact, common connection (2 A, max. 250 VAC, min. 10 mA, AC1) Floating status contact, make for failure Analog output, 0-10 VDC, max. 3 mA, SELV, output of current motor modulation level: 1 V corresponds to 10% modulation level. 10 V corresponds to 100% modulation level. Reference ground for control interface, SELV Use control / current sensor value input 0-10 VDC, impedance 100 kΩ only as alternative to 4-20 mA input, SELV Voltage output 10 VDC (±3%), max. 10 mA, power supply for external devices (e.g. potentiometer), SELV Voltage output 20 VDC (+25%/-10%), max. 50 mA, power supply for external devices (e.g. sensors), SELV Use control / current sensor value input 4-20 mA, impedance 100 Ω only as alternative to 0-10 V input, SELV RS485 interface for ebmBUS, RSB, SELV RS485 interface for ebmBUS, RSA, SELV Item no. 50852-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 9 / 12 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com M3G084-GF06-42 Operating instructions 4.6 Checking connections 5. INTEGRATED PROTECTIVE FEATURES ; Ensure isolation from supply (all phases). The integrated protective functions cause the motor to switch off automatically in the event of the faults described in the table. The status relay drops out and the fault is reported via bus. ; Make sure a restart is impossible ; Check the cables for proper fit. ; Screw the terminal box cover back on again. Terminal box tightening torque, see Chapter 3.1 Product drawing. ; Route the cables in the terminal box so that the terminal box cover closes without resistance. ; Use all screw plugs. Insert the screws by hand to avoid damage to the threads. ; Make sure the terminal box is completely closed and sealed and that all screws and cable glands have been properly tightened. 4.7 Switching on the device Fault Rotor position detection error Blocked rotor Line undervoltage (line voltage outside of permitted nominal voltage range) Phase failure The device may only be switched on if it has been installed properly and in accordance with its intended use, including the required safety mechanisms and professional electrical hookup. This also applies for devices which have already been equipped with plugs and terminals or similar connectors by the customer. ; Before switching on, check the device for visible external damage and make sure the protective devices are functional. ; Check the fan's air flow paths for foreign matter and remove any foreign matter found. ; Apply the nominal supply voltage. ; Start the device by changing the input signal. 4.8 Switching off the device Switching off the device during operation: ; Switch off the device via the control input. ; Do not switch the motor (e.g. in cyclic operation) on and off via power supply. Switching off the device for maintenance: ; Switch off the device via the control input. ; Do not switch the motor (e.g. in cyclic operation) on and off via power supply. Translation of the original operating instructions ; Disconnect the device from the power supply. ; When disconnecting, be sure to disconnect the ground connection last. Safety feature description/ function An automatic restart follows. ; After the blockage is removed, the motor restarts automatically. ; If the line voltage returns to permitted values, the motor restarts automatically. A phase of the supply voltage fails for at least 5 s. ; When all phases are correctly supplied again, the motor automatically restarts after 10-40 s. 6. MAINTENANCE, MALFUNCTIONS, POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device. Send the device to ebmpapst for repair or replacement. WARNING Live terminals and connections even with device switched off Electric shock → Wait five minutes after disconnecting the voltage at all poles before opening the device. CAUTION The motor restarts automatically when operating voltage is applied, e.g. after a power failure. Risk of injury → Keep out of the motor's danger zone. → When working on the motor, switch off the line voltage and ensure that it cannot be switched back on. → Wait until the motor comes to a stop. CAUTION If control voltage or a stored speed set value is applied, the motor will restart automatically, e.g. after a power failure. Risk of injury → Keep out of the device danger zone. → When working on the device, switch off the line voltage and ensure that it cannot be switched back on. → After working on the device, remove any tools or other objects from the device. If the device is out of use for some time, e.g. when in storage, we recommend switching it on for at least two hours to allow any condensation to evaporate and to move the bearings. Malfunction/fault Possible cause Possible remedy Item no. 50852-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 10 / 12 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com Operating instructions M3G084-GF06-42 Rotor not running smoothly Imbalance in rotating parts Motor not turning Mechanical blockage Line voltage faulty Faulty connection Broken motor winding Thermal overload protector activated Deficient cooling Translation of the original operating instructions Ambient temperature too high Clean the device; replace it if imbalance persists after cleaning Switch off, isolate from supply and remove mechanical blockage. Check line voltage, restore power supply. Attention! The error message resets automatically. Device restarts automatically without warning. Isolate from supply, correct connection; see connection diagram. Replace device Allow motor to cool off, locate and rectify cause of error, release restart lockout if necessary Improve cooling. Let the device cool down. To reset the error message, switch off the line voltage for at least 25 s and then switch it on again. Alternatively, reset the error message by applying a control signal of < 0.5 V to Din1 or by shorting Din1 to GND. Reduce the ambient temperature. Let the device cool down. To reset the error message, switch off the line voltage for at least 25 s and then switch it on again. Alternatively, reset the error message by applying a control signal of < 0.5 V to Din1 or by shorting Din1 to GND. Impermissible point of Correct the operating operation (e.g. back point. Let the device pressure too high) cool down. To reset the error message, switch off the line voltage for at least 25 s and then switch it on again. Alternatively, reset the error message by applying a control signal of < 0.5 V to Din1 or by shorting Din1 to GND. In the event of further malfunctions, contact ebm-papst. 6.1 Cleaning NOTE Damage to the device during cleaning Malfunction possible → Do not clean the device using a high-pressure cleaner.# Do not use acid, alkali or solvent-based cleaning agents. → Do not use any pointed or sharp-edged objects for cleaning 6.2 Safety inspection NOTE High-voltage test The integrated EMC filter has Y capacitors. The tripping current is exceeded when AC testing voltage is applied. → Test the device with DC voltage when you perform the legally required high-voltage test. The voltage to be used corresponds to the peak value of the AC voltage required by the standard. What to check Device for damage Fastening the cables Insulation of cables for damage Condensation drainage holes for clogging, where necessary How to check How often Visual inspection At least every 6 months Visual inspection At least every 6 months Visual inspection At least every 6 months What action? Replace device Visual inspection At least every 6 months Open holes Fasten Replace cables 6.3 Disposal For ebm-papst, environmental protection and resource preservation are top priority corporate goals. ebm-papst operates an environmental management system which is certified in accordance with ISO 14001 and rigorously implemented around the world on the basis of German standards. Right from the development stage, ecological design, technical safety and health protection are fixed criteria. The following section contains recommendations for ecological disposal of the product and its components. Item no. 50852-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 11 / 12 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com M3G084-GF06-42 Operating instructions 6.3.1 Country-specific legal requirements NOTE Country-specific legal requirements Always observe the applicable country-specific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle. The corresponding disposal standards are also to be heeded. 6.3.2 Disassembly Disassembly of the product must be performed or supervised by qualified personnel with the appropriate technical knowledge. The product is to be disassembled into suitable components for disposal employing standard procedures for motors. WARNING Heavy parts of the product may drop off. Some of the product components are heavy. These components could drop off during disassembly. This can result in fatal or serious injury and material damage. → Secure components before unfastening to stop them falling. 6.3.3 Component disposal The products are mostly made of steel, copper, aluminum and plastic. Metallic materials are generally considered to be fully recyclable. Separate the components for recycling into the following categories: ● Steel and iron ● Aluminum ● Non-ferrous metal, e.g. motor windings ● Plastics, particularly with brominated flame retardants, in accordance with marking ● Insulating materials ● Cables and wires ● Electronic scrap, e.g. circuit boards Only ferrite magnets and not rare earth magnets are used in external rotor motors from ebm-papst Mulfingen GmbH & Co. KG. Translation of the original operating instructions ; Ferrite magnets can be disposed of in the same way as normal iron and steel. Electrical insulating materials on the product, in cables and wires are made of similar materials and are therefore to be treated in the same manner. The materials concerned are as follows: ● Miscellaneous insulators used in the terminal box ● Power cables ● Cables for internal wiring ● Electrolytic capacitors Dispose of electronic components employing the proper procedures for electronic scrap. → Please contact ebm-papst for any other questions on disposal. Item no. 50852-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 12 / 12 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com