LITTELFUSE 216010

Axial Lead and Cartridge Fuses
Designed to IEC Standard
5 x 20 mm Fast-Acting Fuse 216 Series
®
®
• Designed to International (IEC) Standards for use globally.
• Meets the IEC 60127-2, Sheet 1 specification for Fast Acting Fuses.
• Available in Cartridge and Axial Lead Form.
• Available in ratings of 0.050 to 10 amperes.
• High breaking capacity.
ELECTRICAL CHARACTERISTICS:
150%
210%
275%
400%
1000%
Ampere
Rating
.05 – 6.3
8-16
Opening
Time
60 minutes, Minimum
30 minutes, Minimum
.05 – 16
30 minutes, Maximum
.05 – 4
5– 6.3
8-16
.05 – 6.3
8-16
.05 – 6.3
8-16
0.01 sec., Min.; 2 sec. Max.
0.01 sec., Min.; 3 sec. Max.
0.04 sec., Min.; 20 sec. Max.
.003 sec., Min.; 0.3 sec. Max.
.01 sec., Min.; 1.0 sec. Max.
.02 seconds, Maximum
.03 seconds, Maximum
INTERRUPTING RATING:
0.05 - 10A
Ampere
Rating
.050
.063
.080
.100
.125
.160
.200
.250
.315
.400
.500
.630
.800
1
1.25
1.6
2
2.5
3.15
4
5
6.3
8*
10*
Voltage
Rating
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
cycles –65°C to +125°C)
Vibration: MIL-STD-202F Method 201A
Humidity: MIL-STD-202F Method 103B, Test Condition A. high relative
humidity (95%) and elevated temperature (40°C) for 240 hours.
Salt Spray: MIL-STD-202F Method 101D, Test Condition B
PHYSICAL SPECIFICATIONS:
Material: Body: Ceramic
1500A @ 250 VAC, 0.7-0.8 power factor
Cap: Nickel Plated Brass
Leads: Tin Plated Copper
Filler Sand (160mA – 10A)
Terminal Strength: MIL-STD-202F Method 211A,
Test Condition A
Solderability: Reference IEC 60127 Second Edition 2003-01 Annex A
ORDERING INFORMATION:
Cartridge
Catalog
Number
216.050
216.063
216.080
216.100
216.125
216.160
216.200
216.250
216.315
216.400
216.500
216.630
216.800
216 001
216 1.25
216 01.6
216 002
216 02.5
216 3.15
216 004
216 005
216 06.3
216 008
216 010
ENVIRONMENTAL SPECIFICATIONS:
Operating temperature: -55˚C to 125˚C
Thermal Shock: MIL-STD-202F Method 107G, Test Condition B: (5
Nominal
Resistance
Cold Ohms
15.900
10.450
7.885
5.793
3.675
5.349
3.350
2.350
1.850
0.903
0.847
0.466
0.295
0.237
0.153
0.111
0.076
0.058
0.037
0.025
0.018
0.014
0.010
0.008
Nominal
Melting I2t
A2 Sec.
0.00019
0.00054
0.00084
0.00450
0.00545
0.00576
0.00438
0.00891
0.015
0.036
0.169
0.179
0.288
0.180
0.477
1.008
1.870
2.697
6.700
14.996
27.460
56.429
64.316
154.339
11
Product Marking: Cap 1: current and voltage rating.
Cap 2: Agency approval markings.
Packaging: Available in Bulk (V=5, H=100, M=1000 pcs/pkg) or on
Tape/Reel (MRET1=1000 pcs/reel).
w w w. l i t t e l f u s e . c o m
421
AXIAL LEAD AND
CARTRIDGE FUSES
% of Ampere
Rating
Axial Lead and Cartridge Fuses
Designed to IEC Standard
5 x 20 mm Fast-Acting Fuse 216 Series
®
®
Agency Approvals
Agency Approvals
Certificate No.
Certificate No.
Certificate No.
Cartridge
NBK250702-E10480
NBK250702-E10480
Leaded
NBK250702-E10480
NBK250702-E10480
Ampere Range
20+0.5
0216 000
A&C
E
5.2+0.1
-0.2
1A – 10A
5.1+0.6
B&D
F
2003010207079960
2002010207007594
50mA – 800mA
1A – 6.3A
SU05001-2013
1A – 10A
0216.050 XE
to
0216.100 XE
40
5.1+0.6
6.0 MAX
22.5 MAX
0.65
Recognised File No. E10480
Guide No.
JDYX2
File No.
Acc. Class No.
029862
LR1422-30
Licence No.
KM41462
File No.
9848103, 9931059
304518 & 304555
50mA – 10A
0216001.XE
to
0216010.XE
1A – 6.3A
40
5.8 MAX
22.5 MAX
0.65*
All dimensions in mm
32mA – 6.3A
Notes:
* Ratings above 6.3A
have 0.8 mm dia lead
50mA – 10A
Average Time Current Curves
0.050A
0.063A
0.080A
0.100A
0.125A
0.160A
0.200A
0.250A
0.315A
0.400A
0.500A
0.630A
0.800A
1A
1.25A
1.6A
2A
2.5A
3.15A
4A
5A
6.3A
8A
10A
12.5A
16A
®
10000
1000
100
10
TIME IN SECONDS
®
1
0.1
0.01
0.001
0.01
0.1
1
10
CURRENT IN AMPERES
422
w w w. l i t t e l f u s e . c o m
100
1000