Mining Cable Engineering Handbook 2nd Edition Table of Contents 1. GENERAL PROPERTIES OF COPPER. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 1 1.1 Resistance to Annealing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 1 1.1.1 Table 1: Solid Wire Breaking Strength. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 1 1.2 Table 2: Properties of Annealed Copper Wire. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 1 1.3 The AWG. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 2 1.3.1 Rules of Thumb for AWG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 2 1.3.2 AWG Conversions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 2 1.3.2.1Table 3: Wire Conversions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 2 2. RESISTANCE AND RESISTIVITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 3 2.1 DC Resistance of Stranded Conductors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 3 2.1.1 Table 4: Factors for Determining DC Resistance of Uncoated and Coated Copper Strand . . . . . . . . . . . . . . . . . . . . . . . Pg. 3 2.1.2 Table 5: Copper Wire DC Resistance @ 20°C (68°F) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 4 2.2 2.2.1 Skin Effect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 4 AC Resistance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 4 2.2.2 Proximity Effect. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 4 2.3 2.3.1 Table 6: Resistance and Inductance Ratios due to Skin Effect. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 5 Inter-Strand AC Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 5 3. AMPACITY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 6 3.1 3.1.1 Table 7: Ampacities for Portable Power Cables with 90°C Insulation, Amperes per Conductor . . . . . . . . . . . . . . . . . . . Pg. 6 Method of Calculations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 6 3.1.2 Table 8: Ampacities for Mine Power Feeder Cables with 90°C Insulation, Three Conductor . . . . . . . . . . . . . . . . . . . . . Pg. 7 3.1.3. Table 9: Approximate Ampacity Correction Factors for Cables of all Voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 7 3.1.4. Table 10: Allowable Short Circuit Currents for Insulated Copper Conductors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 8 3.2 Warning: Hot Conductors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 9 4. IMPEDANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 10 4.1 Impedance Terms and Calculations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 10 4.2 Reactance Terms and Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 10 4.2.1 Table 11: Resistance and Reactance of Portable Power Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 11 4.2.2 Table 12: Resistance and Reactance of Mine Power Feeder Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 11 4.3 4.3.1 Table 13: Approximate Voltage Drop Factors at 90°C and 75°C Conductor Temperatures . . . . . . . . . . . . . . . . . . . . . Pg. 12 4.4 Voltage Regulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 12 4.5 Improving Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 12 Voltage Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 12 5. SHIELDING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 13 5.1 5.1.1 Figure 1: Cable as a Capacitor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 13 Cable as a Capacitor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 13 5.2 5.2.1 Figure 2: Conductor Shielding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 14 5.3 5.3.1 To Eliminate Non-Symmetrical Electrical Stresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 14 5.3.2 To Provide a Definite Capacitance to Ground for the Insulated Conductor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 15 5.3.3 To Reduce the Hazard of Both Shock and Danger to Life and Property. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 15 Shielding and Stress Relief in Insulated Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 14 Functions of Insulation Shielding Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 14 5.4 Insulation Stress Relief (Insulation Shielding). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 15 5.5 Stress-Relief Cones. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 16 5.5.1 Figure 3: Voltage Gradient vs. Distance along Dielectric from Shield. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 16 5.6 5.6.1 Figure 4: Stress Distribution at Edge of the Shielding System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 16 5.7 Stress-Relief Mechanism . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 17 5.7.1 Figure 5: Conductor Stresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 17 5.8 Extruded Stress-Relief Layer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 17 5.9 Applications of Shields. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 17 5.10 Effects of Shield Loss on Ampacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 18 5.11 Dielectric Constant. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 18 5.11.1 Table 14: Shielding Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 19 Concentrated Stresses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 16 6. INSULATION AND JACKET STABILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 20 6.1 Partial Discharge Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 20 6.2 The Major Prerequisite of Insulated Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 20 6.3 Ozone Resistance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 20 6.4 Jacket — Physical Toughness. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 21 6.5 Jacket — Hardness. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 21 6.6 Thermal Stability and Heat Resistance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 21 6.7 Moisture Penetration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 22 6.7.1 Table 15: Moisture Transmission. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 22 6.8 Sunlight Resistance of Cable Coverings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 22 6.9 ICEA Minimum Requirements for Mining Cable Jackets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 22 6.9.1 Table 16: ICEA Minimum Requirements for CPE and CSPE Jackets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 22 6.9.2 Table 17: ICEA Minimum Requirements for Thermoplastic Polyurethane Jackets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 22 7. FLEXIBILITY AND FLEX LIFE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 23 7.1 Low Temperature Flexibility. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 23 7.2 Flex Life as a Function of Stress. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 23 7.3 Bending Radii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 24 7.3.1 Table 18: Flex Life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 24 7.4 ICEA Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 24 8. STANDARD PRODUCT LINE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 25 8.1 Table 19: Product Matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 25 8.2 Table 20: Mining Cable Product Constructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 26 8.3 Table 21: Mining Cable Application Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 27 9. TECHNICAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 28 9.1 Engineering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 28 9.1.1 Table 22: Ampacity Correction Factors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 28 9.1.2 Table 23: Voltage Drop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 28 9.1.3 Table 24: AWG-to-Metric Conversion Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 28 9.2 Why and How Mining Cables Fail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 29 9.3 Table 25: Unit Conversion Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 30 9.4 Table 26: Temperature Conversion Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg. 31 The information contained herein is intended for evaluation by technically skilled persons. Any person relying on this document does so at their own independent discretion and sole risk, assumes all risks and liability whatsoever in connection with such use, and General Cable will have no liability with respect thereto, whether the claim is based in contract, tort or other legal theory. General Cable makes no representations or warranties, expressed or implied, with respect to the accuracy, completeness or reliability of this document. GENERAL PROPERTIES OF COPPER 1.1 Resistance to Annealing Both hard-drawn and medium-hard tempered wire can become annealed when used to conduct high current. Because current heating causes wire to lose tensile strength, it is imperative that hard-drawn and mediumhard tempers are designed to resist annealing. Test values of tensile strength and elongation properties of copper wire are used to determine its final temper. See 1.1.1 Table 1 for specifics of solid wire breaking strength. 1.1.1 Table 1: Solid Wire Breaking Strength Approximate Tensile Strength HARD-DRAWN1 Size (AWG) 4/0 3/0 2/0 1/0 1 MEDIUM-HARD2 ANNEALED (SOFT) 3 lbs kg lbs kg lbs kg 8143 6720 5519 4518 3688 3693 3048 2503 2049 1672 6980 5666 4599 3731 3024 3166 2570 2086 1692 1371 5983 4744 3763 2985 2432 2713 2151 1706 1354 1103 2 3 4 5 6 3002 2439 1970 1590 1280 1361 1106 893 721 580 2450 1984 1584 1265 1010 1111 899 718 573 458 1928 1529 1213 961 762 874 693 550 436 345 7 8 9 10 11 1030 826 660 529 423 467 374 299 240 191 806 644 513 410 327 365 292 233 186 148 605 479 380 314 249 274 217 172 142 112 12 13 14 15 16 337 268 214 170 135 152 121 97 77 61 262 209 167 133 106 118 94 75 60 48 197 157 124 98 78 89 71 56 44 35 1Hard-Drawn wire has the highest tensile strength, lowest conductivity and lowest elongation of the tempers. The hot-roll rod is cold-drawn without annealing, which work-hardens the wire. 2Medium-Hard requires the hot-roll rod be briefly cold-worked to the desired diameter. The wire is then heated moderately. The tensile strength, conductivity and elongation properties are mid-way between hard-drawn and annealed. 3Annealed (Soft) wire is cold-drawn first to the desired diameter, then a high heat is applied to soften the copper. This temper has the lowest tensile strength, highest conductivity and greatest elongation of the three tempers. 1.2 Table 2: Properties of Annealed Copper Wire 1 1 Atomic Weight 63.57 Atomic Number 29 Density at 20°C 8.89 g/cm³ Melting Point 1083°C - 1981.4°F Boiling Point 2310°C - 4190°F Specific Heat, 25°C 0.0918 cal per g per deg C Latent Heat of Fusion 43.3 g-cal per gram Linear Coefficient of Expansion 0.00001692 per deg C/0.0000094 per deg F Electrical Resistivity at 20°C 0.15328 ohm (meter gram) Temperature Coefficient of Resistivity at 20°C 0.00393 per deg C Thermal Conductivity 0.93 cal/cm²/cm/sec/deg C 1.3 The AWG 1.3.2AWG Conversions Copper conductor size conversion is determined by: Circular mils = sq in. x 1,273,240 = sq mm x 1,973.5 For cross-sectional forms other than circular, where S is the cross-sectional area in square inches, the conversions are: AWG sizes represent the successive steps in the process of drawing wire. The AWG uses a simple mathematical law to determine size, and its numbers are retrogressive to wire size represented. • Diameters are formed by geometrical progressions based on two diameter specifications. • The basis of the AWG is the diameter of No. 4/0 defined as 0.0046 in. and No. 36 as 0.0050 in. The 38 sizes between these two diameters are specified by the ratio of any diameter to the diameter of the next greater number, as shown below: 39 39 0.4600 92 = 0.0050 X = 1.1229322 • The square of the ratio equals 1.26010. • The sixth power of the ratio equals 2.0050 to the next greater diameter. • As the ratio is approximately 2, it applies a number of useful relations and short cuts in wire computations. 1.3.1 Rules of Thumb for AWG All rules are approximate. 1.An increase of three gauge numbers doubles the area and weight and halves the dc resistance. 2.An increase of six gauge numbers doubles the diameter. 3.An increase of ten gauge numbers multiplies the area and weight by 10 and divides the resistance by 10. 4.For sizes 4/0 AWG to 29 AWG, the maximum and minimum diameters can be found by adding or subtracting 1% of the nominal diameters. 5.For sizes 30 AWG to 46 AWG, the maximum and minimum diameters can be found by adding or subtracting .0001" of the nominal diameters. 6.The weight of 2 AWG copper wire is very close to 200 lb per 1000 ft. 7. A 10 AWG wire has a diameter of approximately 0.10 in., an area of about 10,000 cir mils and a resistance of approximately 1.0 ohm per 1000 ft. 0.0081455 S Feet per ohm at 20°C = 122770 x S 2.1135 Ohms per pound at 20°C = 2 6 S 10 Pounds per ohm at 20°C = 473160 x S2 Pounds per 1000 feet at 20°C = 3854.09 x S Ohms per 1000 feet at 20°C = Feet per pound at 20°C = 0.259465 S Mil is the term used to express wire diameter measurement and represents a unit of length equal to 1/1000 of an inch. Circular mil is used to define cross-sectional areas. One circular mil equals 0.7854 square mil. For actual wire conversions, see 1.3.2.1 Table 3. 1.3.2.1 Table 3: Wire Conversions SIZE AWG/ kcmil 500 350 300 250 4/0 3/0 2/0 1/0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 cir mils 500000 350000 300000 250000 211600 167800 133100 105600 83690 66360 52620 41740 33090 26240 20820 16510 13090 10380 8230 6530 5180 4110 3260 2580 CROSS-SECTIONAL AREA sq inch 0.3927 0.2749 0.2356 0.1963 0.1662 0.1318 0.1045 0.0829 0.0657 0.0521 0.0413 0.0328 0.0260 0.0206 0.0164 0.0130 0.0103 0.0082 0.0065 0.0051 0.0041 0.0032 0.0026 0.0020 sq mm 253.4 177.3 152.0 126.7 107.2 85.0 67.4 53.5 42.4 33.6 26.7 21.1 16.8 13.3 10.5 8.4 6.6 5.3 4.2 3.3 2.6 2.1 1.7 1.3 WEIGHT lb/1000 ft 1513.5 1059.5 908.0 756.6 640.5 507.8 402.8 319.5 253.3 200.9 159.3 126.3 100.2 79.4 63.0 50.0 39.6 31.4 24.9 19.8 15.7 12.4 9.9 7.8 kg/km 2252.1 1576.5 1351.1 1125.8 952.8 755.4 599.2 475.3 376.8 298.9 237.0 187.9 149.1 118.1 93.8 74.4 58.9 46.8 37.0 29.5 23.4 18.4 14.7 11.6 OVERALL DIAMETER inch 0.707 0.592 0.548 0.500 0.460 0.410 0.365 0.325 0.289 0.258 0.229 0.204 0.182 0.162 0.144 0.128 0.114 0.102 0.091 0.081 0.072 0.064 0.057 0.051 mm 17.96 15.04 13.92 12.70 11.68 10.41 9.27 8.26 7.34 6.50 5.82 5.18 4.62 4.12 3.66 3.25 2.90 2.59 2.31 2.06 1.83 1.63 1.45 1.30 2 RESISTANCE AND RESISTIVITY It is commonly held that electric current in stranded conductors is confined to individual strands and does not transfer from strand to strand parallel to the axis of the conductor. Using this reasoning, dc resistance is calculated as follows: 2 • Compare the length of each strand to the axial length of the conductor. Average the increased length of the strands. • Multiply the effective cross-sectional area (the first product) by the average strand length increase to get the strand resistance. • Multiply the number of individual strands by the cross-section area of one wire. This product is the effective cross-sectional area of the conductor. 2.1 DC Resistance of Stranded Conductors In accordance with ASTM Specification B189-63, Tables 4 and 5 show factors for determining the dc resistance of uncoated and coated copper stranded conductors. 2.1.1 Table 4: Factors for Determining DC Resistance of Uncoated and Coated Copper Strand Uncoated Coated Diameter of Individual Coated Wires, Inch All Sizes 0.460-0.290 0.289-0.103 0.102-0.201 0.0200-0.0111 0.0110-0.0030 94.16 93.15 Minimum Conductivity, Percent 100 98 97.66 97.16 96.16 Temperature, Degrees C Conductor 25 20 25 20 25 20 25 20 25 20 25 20 25 20 Resistance Factors — Ohms per Circular Mil * CONCENTRIC To 2000 kcmil 10786 10579 10989 2001 to 3000 10892 10682 11097 3001 to 3400 10998 10786 11205 4001 to 5000 11104 10890 11313 ROPE-LAY — Concentric-Stranded Members 49 Wires 10892 10682 11097 133 Wires 10998 10786 11205 259 Wires 11051 10838 11259 427 Wires 11104 10890 11313 Over 427 Wires 11209 10993 11420 ROPE-LAY — Bunch-Stranded Members 7 Ropes 10998 10786 11205 19, 37, 61 Ropes 11104 10890 11313 7 x 7 Ropes 11209 10993 11420 19 x 7, 37 x 7 or 61 x 7 Ropes 10795 10900 11006 11112 11045 11153 11261 11370 10832 10938 11044 11150 11102 11210 11319 11428 10888 10994 11101 11208 11217 11327 11437 11547 11001 11109 11217 11325 11456 11568 11681 11793 11235 11345 11455 11566 11579 11693 11806 11920 11356 11647 11579 11690 10900 11006 11059 11112 11199 11153 11261 11315 11370 11478 10938 11044 11097 11150 11257 11210 11319 11374 11428 11537 10994 11101 11155 11208 11315 11327 11437 11492 11547 11657 11109 11217 11271 11325 11432 11568 11681 11737 11793 11905 11345 11455 11511 11566 11676 11693 11806 11863 11920 12033 11467 11579 11634 11690 11801 11006 11112 11199 11261 11370 11478 11044 11150 11257 11319 11428 11537 11101 11208 11315 11437 11547 11657 11217 11325 11432 11681 11793 11905 11455 11566 11676 11806 11920 12033 11579 11690 11801 11315 11097 11528 11305 11586 11363 11646 11421 11767 11540 12018 11786 12147 11913 BUNCHED STRAND All sizes 10786 10579 10989 10795 11045 10832 11102 10888 11217 11001 11456 11235 11579 11356 *The direct current resistance in ohms per 1000 feet of the completed strand shall not exceed the value calculated by dividing the appropriate factor above by the nominal circular mil area of the conductor. 3 2.1.2 Table 5: Copper Wire DC Resistance at 20°C (68°F) Solid Conductor Size (AWG/kcmil) ohms per 1000 ft ohms per km ohms per 1000 ft ohms per km ohms per 1000 ft ohms per km ohms per 1000 ft ohms per km 4/0 3/0 2/0 1/0 1 0.0504 0.0636 0.0802 0.1022 0.1289 0.166 0.209 0.263 0.335 0.423 0.0502 0.0633 0.0798 0.1016 0.1282 0.165 0.206 0.262 0.334 0.421 0.0490 0.0618 0.0779 0.0983 0.1239 0.161 0.203 0.256 0.322 0.407 0.0502 0.0633 0.0798 0.1006 0.1275 0.165 0.208 0.262 0.330 0.419 2 3 4 5 6 0.1625 0.2050 0.2584 0.3260 0.4110 0.533 0.672 0.848 1.070 1.350 0.1617 0.2039 0.2571 0.3243 0.4088 0.531 0.669 0.843 1.060 1.340 0.1563 0.1971 0.2485 0.3135 0.3952 0.513 0.647 0.815 1.030 1.300 0.1609 0.2028 0.2557 0.3226 0.4067 0.528 0.667 0.839 1.060 1.330 7 8 9 10 11 0.5180 0.6538 0.8241 1.0390 1.3100 1.700 2.140 2.700 3.410 4.300 0.5153 0.6498 0.8199 1.0330 1.3000 1.690 2.130 2.690 3.390 4.280 0.4981 0.6281 0.7925 0.9988 1.2600 1.630 2.060 2.600 3.280 4.140 0.5126 0.6465 0.8156 1.0390 1.3100 1.680 2.120 2.680 3.410 4.300 12 13 14 15 16 1.6500 2.0800 2.6300 3.3140 4.1800 5.420 6.840 8.940 10.900 13.700 1.6400 2.0700 2.6100 3.2900 4.1600 5.390 6.770 8.580 10.800 13.700 1.5900 2.0000 2.5200 3.1800 4.0200 5.210 6.590 8.270 10.400 13.100 1.6500 2.0800 2.6300 3.3100 4.1800 5.420 6.840 8.640 10.900 13.700 BARE HARD-DRAWN BARE MEDIUM-HARD BARE ANNEALED (SOFT) TINNED ANNEALED (SOFT) 2.2 AC Resistance For conductors larger than 1,500,000 circular mils, other calculation formulas must be used for accuracy. The non-uniform cross-sectional distribution of current also affects the inductance, the value of which is less than if the current density were uniform. The table of skin effect ratios, therefore, lists the inductance ratio L/L0 where L is the inductance due to a non-uniform current density and L0 is the inductance assuming uniform current density. A conductor offers a greater resistance to the flow of alternating current than it does to direct current. The magnitude of the increase is usually expressed as an “ac/dc ratio”. The reasons for the increase are several: 1) skin effect, 2) proximity effect, 3) hysteresis and eddy current losses in nearby ferromagnetic materials, and 4) induced losses in short-circuited nearby non-ferromagnetic materials. 2.2.1Skin Effect describes the phenomena of alternating current flowing more densely near the surface of the conductor. The net effect is a reduction in effective area and an increase in the resistance. To calculate skin effect in tubular conductors made of solid wire to an infinitely thin tube, the curves of Ewan are used. The parameter is: X = 0.027678 f R0 2.2.2Proximity Effect is the distortion of the crosssectional current distribution of the conductor due to nearby currents. To calculate approximately the proximity effect, use the following formula: 1-phase fp = 4 GMR GMD 3-phase fp = 6 GMR GMD 2 2 R -1 R0 R -1 R0 Where: f = frequency, Hz R0 = dc resistance at operating temperature, ohms per 1000 feet Where: fp = the factor to account for proximity effect When: f = 60 Hz, the formula becomes: 0.21439 x= R0 GMD = the geometric mean spacing of the conductors Table 6 gives the factors for skin effect ratio R/R0 as a function of x, where R is the ac resistance and R0 is the dc resistance. GMR = the geometric mean radius of the equal conductors R/R0 = the skin effect ratio The resistance of a conductor based on skin- and proximity-effect is expressed: R = R0 R + f p R0 4 2.3 Inter-Strand AC Resistance The effect of inter-strand resistance is also significant to ac resistance. If the current is, or can be, confined to the individual strands, skin effect will be materially reduced below that of an effectively solid conductor. The difference may be 2 percent or more. 2.3.1 Table 6: Resistance and Inductance Ratios due to Skin Effect (when f = 60 Hz) X R/R0 L/L0 X R/R0 L/L0 X R/R0 L/L0 X R/R0 L/L0 0.0 0.1 0.2 0.3 0.4 1.00000 1.00000 1.00001 1.00004 1.00013 1.00000 1.00000 1.00000 0.99998 0.99993 2.9 3.0 3.1 3.2 3.3 1.28644 1.31809 1.35102 1.38504 1.41999 0.86012 0.84517 0.82975 0.81397 0.79794 6.6 6.8 7.0 7.2 7.4 2.60313 2.67312 2.74319 2.81334 2.88355 0.42389 0.41171 0.40021 0.38933 0.37902 17.0 18.0 19.0 20.0 21.0 6.26817 6.62129 6.97446 7.32767 7.68091 0.16614 0.15694 0.14870 0.14128 0.13456 0.5 0.6 0.7 0.8 0.9 1.00032 1.00067 1.00124 1.00212 1.00340 0.99984 0.99966 0.99937 0.99894 0.99830 3.4 3.5 3.6 3.7 3.8 1.45570 1.49202 1.52879 1.56587 1.60314 0.78175 0.76550 0.74929 0.73320 0.71729 7.6 7.8 8.0 8.2 8.4 2.95380 3.02411 3.09445 3.16480 3.23518 0.36923 0.35992 0.35107 0.34263 0.33460 22.0 23.0 24.0 25.0 26.0 8.03418 8.38748 8.74079 9.09412 9.44748 0.12846 0.12288 0.11777 0.11307 0.10872 1.0 1.1 1.2 1.3 1.4 1.00519 1.00758 1.01071 1.01470 1.01969 0.99741 0.99621 0.99465 0.99266 0.99017 3.9 4.0 4.1 4.2 4.3 1.64051 1.67787 1.71516 1.75233 1.78933 0.70165 0.68632 0.67135 0.65677 0.64262 8.6 8.8 9.0 9.2 9.4 3.30557 3.37597 3.44638 3.51680 3.58723 0.32692 0.31958 0.31257 0.30585 0.29941 28.0 30.0 32.0 34.0 36.0 10.15422 10.86101 11.56785 12.27471 12.98160 0.10096 0.09424 0.08835 0.08316 0.07854 1.5 1.6 1.7 1.8 1.9 1.02582 1.03323 1.04205 1.05240 1.06440 0.98711 0.98342 0.97904 0.97390 0.96795 4.4 4.5 4.6 4.7 4.8 1.82614 1.86275 1.89914 1.93533 1.97131 0.62890 0.61563 0.60281 0.59044 0.57852 9.6 9.8 10.0 10.5 11.0 3.65766 3.72812 3.79857 3.97477 4.15100 0.29324 0.28731 0.28162 0.26832 0.25622 38.0 40.0 42.0 44.0 46.0 13.68852 14.39545 15.10240 15.80936 16.51634 0.07441 0.07069 0.06733 0.06427 0.06148 2.0 2.1 2.2 2.3 2.4 1.07816 1.09375 1.11126 1.13069 1.15207 0.96113 0.95343 0.94482 0.93527 0.92482 4.9 5.0 5.2 5.4 5.6 2.00710 2.04272 2.11353 2.18389 2.25393 0.56703 0.55597 0.53506 0.51566 0.49764 11.5 12.0 12.5 13.0 13.5 4.32727 4.50358 4.67993 4.85631 5.03272 0.24516 0.23501 0.22567 0.21703 0.20903 48.0 50.0 60.0 70.0 80.0 17.22333 17.93032 21.46541 25.00063 28.53593 0.05892 0.05656 0.04713 0.04040 0.03535 2.5 2.6 2.7 2.8 1.17538 1.20056 1.22753 1.25620 0.91347 0.90126 0.88825 0.87451 5.8 6.0 6.2 6.4 2.32380 2.39359 2.46338 2.53321 0.48086 0.46521 0.45056 0.43682 14.0 14.5 15.0 16.0 5.20915 5.38560 5.56208 5.91509 0.20160 0.19468 0.18822 0.17649 90.0 100.0 — — 32.07127 35.60666 — — 0.03142 0.02828 — — R/R0 = Resistance ratio due to skin effect L/L0 = Inductance ratio due to skin effect X= 0.21439 R0 Reproduced from National Bureau of Standards 5 AMPACITY 3 3.1 Method of Calculations To calculate ampacity, a two-part relationship is used: Ampacity (current-carrying capacity) calculation should take into account natural variables such as solar warming, wind and air density, viscosity, and thermal conductivity. Ampacity is a temperature rating; mining cables insulated with ethylene propylene are rated to operate continuously at 90°C. Commonly used ICEA ratings (Publication No. S-75-381/NEMA WC 58) are for cables isolated in still air of 40°C with a conductor temperature of 90°C. I2 Rac = QC – QS Where: QC = heat dissipated through conduction, convection and radiation QS = heat absorbed from solar radiation T = I2 Rac Rth Where: Rth = thermal resistance of the insulation Rac = effective electrical resistance I = current T = temperature difference of conductor and jacket surface When the two equations are solved simultaneously, it defines the ampacity for a set of given parameters. See 3.1.1 and 3.1.2 Tables 7 and 8. 3.1.1 Table 7: Ampacities for Portable Power Cables with 90°C Insulation, Amperes per Conductor Single Conductor Power Conductor 2001800115001Size 0-2000 8000 15000 25000 (AWG or Volts Volts* Volts* Volts* kcmil) Nonshielded Shielded Shielded Shielded 8 83 — — — 6 109 112 — — 4 145 148 — — 3 167 171 — — 2 192 195 195 — 1 223 225 225 222 Two Conductor Round and Flat 0-2000 Volts 72 95 127 145 167 191 Three Conductor Round and Flat Three Conductor Round 8001150010-8000 15000 25000 0-5000 Volts Volts* Volts* Volts* Nonshielded Shielded Shielded Shielded 59 — — — 79 93 — — 104 122 — — 120 140 — — 138 159 164 178 161 184 187 191 Four Five Six Conductor Conductor Conductor 0-2000 Volts 54 72 93 106 122 143 0-2000 Volts 50 68 88 100 116 136 0-2000 Volts 48 64 83 95 110 129 1/0 2/0 3/0 4/0 258 298 345 400 260 299 345 400 259 298 343 397 255 293 337 389 217 250 286 328 186 215 249 287 211 243 279 321 215 246 283 325 218 249 286 327 165 192 221 255 — — — — — — — — 250 300 350 400 450 500 550 600 650 700 750 800 900 1000 445 500 552 600 650 695 737 780 820 855 898 925 1010 1076 444 496 549 596 640 688 732 779 817 845 889 925 998 1061 440 491 543 590 633 678 — — — — — — — — 430 480 529 572 615 659 — — — — — — — — 363 400 436 470 497 524 — — — — — — — — 320 357 394 430 460 487 — — — — — — — — 355 398 435 470 503 536 — — — — — — — — 359 — — — — — — — — — — — — — 360 — — — — — — — — — — — — — 280 310 335 356 377 395 — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — *These ampacities are based on single isolated cable in air operated with open-circuited shield. NOTE — these ampacities are based on a conductor temperature of 90°C and an ambient air temperature of 40°C. Permission has been granted by ICEA to reproduce this material. 6 3.1.2 Table 8: Ampacities for Mine Power Feeder Cables with 90°C Insulation, Three Conductor 5000 to 25,000 Volts Copper Ampacities* Conductor Size (AWG or kcmil) 5000 & 8000 Volts 15000 Volts 25000 Volts 6 4 2 1 93 122 159 184 — 125 164 187 — — — 189 1/0 2/0 3/0 4/0 211 243 279 321 215 246 283 325 216 247 284 325 250 300 350 400 500 355 398 435 470 536 359 401 438 473 536 359 401 438 473 536 *These ampacities are based on single isolated cable in air operated with open-circuited shield. NOTE — these ampacities are based on a conductor temperature of 90°C and an ambient air temperature of 40°C. Permission has been granted by ICEA to reproduce this material. 3.1.3 Table 9: Approximate Ampacity Correction Factors for Cables of all Voltages Correction factors are listed below for various ambient temperatures. Ambient Temperature Correction Factors for Insulations Rated At: °C 90°C 75°C 10 20 30 40 50 1.26 1.18 1.10 1.00 0.90 1.36 1.25 1.13 1.00 0.85 When cables are used with one or more layers wound on a reel, the ampacities should be derated as follows: No. of Layers Multiply Ampacities By: 1 2 3 4 0.85 0.65 0.45 0.35 Permission has been granted by ICEA to reproduce this material. 7 3.1.4 Table 10: Allowable Short Circuit Currents for Insulated Copper Conductors Allowable Short Circuit Currents for Insulated Copper Conductors Rated for 90°C Continuous Operation 1000000 100000 Short Circuit Current—Amperes 10000 Curves Based on the Formula 1000 2 [ ] t = 0.0297 log [ TT ++ 234 234 ] I A 2 10 1 I =Short Circuit Current–Amperes A =Conductor Area–Circular Mils t =Time of Short Circuit–Seconds T1=Maximum Operating Temperature–90°C T2=Maximum Short Circuit Temperature–250°C 100 10 8 6 4 2 1 1/0 2/0 3/0 4/0250 350 500 750 1000 Conductor Size (AWG/kcmil) 1 Cycles 16 Cycles 2 Cycles 30 Cycles 4 Cycles 60 Cycles 8 Cycles 100 Cycles Reprinted with permission from ICEA P-32-382 Short Circuit characteristics of Insulated Conductors, Copyright 2006, Insulated Cable Engineers Association, Carrollton, GA 30112. This reprint is not the referenced subject, which is represented only by the standard in its entirety. 8 3.2 Warning: Hot Conductors 9 A primary goal in the development of rubber or plastic compounds for cable insulations and jackets is to obtain physical and electrical characteristics that are stable at elevated temperatures in either wet or dry environments. From an engineering and design viewpoint, high temperature resistance is highly desirable and increases the safety factor during periods of emergency. Insulation stability during an emergency overload is of extreme importance. As noted in ICEA Standards covering emergency overload ratings, “Operation at these emergency overload temperatures shall not exceed 100 hrs. per year. Such 100-hr. overload periods shall not exceed five over the life of the cable.” Operating temperatures must be kept in the correct, and safe, perspective. As the current load increases, the following phenomena occur: • Conductor resistance increases • Voltage drop increases and causes conductor inefficiency • Increased conductor temperature becomes an electric furnace • Degradation of insulations and coverings is accelerated IMPEDANCE 4.1 Impedance Terms and Calculations 4 4.2 Reactance Terms and Calculations Impedance (Z) of a circuit to a specified periodic current, and potential difference, is the ratio of effective value of the potential difference between terminals to the effective value of the current, there being no source of power in the portion of circuit under consideration, is expressed: Z = E (ohms) or I Z= 2 R +X 2 Reactance of a portion of a circuit for a sinusoidal current, and potential difference of the same frequency, is the product of the sine of the angular phase difference between the current and potential difference times the ratio of the effective potential difference to the effective current, when there is no source of power in the portion of the circuit under consideration. Inductive Reactance (XL) is calculated from the relationship: (ohms) Admittance (Y) is the reciprocal of impedance. Ohm’s Law applies to all metallic circuits and to others containing electrolytic resistance. It states that current in a circuit is directly proportional to the electromotive force in the circuit. In a direct-current circuit: Where: L = inductance (henries) I = E = Electromotive Force (volts) (amperes) R Resistance (ohms) f = frequency (Hertz) Also from the above formula: XL = 0.05292 log10 GMR (ohms to neutral per GMD 1000 feet at 60 Hz) In an alternating current circuit: XL = 2f L (ohms) For other frequencies, multiply X L by: Reff = Rdc x Rac /Rdc f 60 Capacitive Reactance (XC) is calculated from: Where: Rac /Rdc = ratio of alternating-current resistance to direct-current resistance of the circuit conductor XC = – 1 (ohms) 2fC Where: C = capacitance (farads) For resistance and reactance of portable power and feeder cables, see 4.1.1 and 4.1.2 Tables 11 and 12. Total Reactance (X) of a circuit is the sum of the inductive and capacitive reactance: X = 2fL + - 1 = XL + XC 2fC • If there is no capacitance in the circuit, the total reactance is equal to the inductive reactance. • If there is no inductance in the circuit, the total reactance is equal to the capacitance reactance. 10 4.2.1 Table 11: Resistance and Reactance of Portable Power Cables Conductor Size (AWG or kcmil) 8 7 6 5 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 800 900 1000 R[ac]1 Ohms/1000 Ft. XL [60HZ] 2 Ohms/1000 Ft. 75°C 90°C .838 .665 .528 .418 .332 .263 .209 .165 .128 .102 .081 .065 .055 .046 .039 .035 .028 .023 .020 .018 .016 .014 .878 .696 .552 .438 .347 .275 .218 .173 .134 .107 .085 .068 .057 .048 .041 .036 .029 .024 .021 .019 .017 .015 2 kV3 G-GC, G + GC .034 .033 .032 .031 .031 .031 .029 .0303 .029 .029 .028 .027 .0283 .027 .027 .027 .026 .026 .026 .025 .025 .025 2 kV3 SHD-GC 5 kV SHD-GC 8 kV SHD-GC 15 kV SHD-GC 25 kV SHD-GC — — .038 .036 .035 .034 .033 .033 .032 .031 .030 .029 .0303 .029 .029 .028 .028 .027 .027 .026 .026 .026 — — .043 .042 .040 .039 .038 .036 .035 .034 .033 .032 .031 .031 .030 .030 .029 .028 .028 .028 .027 .027 — — — — .043 .042 .040 .039 .037 .036 .035 .034 .033 .032 .032 .031 .030 .030 .029 .029 .028 .028 — — — — — — .044 .042 .040 .039 .038 .036 .036 .035 .034 .033 .032 .032 .031 .030 .030 .030 — — — — — — — .046 .044 .043 .041 .040 .039 .038 .037 .036 .035 .034 .033 .033 .032 .032 1 a.Sizes 8 AWG - 1 AWG based on tinned copper 94.16% conductivity. b.Sizes 1/0 AWG and larger based on tinned copper 96.16% conductivity. c.Resistance increased per ASTM B-172, Note 7, to compensate for stranding factor. d.Skin effect calculated according to Arnold’s Table, National Bureau of Standards. e.Nominal cross-sectional areas. 2 a.Based on conductor dimensions given for Class H Rope Lay conductors in ICEA S-75-381/NEMA WC 58. b.Extruded strand thickness .015". c.Insulation thickness according to nominals given in ICEA S-75-381/NEMA WC 58. 3 a.Deviations from normal progression due to changes in insulation thickness for same voltage rating. 4.2.2 Table 12: Resistance and Reactance of Mine Power Feeder Cables Conductor Size (AWG or kcmil) 6 5 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 800 900 1000 R[ac]1 Ohms/1000 Ft. 90°C .510 .404 .321 .254 .201 .160 .127 .101 .080 .063 .054 .045 .039 .034 .027 .023 .020 .017 .016 .014 XL [60HZ] 2 Ohms/1000 Ft. 5 kV MP-GC .041 .040 .038 .037 .036 .035 .034 .033 .032 .031 .030 .029 .029 .029 .028 .028 .027 .027 .027 .026 8 kV MP-GC .044 .042 .041 .039 .038 .037 .035 .034 .033 .032 .031 .031 .030 .030 .029 .029 .028 .028 .027 .027 15 kV MP-GC — — — — .042 .041 .039 .038 .036 .035 .034 .034 .033 .032 .031 .031 .030 .030 .029 .029 1 a.Based on bare copper 100% conductivity. b.Nominal cross-sectional areas. c.Resistance increased by increments per ASTM B-8 to compensate for stranding factor. d.Skin effect calculated according to Arnold’s Table, National Bureau of Standards. 2 a.Based on conductor dimensions given for Class B Concentric Stranded conductors in ICEA S-75-381/NEMA WC 58. b.Extruded strand shield thickness .015". c.Insulation thickness according to nominals given in ICEA S-75-381/NEMA WC 58. 11 25 kV MP-GC — — — — — .044 .043 .042 .040 .039 .038 .037 .036 .035 .034 .033 .032 .031 .031 — 4.3 Voltage Drop Load current, power factor and impedance of the conductor all affect voltage drop. Generally, capacitance can be neglected in distribution circuits because its effect on voltage drop is negligible for the circuit lengths and operating voltages used. A major point in circuit design is to determine the proper size of conductor that will carry the current load without exceeding a specified voltage drop. In a balanced 3-phase circuit, the drop in phase voltage is 1.73 times the drop in each conductor when they are treated as a single-phase circuit with no return wire. V drop = 1.73 IZ cos ( – ) Where: I = amperes in each conductor Z= ohmic impedance of one conductor = impedance angle = power factor angle See 4.2.1 Table 13. 4.3.1 Table 13: Approximate Voltage Drop Factors at 90°C and 75°C Conductor Temperatures Three Conductor Cables at 90°C Conductor Temperature 60 Hertz Phase-To-Phase Voltage Drop Per Ampere Per 1000 ft at Power Factors of: Conductor Size 80% 90% (AWG/kcmil) 6 0.82 0.90 4 0.54 0.58 2 0.35 0.38 1 0.29 0.31 1/0 0.24 0.25 2/0 0.20 0.20 3/0 0.16 0.17 4/0 0.14 0.14 250 0.12 0.12 300 0.11 0.11 350 0.10 0.09 400 0.09 0.08 500 0.08 0.07 Three Conductor Cables at 75°C Conductor Temperature 60 Hertz Phase-To-Phase Voltage Drop Per Ampere Per 1000 ft at Power Factors of: Conductor Size 80% 90% (AWG/kcmil) 6 0.76 0.83 4 0.50 0.54 2 0.33 0.35 1 0.27 0.28 1/0 0.22 0.23 2/0 0.18 0.19 3/0 0.15 0.15 4/0 0.13 0.13 250 0.11 0.11 300 0.10 0.09 350 0.09 0.08 400 0.08 0.08 500 0.07 0.06 4.4 Voltage Regulation Where: VR = voltage regulation in percent Es = sending-end voltage to neutral in volts Er = receiving-end voltage to neutral in volts The permissible variation in voltage depends to a considerable extent on the kind of service being supplied. It must be kept within practical limits in order 0.95 0.60 0.38 0.30 0.24 0.19 0.15 0.12 0.10 0.08 0.07 0.06 0.05 100% 0.85 0.55 0.35 0.28 0.22 0.17 0.14 0.11 0.09 0.08 0.07 0.06 0.05 to obtain proper candle power and life from lamps and proper efficiency, torque, power factor, etc., from motor loads. Voltage regulation may usually be kept within desirable limits normally not over 5 percent by insuring low resistance and reactance of the lines and feeders. If this is impractical, special apparatus must be installed to regulate voltage. Voltage regulations are expressed as follows: E -E VR = s r x 100, percent Er The relationship between Es and Er is expressed by: Es = Er + IrZ (vectorially) Es = as above Er = as above Ir = receiving-end current per conductor, amperes Z = total series impedance per conductor, ohms 100% The National Electrical Code (NEC) recommends maximum voltage drops of 3% for power loads and 1% for lighting loads. 4.5 Improving Voltage Regulation • • • • Use a larger conductor size Reduce conductor spacing Paralleling circuits Improve power factor 12 SHIELDING 5 5.1 Cable as a Capacitor A capacitor is an electrical device consisting of two conducting surfaces separated by insulating material (dielectric) such as air, paper, oil or rubber. A shielded cable operates as a capacitor with the insulation as the dielectric and the shield as the other conducting surface. This must be taken into consideration during cable design and application. 5.1.1 Figure 1: Cable as a Capacitor Jacket Shield Air Insulation Cable The following characteristics of a capacitor are related to shielded cable: • A capacitor stores electrical energy. The SIC (specific inductive capacity) of insulation is determined by comparing the amount of energy an insulated cable (capacitor) can store to the amount of energy stored by a capacitor using air (in a vacuum) as the insulator. For example, if a certain air capacitor has a measured capacitance of one F (microfarad), but the measured capacitance is 3 F when the air is replaced with insulation, then the insulating material has a SIC of about 3. SIC is also referred to as dielectric constant and permittivity. For a capacitor designed to store energy, a high SIC is desirable. For a cable that transports electricity, a low SIC is needed. For 600 Volt cables, the SIC is generally kept below 7. For 15kV cable, the SIC should be below 4. Cable above 15kV should have the SIC value kept as low as possible. 13 Copper Plate Copper Plate Capacitator • A capacitor permits the flow of alternating current. The amount of ac flow is dependent on the SIC of the insulation and the frequency of the current. In cable design, ac flow should be kept in mind when determining whether or not to shield, the type of grounding method, the cable size, the conductor spacing and the geometry of cable. 5.2 Shielding and Stress Relief in Insulated Cable Shielding systems work to confine the dielectric field to the insulation. Without proper shielding, the electrical stress can cause deterioration of the insulation and danger of electrical shock. There are three principal functions of a shielding system: 5.3.1To Eliminate Non-Symmetrical Electrical Stresses CONDUCTOR SHIELDING Conductor stress relief (conductor shielding) functions to eliminate stress between the conductor and the insulation. To be effective, the conducting layer must adhere to, or remain in intimate contact with, the insulation. 5.2.1 Figure 2A shows an air gap between the conductor and the insulation. The voltage stress across the air gap can cause ionization of the air and result in deterioration of the insulation. 5.2.1 Figure 2B shows extruded shielding around the conductor. This layer presents a smooth round electrode (precluding excessive gradients due to physical irregularities) that has the same electrical potential as the conductor and is bonded to the insulation so there is no ionization within the cable. 5.3 Functions of Insulation Shielding Systems 5.2.1 Figure 2: Conductor Shielding Power cables are subjected to radial tangential or longitudinal voltage stresses. Radial stresses are always present in cable insulation when the cable is energized. Insulation is most efficient when the electrical field is uniformly distributed around the conductor and within the envelope of the cable insulation. Non-uniform distribution of the dielectric field results in increased radial stress in portions of the insulation and less efficient usage of the insulation as a whole. Shielding systems applied over the insulation of the individual conductors remove the fillers from the dielectric field, leaving a symmetrically distributed radial stress. This utilizes the insulation to its greatest efficiency and in the direction of its greatest strength. AIR VOID A CONDUCTOR SHIELD B One of the basic laws of electric fields states that voltage applied across dielectrics in series will divide in inverse proportion to the dielectric constant on the material. Thus, when an air gap is in series with the cable insulation, a portion of the voltage will appear across the gap. The surface of the insulation or cable will then have a voltage to ground equal to the voltage across the gap. This voltage can approach the full conductor potential when the air gap is large and will approach ground potential when the surface is in contact with a grounded surface. This phenomenon gives rise to tangential and longitudinal stresses. Tangential stresses are always associated with nonuniform radial stress. They occur in multi-conductor cables when the individual conductors are not shielded and in all single conductor non-shielded cables installed so that non-symmetrical relations exist between conductor and adjacent grounded surfaces. Longitudinal stresses are not necessarily associated with non-uniform radial stress but are always apparent with radial stresses of different magnitude along the length of the cable. These stresses occur in non-shielded cable installed so that intermittent contacts or variable spacings exist between the cable surface and grounded objects. Examples include metal conduits, steel supports or cable brackets, local conducting areas and wet spots in ducts. The proper application of an external shielding system will eliminate tangential and longitudinal stresses by bringing the entire surface to ground potential. 14 5.3.2To Provide a Definite Capacitance to Ground for the Insulated Conductor cable, a considerable potential difference may exist between the covering and the ground. This may create a hazard for the following reasons: Cables which are laid in ducts or directly in the earth will often run through sections of dry and wet soil or ducts having varying electrical characteristics. This results in varying electrostatic capacity to ground, hence a change in the surge impedance of the cable. In addition, cables entering metallic ducts or risers will have a change in impedance due to varying capacitance to ground. In cables connected to overhead lines, traveling waves caused by lightning or induction from charged clouds or fog drifts will be partially reflected at points of change in the surge impedance. This will result in further build-up of the surge voltage in the cable, which may cause breakdown of the insulation. In some cases where cables run through very dry ground, traveling waves may be induced by direct induction from the clouds. a. Contact with the covering may induce panic or fear, resulting in hazards to life such as falls, or other secondary factors, even though the electrical shock may not be lethal. b. Contact with the covering under unusual conditions may be a hazard to life by electrical shock if the charging current from a considerable length of cable is carried by the covering to the point of contact. This might occur, for instance, with a heavily contaminated damp cable surface. c. The potential difference may cause sparking, which could result in the ignition of explosive gas mixtures in tunnels or duct systems. A properly grounded shielding system will confine the dielectric field to the insulation and eliminate these hazards. To obtain full benefit, the shield should be applied over the insulation of individual conductors. An additional safety factor is derived from shielding by providing a path to ground; this reduces the hazard to workmen who may accidently drive a pick or other tool into the energized conductor of the cable. See 5.11.1 Table 14 for different types of shielding systems. The application of a shielding system over the insulation of individual conductors or the assembly of a multi-conductor cable reduces these surge potentials. A shield over the insulation of individual conductors functions by: a. creating a uniform capacitance from conductor to ground, resulting in a uniform surge impedance along the cable, thus preventing partial reflections and the consequent build-up of the surge voltages within the cable. b. providing maximum capacitance from conductor to ground, thereby effecting the maximum reduction of the incoming surge potential. 5.4 Insulation Stress Relief (Insulation Shielding) Shielding systems consist of a semi-conducting layer or an extruded layer of electrically conducting material over the insulation in conjunction with a metallic, non-magnetic tape, wire, or braid. The stress-relief portion (inner layer) of the system must adhere to the insulation under all conditions. It and the metallic portion serve as a current-carrying medium for charging and leakage currents. The shielding system should operate at or near ground potential at all times. Shielding which does not have adequate ground connection is more hazardous from a safety standpoint than non-shielded cable. An undergrounded or “floating” shield can cause electrical failure of the cable, and if the potential on such a shield penetrates the outer jacket, the resultant discharge can result in an extreme shock hazard. To minimize the possibility of open sections in the shielding system, use a trailing cable design that has the grounding conductor laid in intimate contact with the insulation shielding throughout the length of the cable. c. absorbing surge energy in the same manner as the conductor by reason of the current induced magnetically in the shield. d. reducing stress on the insulation under many circuit arrangements, because surge potential will momentarily exist on both conductors and shield. A shielding system applied over the multi-conductor cable assembly is somewhat less effective with respect to points (a) and (c). Although it does not provide the maximum capacitance (b), it is an improvement upon non-shielded, non-metallic-covered cables and is probably equal to individual shield for (d). 5.3.3To Reduce the Hazard of Both Shock and Danger to Life and Property 15 As explained in 5.3.2, when the outer surface of the insulation or covering of insulated cables is not in contact with ground throughout the entire length of the A stress-relief cone is important in relieving the area of concentrated stress at the end of a grounded shield. This stress occurs because of the potential difference between the surface of the insulation without shielding and the surface, which is still shielded. A stress-relief cone relieves the stress, but it does not eliminate it. Even a well-designed stress cone has areas of stress concentration, but the conditions will be tolerable. The shielding system must be removed completely and proper stress-relief cones made at all shield terminations. If all elements of the shield are not removed, excessive leakage current, tracking and flashover may result. When determining the removal distance of grounded external shielding, remember that the voltage gradient between the end of the conductor and the shield terminus is extremely non-linear. The longitudinal and radial stress concentration at the edge of the shield diminishes only slightly as the axial length of shielding system removal is increased. 5.5.1 Figure 3 clearly illustrates that the voltage gradient at the shield edge is the same (for graphing purposes) for three terminations with different removal distances. 5.6 Concentrated Stresses The voltage gradient between the end of the conductor and the edge of the shielding system is non-linear and, for all practical purposes, independent of removal distance. One of the primary purposes of shielding in cables is to achieve uniform radial stress distribution so that all flux lines extend from the conductor to the grounded metallic shield. 5.6.1 Figure 4 shows the stress distribution at the edge of the shielding. For the portion of the conductor beyond the edge of the shield, the shielding tape is still the nearest component at ground potential, and all electrical flux lines concentrate at this shield edge. Under such conditions, this is the weakest point in the cable circuit and electrical failure can result either radially or longitudinally at this location unless measures are taken to reduce these electrical stresses. 5.5.1 Figure 3: Voltage Gradient vs. Distance along Dielectric from Shield 100 VOLTAGE IN PERCENT 5.5 Stress-Relief Cones 0 DISTANCE ALONG DIELECTRIC FROM SHIELD 5.6.1 Figure 4: Stress Distribution at Edge of the Shielding System INSULATION CONDUCTOR FLUX LINES SHIELDING SYSTEM 16 5.7 Stress-Relief Mechanism 5.7.1 Figure 5: Conductor Stresses 5.7.1 Figure 5 illustrates a conventional stressrelief cone made of hand-applied insulating tapes and shielding braid. This simple mechanism relieves the high concentration of stress at the cable shield terminus by providing a gradual transition. The cone does not completely eliminate the stress but reduces it below the limits of trouble-free cable operation. FLUX LINES CABLE SHIELDING SYSTEM CONDUCTOR INSULATION HAND-APPLIED INSULATING TAPES HAND-APPLIED SHIELDING BRAID 5.8 Extruded Stress-Relief Layer Following are some factors that characterize both types: The use of conducting extruded layer as part of the shielding system has gained acceptance through three contributing factors: Thermoplastic Conducting Compounds • Deforms at elevated temperatures • Sharp increase in resistance at higher temperatures 1. Cable Acceptance • Not inherently flame resistant Extruded conducting compounds used over the insulation have proved to have distinct advantages over tape bedding. Conducting compounds are not susceptible to the deterioration of fabric tapes and are not limited to the decreased physical protection of tape. Conducting compounds have also had an excellent performance record over a wide range of cable environments and locations. • Does not subject insulation to vulcanization or cross-linking • Adhesion control is possible for easy stripping • Good performance record in a variety of applications Thermosetting Conducting Compounds • Excellent deformation characteristics • Consistent in resistant characteristics over temperature range 2. Rigorous Requirements for Corona Levels Corona level testing determines voids in conductor/ insulation interface and insulation surface/shielding system interface. Because fabric tapes have a wide range of limitations in conductivity, splices, fiber ends, uneven tensions and tape laps, there is a difficulty in obtaining a consistent, smooth interface which reduces voids. Conducting compounds suffer from none of these variables and have proven to be far less likely to develop voids. 3. Intimate Contact With Insulation Surface Conducting insulation shield or extruded stress-relief layers provide smooth round electrodes and intimate contact with the insulation. It is able to match the expansion characteristics of the insulation, which prevents the formation of voids. Extruded conducting compounds are available in thermoplastic and thermosetting types. The choice is dependent on cable type, thermal rating, emergency and short-circuit ratings. 17 • Not inherently flame resistant • Requires heat for cross-linking, can cause conductor drift and very tight bond with insulation 5.9 Applications of Shields Association of Edison Illuminating Companies (AEIC) and Insulated Cable Engineers Association (ICEA) offer shielding guidelines and recommendations. It may be difficult to determine when a shield is absolutely required, but a properly installed shielded cable will always offer the maximum in safety and reliability. The shielding system must always operate at or near ground potential. 5.10 Effects of Shield Loss on Ampacity The purpose of a cable insulation shield is to confine electrostatic stresses to a definite pattern and provide a fixed path of grounding for cable charging and leakage currents. When a cable carries current, there is an electrostatic and a magnetic field. The cable shield confines the electrostatic field but not the magnetic field. The magnetic field affects the current density in adjacent conductors and induces voltage in nearby metallic objects. If metallic circuits in the cable, or metal nearby, form a closed electrical path, there will be I 2R losses. The losses that occur in these “external” circuits are felt in the electrical characteristics of the cable, particularly if the object is made of magnetic material which will increase power loss by hysteresis effects. Three single conductor cables laid in an equilateral triangular configuration will experience losses based on this formula: S Xm = 52.92 Log r Where: Xm = micro-ohms per foot of cable S = spacing between centers of cables in inches r = radius of cable shield in inches The Dielectric Constant of a material is defined as the ratio of the amount of energy that a given capacitor with insulating material between its plates can store to the amount of energy that the same capacitor can store when it has air between its plates. In the cable industry, the Dielectric Constant of a material is referred to as Specific Inductive Capacity (SIC). If one plate of a capacitor is bent into a circle and the other plate is stretched and then wrapped concentrically around the first, it is a capacitor and the cross-section of a shielded cable. Obviously, whenever a shielded cable is made, a capacitor is also made. In the case of a shielded, single conductor cable, the size of this capacitor is: If cable shields are grounded at both ends, the electrical circuit is complete, and a current flows as a result of VS. The power loss due to this current is: Xm2 Ws = I2Rs Rs2/ Xm2 Where: Inductive losses make the use of large single conductor leaded or armored cables impractical. The low resistance of these coverings causes excessive losses that reflect back to the conductor as an increase in impedance. This results in an excessive voltage drop in the cable circuit. 7.354Le C= Where: C = picofarads L = length of cable in feet e = SIC of insulation D = outside diameter of insulation d = inside diameter of insulation Log (D/d) Whenever an ac voltage is applied across a capacitor, a current will flow. In a power cable, this is referred to as the charging current. The magnitude of this current per thousand feet of cable is: I= 2,772.46(kV)e 1,000,000Log (D/d) Where: I = amperes kV = kilovolts between conductor and shield e = SIC of insulation D = outside diameter of insulation d = inside diameter of insulation Ws = micro-watts per foot per cable Rs = shield resistance in micro-ohms per foot I = current in conductor, amperes Xm = micro-ohms per foot of cable On a three-phase system, the total shield loss is approximately three times the above value. Vs = IXm Where: Vs = micro-volts per foot, to neutral I = current in conductor, amperes Xm = micro-ohms per foot of cable One advantage of a three conductor cable is the 120-degree phase difference between the conductor currents, which results in a partial cancellation of the magnetic field around the three conductor cable. This reduces the losses in the shield to a tolerable level. The impedance of a three conductor cable is less than the impedance of three single conductor cables of a corresponding size. 5.11 Dielectric Constant If the cable shields are open circuited (i.e., they are grounded at only one place and they are not in contact with each other at any one point), the voltage induced in one of them is: There are two sources of current in the shield of a cable: 1) the current that is due to the inductive coupling with the conductor and is a function of the conductor current, and 2) the current which results from the capacitive coupling between the conductor and the shield, which is dependent upon the voltage that exists between the conductor and the shield. The current flowing in the shield and the shield resistance losses show up as heat, similar to losses and heat due to current in the phase conductor. 18 The ampacity of a cable is dependent on the amount of heat generated in a cable and the dissipation rate of the heat to the cable surroundings. Once the surroundings have been chosen, the amount of heat dissipation is fixed, as is the amount that the cable can be allowed to generate. Any heat that the shield generates must be subtracted from the amount that would otherwise be allotted to the phase conductor. This reduces ampacity. The greater the shield losses, the higher the economic loss. In essence, excessive shield loss translates into paying a premium to obtain less cable capacity. 5.11.1 Table 14: Shielding Systems Solid Dielectric Cables Shielding System 19 Advantages Disadvantages Non-Magnetic Copper Tape Shield (1) Effective electrostatic shield (2)Consistent and controlled electrical properties (3)Universally accepted – reliable standard for comparison (1) Difficult to apply tapes without wrinkling (2)Requires semi-con bedding layer to insure intimate contact and high corona resistance (3)Vulnerable to damage during installation (4)Relatively high cost (5)Cutting of tapes during splicing and termination requires considerable skill and careful handling Semi-Conducting Extruded Layer With Concentric Metallic Drain (1) Effective electrostatic shield (2)Combination of semi-con layer with drain wires insures both intimate contact with insulation and controllable electrical properties (3)Easy to add capacity with extra or larger wires (1) Requires caution during installation to prevent displacement of wires (2)Should not be used in contact with oil (3)External wires vulnerable to corrosion (4)Design balance to control shield losses critical for top efficiency in three-phase operation Flexible Nylon/Copper Braid Over Semi-Conducting Tape (1) Effective electrostatic shield (2)Provides additional grounding conductor capacity in type SHD cables (3)Good shock hazard protection (1) Extensive flexing lowers corona extinction levels (2)Shield losses relatively high Flexible Full Copper Braid Over Semi-Conducting Tape (1) Effective electrostatic shield (2) Provides additional grounding conductor capacity in type SHD cables (3) Good shock hazard protection (1) Extensive flexing lowers corona extinction levels (2) Shield losses higher than nylon/copper (3) Broken shield wires buttonhook, producing possible insulation penetration INSULATION AND JACKET STABILITY 6.1 Partial Discharge Resistance Partial discharge is the name given to the corona phenomenon by power cable engineers. Corona, or partial discharge, is a very complicated phenomenon and not easily defined. Below are a few accepted facts that outline the characteristics of partial discharge: • Ozone resistance is not synonymous with partial discharge resistance; they are separate phenomena. • Extinction level is the voltage point where partial discharge disappears. • Voids within the insulation, between insulation and the conductor shield, or between insulation and the insulation shield can cause partial discharges. • Extruded strand shields with smooth surfaces and a bond to the insulation will virtually eliminate partial discharge at the interface. • Keeping insulation voids to a minimum will drastically reduce partial discharge. • Choose insulation with a high degree of resistance to partial discharge. • Design the cable to incorporate features that facilitate the partial discharge extinction level. • Use processing techniques that minimize voids. An insulated cable has one purpose – to transmit power. To achieve this at the highest possible levels, the characteristics of the insulated cable must remain stable and predictable. The environments that affect performance levels can be divided into four areas: • Physical environment affects cable installation and its actual operation. Severe bending, compression, cutting abrasion, and excessive tension can all contribute to damage which reduces the reliability of a cable installation. • Chemical environment affects the cable components. Chemical environments such as free chlorine, oil, ozone, etc., can influence the choice of materials for insulations and jackets. • Thermal environment can affect the degradation of insulation and jackets at elevated levels since the speed of a chemical reaction is doubled with a 10°C rise in temperature. • Electrical environment that causes magnetic and static fields can result in data logging control cable interference. The environments should be taken into consideration whenever specifying material and cable design. Thought-out choices allow a balance between economy and sound engineering. Similar to an oxygen molecule (O2) in chemical structure but containing one more atom of oxygen (O3), ozone is a gas with a pungent characteristic odor. Ozone can be produced anywhere a combination of air and an electrical discharge is present and is usually encountered in diluted form mixed with air. Cable problems related to ozone are most likely to occur at voltages above 5kV; however, 2kV cables can also be attacked if they are in an environment where ozone is being generated. Ozone and cable coverings share an interesting history. The chemical nature of ozone is such that it is capable of deteriorating virtually every extruded type of cable covering used in the industry. For many years, the most practical method of obtaining some degree of ozone resistance in cable insulation was to incorporate a substantial quantity of polymerized oil or factice into the compound. The disadvantage of obtaining ozone resistance in this fashion is a significant sacrifice of heat aging resistance, low-temperature flexibility and physical strength. Ozone attack of cable covering is more easily understood if the basic polymer is considered as a discrete and identifiable chemical. The major component in polymers is a chain of carbon atoms. How these carbon atoms are linked is the determining factor in predicting ozone resistance. 6.2 The Major Prerequisite of Insulated Cables 6.3 Ozone Resistance • Intimate contact between the outer surface of the insulation and the shielding system will reduce partial discharges. A few factors can minimize partial discharge. Consider these when specifying insulated cable: 6 20 In some polymers like polyethylene and the ethylenepropylene types, the carbon-to-carbon link or bond in the main chain looks something like the following: This arrangement provides excellent ozone resistance. Many polymers like SBR, Neoprene and natural rubber have a carbon-to-carbon linkage or bond that looks like this: (-C-C = C-C-) Notice there is a double bond between two of the carbons. This is the location where ozone attacks and reacts, splitting the carbon chain and resulting in radial cracks in the cable covering. The more of these double bonds present, the more quickly the deterioration in the presence of ozone, limiting polymers of this type to 600 Volt service. EPR and XLPE are the leaders in medium-voltage insulations with inherent or built-in ozone resistance. EPR and XLPE contain a limited number of double bonds, virtually all of which are used up in the vulcanizing process. The resulting compound has a high degree of ozone resistance without sacrificing important properties. The hardness of the cable jacket can be indicative of the health of the insulation and jacket. Hardness is usually measured with a Shore Durometer; for example, a mining-grade synthetic rubber jacket in good condition would show a Shore A hardness of 65-75. If the jacket goes to 90, it’s a good indication that it has been exposed to elevated temperatures and is becoming brittle. Elevated temperatures or a loss of plasticizer increase hardness, while a decrease in hardness signals cable deterioration. An excessive hardness increase or decrease is a sign that a problem is occurring. (-C-C-C-C-) 6.5 Jacket — Hardness General Cable’s Technology Center monitors polymer innovations and the development of built-in ozone resistance. Some of the better ozone-resistant jackets on the market include CSPE and CPE. 6.6 Thermal Stability and Heat Resistance Heat resistance is a major component of thermal stability, cable longevity and reliability. By reviewing the properties of insulation that affect heat resistance, it is easier to make cable specifications that will offer true thermal stability and facilitate service life predictions. • Heat aging is tested by exposing insulation to air oven, oxygen bomb and air pressure heat test (APHT). Noting whether a material gets brittle or softens during these tests gives good insight to polymer choice and compounding ingredient control. • Deformation of the insulation under stress or high loads should not occur to an excessive degree. In general, thermoplastic insulations deform more readily than thermosetting compounds at high temperatures. At temperatures over 100°C, even thermosetting compounds will show differing degrees of deformation. The polymer insulation that shows the least deformation should be considered the most stable. • Creep is the dimensional change of a material under load over a given time. In vertical riser cable and terminations, creep could be a very serious problem. Insulation with zero creep is considered to be extremely stable. • Thermal expansion is the fractional change in length or volume of a material related to a unit change in temperature. Cables used for alternating heavy and light current loads will be subject to expansion and contraction. If the expansion is excessive, the integrity of the overall design can be disrupted, and cable failure is accelerated. Thermal expansion stability is measured by cyclic aging tests. • Physical properties of insulation, such as tensile strength and cut resistance, can be reduced dramatically by repeated exposure to elevated temperatures. The insulating compound that retains the greatest degree of its properties after high temperature aging should be considered the most stable. 6.4 Jacket — Physical Toughness For most industrial power cables, the durability of protective sheaths or jackets is secondary to electrical stability but still an important part of a cable system. However, for mining cables, the jacket durability is more important than electrical stability. Over 90% of cable failure can be traced to physical damage to the cable in handling, installation or service. Cable is laboratory- and field-tested for the following factors of physical toughness: • Compression-cut is the result of a crushing load that ruptures the insulation and/or jacket. The conductor can act as a cutting tool. • Impact damage occurs upon impingement. The degree of damage is dependent upon the foot-pounds of force and the size of the area impinged. • Tearing is caused in cables that are pulled over rough terrain having sharp rocks or other obstructions. • Abrasion is rare in industrial power cables but occurs readily in mining applications. • Deformation is caused by excessive shearing stress and will be accelerated by high temperatures. Cable used in fill with large rocks is subject to the natural shearing stress of the earth’s movements. 21 • Electrical EP rubber properties are also affected by high temperatures. However, most insulations are designed to remain stable through a variety of temperatures. 6.8 Sunlight Resistance of Cable Coverings The continuous exposure of cable to weather is a major concern for cable engineers. All polymer-type coverings undergo degradation over time. Environment, installation and chemical composition of the polymer significantly influence longevity. Sunlight is a serious and potent threat to wire covering. The ultraviolet band of sunlight promotes the oxidation of polymers and results in cracking, chalking and crazing. Cable coverings that incorporate 2-3% channel black dispersed in the polymer have proven to provide the best protection against sunlight deterioration. 6.7 Moisture Penetration Cables absorb water at a rate determined by the ambient water temperature, conductor temperature, cable insulation temperature, and the permeabilities of the cable jacket and insulation. The usual method for determining moisture resistance properties is a gravimetric measurement of the moisture absorbed by an insulation after seven days in hot water. The value is reported in mg/in2. While gravimetric measurements show the amount of moisture absorbed, there is only one factor when determining the correct insulation for wet environments. Some insulations, such as EPR, will show a high moisture gain but actually have a higher probability of wet environment survival when voltage is applied. Measurements of the maximum flow rate into unloaded 15kV cables in various water temperatures are shown below: 6.7.1 Table 15: Moisture Transmission Milligrams Per Foot Per Day Insulation PE XLPE EPR 50°C 75°C 90°C 3 6 11 10 14 25 42 63 110 The best insulation in a wet environment is the one that demonstrates intrinsic resistance to moisture-induced deterioration, as does EPR insulation in the Electrical Moisture Absorption test. In this test, insulated conductors are immersed in a 90°C water bath with continuous voltage stress applied. The cables are tested until dielectric breakdown occurs. In this test, which more closely resembles actual field service, EPR outlasts polyethylenes by a wide margin. 6.9 ICEA Minimum Requirements for Mining Cable Jackets 6.9.1 Table 16: ICEA Minimum Requirements for CPE and CSPE Jackets Physical Requirements Tensile Strength, lbs. per square inch (The pull stress required to break a specimen) Elongation, percent (The percentage increase in length of a material stressed in tension before rupture) Tensile Stress @ 200%, psi (The tensile force needed to stretch a material to 200% of its original length) Tear Resistance, lbs/in (The force required to initiate a tear in a material under specified conditions) Heavy-Duty Extra-HeavyDuty 1,800 2,400 300 300 500 700 N/A 40 6.9.2 Table 17: ICEA Minimum Requirements for Thermoplastic Polyurethane Jackets Physical Requirements Tensile Strength, lbs. per square inch (The pull stress required to break a specimen) Elongation, percent (The percentage increase in length of a material stressed in tension before rupture) Tensile Stress @ 200%, psi (The tensile force needed to stretch a material to 200% of its original length) Tear Resistance, lbs/in (The force required to initiate a tear in a material under specified conditions) TPU 3,700 400 800 80 22 FLEXIBILITY AND FLEX LIFE Cable flexibility is a relative term; there are no real standards of comparison. In the past, cable coverings were manufactured from natural rubber (a material that is inherently flexible) and had to be specially processed to achieve rigidity. Today, cable coverings are made of polymer compounds that are by nature semi-rigid. This major difference in cable-covering technology has led to new ways to judge cable flexibility — but the best guide is still personal judgment and choice. The flexibility of the copper wires is often offset by the flexibility of the cable insulation and jacket. Even reducing the size of individual wires may not mean the cable becomes more flexible, especially if the cable covering is harder to bend than the wires it is protecting. The primary advantage of a flexible cable is its ease in handling. Rarely is cable faulted because it is too flexible, so the judgment becomes how flexible does it need to be? By taking the following advantages of flexibility into consideration, you should be able to weigh that against your rigidity needs to make a sound judgment. The more flexible the cable: • the easier to handle during reeling and the less likely to sustain damage • the easier to train into position, which subsequently saves space • the easier for craftsmen to work with, which leads to timesaving and safe working practices 23 7 7.1 Low Temperature Flexibility All polymers have a tendency to become progressively stiffer as they are cooled. Cable difficulty occurs when two conditions are reached: • Cable coverings become too stiff to be functional. • Cable coverings become brittle or will shatter under impact. The ability of a cable to withstand impact at a low temperature is a prime factor to consider during application or installation in northern areas. A cable which can be bent successfully under a low temperature may shatter under impact at a significantly higher temperature. In general, XLPE, EPR, and CPE all have excellent low-temperature resistance properties rated to -50°F. General purpose CSPE and PVC compounds have passed cold bend tests in the -22°F to -40°F range. The overall choice for a range of temperature applications is CPE. In laboratory tests, it showed superiority in respect to physical properties at elevated, room and sub-zero temperatures. 7.2 Flex Life as a Function of Stress The elastic limit of soft copper is safely figured at 10% of its breaking strength. The magnitude of stress applied to copper above the elastic limit decreases its flex life at an exponential rate. This is the basis for manufacturers’ recommendations that portable cables not be subjected to tensile stresses above this limit. 7.3 Bending Radii 7.4 ICEA Recommendations Cables are exposed to both electrical and physical environments. In a physical environment, a cable can be considered a machine and amenable to the laws of mechanics. The laws of torsion, shear, tension and compression forces can all be applied to cable technology and bending radius. Mining cable conductors are composed of many wires. The number of wires in an AWG size is dependent on the ultimate application and is usually designated as Class A, B, C, G, H, K, etc. Note that the nearer the end of the alphabet, the greater the number of wires. The recommended bending radius for a specific cable construction is related to, and dependent upon, the length of lay of individual components making up the construction. Maximum efficiency in a conductor composed of a number of wires is obtained only when all of these wires work together during bending, flexing or tension. ICEA minimum recommended bending radii are standardized at a level to assure that working cable will not exceed a critical level, resulting in a non-uniform distribution of individual wire stress. In the following chart, flex life data is shown for a 4 AWG conductor utilizing one bending radius less than the critical diameter (A) and one safely above (B). The ICEA minimum bending radius recommendations for portable cable are: • Braid-shielded portable cables — 8 times the cable diameter • Non-shielded portable cables — 6 times the cable diameter • Flat non-shielded cables — 6 times the minor dimension • Copper tape shielded cables — 12 times the cable diameter 7.3.1 Table 18: Flex Life No. of Strands 2" Sheave 7 37 133 259 420 1064 203 726 3055 6118 13820 20925 4" Sheave 415 2008 13844 47987 187237 500778 Ratio [A/B] .489 .362 .221 .127 .074 .042 Notice that even though the ratio of A to B decreases as the number of strands increases, the flex life increases significantly with the number of strands. 24 STANDARD PRODUCT LINE 8 8.1 Table 19: Product Matrix Type Type Type Type Type Type Type Type Type Type Type Product Range Portable Cables Anaconda® Brand Lead-Cured Mining-Grade Cable Types Carol® Brand CV-Cured Industrial-Grade Cable Types W Flat G Flat G-GC Flat SHD Flat W Round G Round G-GC Round G plus GC SHD-GC SHD plus GC SHD-PCG Longwall 2kV 2kV 2kV 2kV 2kV — 2kV 2 & 5kV 2, 5, 8, 15 & 25kV 2 & 5kV 2 & 5kV — — — — 2kV 2kV 2kV — — — — Mine Power Feeder Type MP-GC (XLPE/PVC) Type MP-GC (EPR/CPE) 25 8 & 15kV 5, 8, 15 & 25kV — — 8.2 Table 20: Mining Cable Product Constructions General Cable offers the broadest line of mining- and industrial-grade flexible power cables. Carol® Brand IndustrialGrade Cables Construction Anaconda® Brand Mining-Grade Cables Conductors: • Fully Annealed Bare Copper • Fully Annealed Tinned Copper X X Type MP-GC: • Fully Annealed Bare Copper X Insulation: • Premium-Grade EPR X Type MP-GC: • Premium-Grade EPR • Premium-Grade XLPE X X X Shielding: Type SHD-GC and SHD Plus GC: • Copper/Textile Braid X Type MP-GC: • EIS/Copper Tape X Features and Benefits Bare Copper Conductor • Flexible conductor for industrial and static applications • Cost-effective conductor designs where cable is not being subjected to repetitive movement Tinned Copper Conductor • Enhanced flex life and increased resistance to wire breakage during repeated movement • Additional corrosion resistance adds to service life EPR Insulation • Outstanding dielectric properties • Long life at temperatures rated from -40˚C to +90˚C • Excellent moisture and corona resistance • Flexible for ease of handling Tinned Copper/Textile Composite Braid Shielding • Provides maximum shield flex life Copper Tape Shielding (EIS) • 100% coverage and added corona protection (EIS - Extruded Insulation Shield) Grounding Conductors: Type G: • Covered Bare Copper • Covered Tinned Copper X X (Flat) Bare Copper Grounding Conductor • Flexible conductor for industrial applications • Cost-effective conductor designs where cable is not being subjected to repetitive movement Type G-GC: • Covered Bare Copper • Covered Tinned Copper • Tinned Copper X X (Flat) X Tinned Copper Grounding Conductor • Enhanced flex life and increased resistance to wire breakage during repeated movement • Additional corrosion resistance adds to service life Type W: • Covered Bare Copper • Covered Tinned Copper X X Type SHD-GC: • Tinned Copper X Type MP-GC: • Tinned Copper X Ground-Check Conductors: • Insulated Bare Copper • Insulated Tinned Copper X Ground-Check Conductor X (Round) • Provides maximum reliability of the ground-check circuit in all round constructions X (Flat) • Insulated with high-strength polypropylene (Anaconda) Jackets: Round Constructions: • CV-Cured, Single-Layer, Reinforced X Chlorinated Polyethylene (CPE) • Lead-Cured, Two-Layer, Reinforced Chlorinated Polyethylene (CPE) Heavy-Duty, Single-Layer Jacket • Heavy-duty construction for non-critical applications and distribution cable • Good physical characteristics with high degree of resistance X (Round) to cutting, abrasion and medium-duty flexing • Excellent general purpose industrial performance Flat Constructions: • Lead-Cured, Chlorinated Polyethylene (CPE) X (Flat) Type MP-GC: • Premium-Grade PVC • Lead-Cured, Chlorinated Polyethylene (CPE) X X Extra-Heavy-Duty, Two-Layer Reinforced Jacket • Increased jacket tensile strength • Increased mechanical strength for high flex applications • Maximum mechanical protection against crushing and tearing • Maximum abrasion resistance • Preferred construction for mining machines *Anaconda® Brand Flat and Type MP-GC cables have an extra-heavy-duty, single-layer jacket. 26 8.3 Table 21: Mining Cable Application Guide APPLICATION CAROL® BRAND INDUSTRIAL GRADE CABLES ANACONDA® BRAND MINING-GRADE CABLES UNDERGROUND MINING APPLICATIONS X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X Longwall Shearers Shuttle Cars Bridge Conveyors High-Voltage Distribution Cutting Machines Loading Machines Continuous Miners Drills Roof Bolters Locomotives Hydraulic Pumps Sectionalized Portable Power Borehole Cables Pumps Accessory Equipment Two-Conductor Welding Belt Drives Hydraulic Power Packs Belt Take-Ups Battery Changers Conveyor Feeder/Breakers SURFACE MINING APPLICATIONS Drills Stripping Shovels Loading Shovels Drag Lines Pumps Accessory Equipment General Cable mining cables are manufactured in accordance with: • ICEA S-75-381 Portable and Power Feeder Cables for Use in Mines and Similar Applications. • CAN/CSA-C22.2 No. 96 Portable Power Cables, and certified by Natural Resources Canada. • CAN/CSA-C22.2 No 96.1 Mine Power Feeder Cables. • Mine Safety and Health Administration flame test requirements and accepted for listing by MSHA. 27 TECHNICAL 9 9.1.2 Table 23: Voltage Drop 9.1 Engineering Information Working Tension The maximum working tension per conductor should not exceed 10 percent of the rated conductor strength. To determine the approximate tensile strength of the cable, multiply the total power conductor area (in2) by 30,000 psi. Bending Radius The recommended Insulated Cable Engineers Association (ICEA) minimum bending radii are as follows: • Braid-shielded portable cables — 8 times the cable diameter • Non-shielded portable cables — 6 times the cable diameter • Flat non-shielded cables — 6 times the minor dimension • Copper tape shielded cables — 12 times the cable diameter 9.1.1 Table 22: Ampacity Correction Factors Approximate for all cable voltages Correction factors are listed below for various ambiant temperatures. AMBIENT TEMPERATURE CORRECTION FACTORS FOR INSULATIONS RATED AT: ˚C 10 20 30 40 50 90˚C 1.26 1.18 1.10 1.00 0.90 When cables are used with one or more layers wound on a reel, the ampacities should be derated as follows: NUMBER OF LAYERS MULTIPLY AMPACITIES BY 1 2 3 4 0.85 0.65 0.45 0.35 Approximate for all cable voltages— Three Conductor Cables 90˚C 60-CYCLE PHASE-TO-PHASE VOLTAGE DROP PER AMPERE PER 1,000 FT AT POWER FACTORS OF: SIZE (AWG or kcmil) 80% 90% 100% 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 0.82 0.54 0.35 0.29 0.24 0.20 0.16 0.14 0.12 0.11 0.10 0.09 0.08 0.90 0.58 0.38 0.31 0.25 0.20 0.17 0.14 0.12 0.11 0.09 0.08 0.07 0.95 0.60 0.38 0.30 0.24 0.19 0.15 0.12 0.10 0.08 0.07 0.06 0.05 9.1.3 Table 24: AWG-to-Metric Conversion Chart SIZE (AWG) 18 16 14 12 10 9 8 6 4 2 1 mm2 SIZE (AWG or kcmil) mm2 0.82 1.31 2.08 3.31 5.26 6.63 8.37 13.30 21.15 33.62 42.40 1/0 2/0 3/0 4/0 250 300 350 500 600 750 1000 53.5 64.4 85.0 107.2 126.7 152.0 177.3 253.4 304.0 380.0 506.7 28 9.2 Why and How Mining Cables Fail Cable breakdowns are neither mysterious nor unaccountable and almost without exception can be traced to one or more of the following causes: 1.Excessive tension 2.Mechanical damage 3.Current overload 4.Improper splicing and termination techniques Excessive Tension Many cable failures are the direct result of excessive tension. A cable that has been “stretched” no longer has the balanced construction that is so vital to long life. Tension on the conductors subjects the individual wires in the strand to compression and shear. These thin wires are damaged and will break more easily when bent or flexed. Tension also elongates the conductor insulation. The elongated insulation is then vulnerable to compression cutting. It will rupture more easily when it is crushed against the stranded conductor during runovers. The insulation will also have a tendency to creep over the conductor at a splice. Jackets under tension lose a considerable part of their resistance to mechanical damage. A jacket under tension is much more likely to be cut or torn. Stretching also causes the copper conductors to take a permanent set. Of course, the insulation and jacket are stretched as well, but they will return to their original length when the tension is removed. This difference in the properties of rubber and copper when subjected to tension will cause the conductors to be wavy and fail prematurely. Current Overload The temperatures of the conductors, insulation and jacket are, of course, elevated when cables are subjected to an electrical load. The resistance of the copper is increased, voltage drop in the cable is increased, and therefore, a reduced voltage is supplied to the machine. As a result, the machine calls for more current, which adds further to cable heating. A trailing cable’s insulation and jacket materials exhibit maximum resistance to physical abuse at the rated conductor temperature of 90°C or less. The ability of these components to withstand damage decreases as the temperature increases. Conditions which normally cause few cable failures suddenly become a problem. At elevated temperatures, the jacket has lost much of its resistance to cutting, crushing, tearing and abrasion. The section of the cable that remains on the reel is most likely to be damaged by electrical overload. Layering on the reel hinders ventilation and heat dissipation. Continued exposure to elevated temperatures will age the jacket, making it hard and brittle and causing crazing or cracking upon subsequent reeling. Improper Splicing and Termination Techniques Over the years, much work has been done to improve both splicing materials and techniques. The following items have been found to be primarily responsible for unsatisfactory splice service: To reduce tension on the cable: 1.Avoid backspooling, if possible. 2.If backspooling is unavoidable, locate the tie point as far back from the haulageway as possible. 3.Tram slowly when passing the tie point. 4.Set hydraulic tension on the cable reel so that approximately 12-15 feet of cable is picked up off the mine bottom when starting to tram. Mechanical Damage This is one of the most prevalent sources of trailing cable failures. Factors initiating mechanical damage include cutting, compression (crushing), punctures and abrasion. In extreme cases of mechanical damage, the failure is instant, and the cause can be assigned on the spot. Many times, however, the cable components are merely “injured” and become latent failures. At that point, it may be more difficult to pinpoint the exact cause and to take remedial action. 29 1.Ending up with a grounding or ground-check conductor which is shorter than the power conductors. 2.Semi-conducting residue on the insulation surface was not removed. 3.Gaps, voids or soft spots in insulating tape build-up. 4.Improper termination of shielding system, leaving inward-pointing projections. 5.Damage to factory insulation by improper removal of shielding systems. 6. Excessive slack in one or more individual conductors. 7. Splice has low tensile strength and is easily pulled in two. 8.Individual wires are damaged during application of connector. 9.Splice is too bulky — will not pass through cable guides or over sheaves. 10.Improper application of the outer covering, allowing water to enter the cable interior. By choosing a cable with an adequate current rating, avoiding excessive tension and mechanical damage, and using proper splicing techniques, it is not unreasonable to reduce cable-related downtime by 50 percent or more. This will, of course, translate into increased production and profits. 9.3 Table 25: Unit Conversion Table UNIT CONVERSION FACTORS UNIT X CONSTANT = UNIT UNIT X CONSTANT = UNIT BTU 778.0 foot-pound (ft-lb) gallons 3.785332 liters (l) BTU 1054.8 joules gallons 0.13368 cubic foot (ft3) BTU 0.293 watt-hours (w-hr) gallons 231.0 cubic inch (in3) centimeters (cm) 0.032808 feet (ft) gallons 3785.332 cubic centimeter (cm3) centimeters (cm) 0.3937 inches (in) grams (g) 15.432 grains centimeters (cm) 0.00001 kilometers (km) gram/centimeter3 (g/cm3) 0.0361275 pounds/in3 (lb/in3) centimeters (cm) 0.010 meters (m) horsepower (hp) 33000.0 ft-lb/min centimeters (cm) 10.0 millimeters (mm) horsepower (hp) 550.0 ft-lb/sec circular mils 0.00064516 circular millimeters horsepower (hp) 745.7 watts (w) circular mils 0.0000007854 inches (in ) inch (in) 0.027178 yards (yd) circular mils 0.00050671 square millimeters (mm2) inch (in) 0.083333 feet (ft) 0.7854 mils2 inch (in) 0.00002540 kilometer (km) meter (m) circular mils 2 2 cubic centimeter (cm ) 0.000035314 cubic foot (ft ) inch (in) 0.025400 cubic centimeter (cm3) 0.061023 cubic inch (in3) inch (in) 2.54000514 centimeter (cm) cubic centimeter (cm3) 0.000001 cubic meter (m3) inch (in) 25.4000514 millimeter (mm) cubic centimeter (cm3) 0.0026417 gallons inch (in) 1000.0 mils cubic foot (ft3) 1728.0 cubic inch (in3) joules 0.000948 BTU cubic foot (ft3) 28317.016 cubic centimeter (cm3) joules 107 ergs cubic inch (in ) 0.00057870 cubic feet (ft ) liters (l) 61.0250 cubic inch (in3) cubic inch (in3) 0.000016387 cubic meter (m3) meters (m) 1.093611 yards (yd) feet (ft) 3 3 3 3 cubic inch (in ) 16.387162 cubic centimeter (cm ) meters (m) 3.2808333 cubic meter (m3) 1000000.0 centimeter (cm) meters (m) 39.37 inch (in) cubic meter (m3) 35.314456 cubic foot (ft3) meters (m) 100.0 centimeter (cm) cubic meter (m3) 264.17 gallons miles 1760.0 yards (yd) feet (ft) 0.00018939 miles miles 5280.0 feet (ft) feet (ft) 0.33333 yards (yd) miles 1.6093 kilometer (km) feet (ft) 12 inches (in) millimeters (mm) 0.0032808 feet (ft) feet (ft) 0.00030480 kilometers (km) millimeters (mm) 0.03937 inch (in) feet (ft) 0.30480 meters (m) millimeters (mm) 0.001 meters (m) feet (ft) 30.480 centimeters (cm) millimeters (mm) 0.01 centimeters (cm) feet (ft) 304.80 millimeters (mm) millimeters (mm) 39.3701 mils feet/pound (ft/lb) 0.00067197 meters/grams (m/g) millimeters (mm) 1000.0 microns (u) foot-pound (ft-lb) 0.001285 BTU watts (w) 44.25 ft-lb/minute foot-pound (ft-lb) 1.356 joules watts (w) 0.737562 ft-lb/sec foot-pound (ft-lb) 0.1383 kilogram/meter (kg/m) watts (w) 0.001341 horsepower (hp) 3 3 30 9.4 Table 26: Temperature Conversion Chart To use this chart, find your known temperature (˚F or ˚C) in the shaded column. If the known temperature is in ˚C and you wish to know its value in ˚F, move to the adjacent right-hand column. If the known temperature is in ˚F and you wish to know its value in ˚C, move to the adjacent left-hand column. °C KNOWN TEMP °F °C KNOWN TEMP °F °C KNOWN TEMP °F °C KNOWN TEMP °F °C KNOWN TEMP Temperature Conversion Formulas °F -45.0 -49.0 -56.2 -17.2 1.0 33.8 10.6 51.0 123.8 38.3 101.0 213.8 66.1 151.0 303.8 -44.4 -48.0 -54.4 -16.7 2.0 35.6 11.1 52.0 125.6 38.9 102.0 215.6 66.7 152.0 305.6 -43.9 -47.0 -52.6 -16.1 3.0 37.4 11.7 53.0 127.4 39.4 103.0 217.4 67.2 153.0 307.4 -43.3 -46.0 -50.8 -15.6 4.0 39.2 12.2 54.0 129.2 40.0 104.0 219.2 67.8 154.0 309.2 -42.8 -45.0 -49.0 -15.0 5.0 41.0 12.8 55.0 131.0 40.6 105.0 221.0 68.3 155.0 311.0 -42.2 -44.0 -47.2 -14.4 6.0 42.8 13.3 56.0 132.8 41.1 106.0 222.8 68.9 156.0 312.8 -41.7 -43.0 -45.4 -13.9 7.0 44.6 13.9 57.0 134.6 41.7 107.0 224.6 69.4 157.0 314.6 -41.1 -42.0 -43.6 -13.3 8.0 46.4 14.4 58.0 136.4 42.2 108.0 226.4 70.0 158.0 316.4 -40.6 -41.0 -41.8 -12.8 9.0 48.2 15.0 59.0 138.2 42.8 109.0 228.2 70.6 159.0 318.2 -40.0 -40.0 -40.0 -12.2 10.0 50.0 15.6 60.0 140.0 43.3 110.0 230.0 71.1 160.0 320.0 -39.4 -39.0 -38.2 -11.7 11.0 51.8 16.1 61.0 141.8 43.9 111.0 231.8 71.7 161.0 321.8 -38.9 -38.0 -36.4 -11.1 12.0 53.6 16.7 62.0 143.6 44.4 112.0 233.6 72.2 162.0 323.6 -38.3 -37.0 -34.6 -10.6 13.0 55.4 17.2 63.0 145.4 45.0 113.0 235.4 72.8 163.0 325.4 -37.8 -36.0 -32.8 -10.0 14.0 57.2 17.8 64.0 147.2 45.6 114.0 237.2 73.3 164.0 327.2 -37.2 -35.0 -31.0 -9.4 15.0 59.0 18.3 65.0 149.0 46.1 115.0 239.0 73.9 165.0 329.0 -36.7 -34.0 -29.2 -8.9 16.0 60.8 18.9 66.0 150.8 46.7 116.0 240.8 74.4 166.0 330.8 -36.1 -33.0 -27.4 -8.3 17.0 62.6 19.4 67.0 152.6 47.2 117.0 242.6 75.0 167.0 332.6 -35.6 -32.0 -25.6 -7.8 18.0 64.4 20.0 68.0 154.4 47.8 118.0 244.4 75.6 168.0 334.4 -35.0 -31.0 -23.8 -7.2 19.0 66.2 20.6 69.0 156.2 48.3 119.0 246.2 76.1 169.0 336.2 -34.4 -30.0 -22.0 -6.7 20.0 68.0 21.1 70.0 158.0 48.9 120.0 248.0 76.7 170.0 338.0 -33.9 -29.0 -20.2 -6.1 21.0 69.8 21.7 71.0 159.8 49.4 121.0 249.8 77.2 171.0 339.8 -33.3 -28.0 -18.4 -5.6 22.0 71.6 22.2 72.0 161.6 50.0 122.0 251.6 77.8 172.0 341.6 73.0 163.4 50.6 123.0 253.4 78.3 173.0 343.4 -32.8 -27.0 -16.6 -5.0 23.0 73.4 22.8 -32.2 -26.0 -14.8 -4.4 24.0 75.2 23.3 74.0 165.2 51.1 124.0 255.2 78.9 174.0 345.2 -31.7 -25.0 -13.0 -3.9 25.0 77.0 23.9 75.0 167.0 51.7 125.0 257.0 79.4 175.0 347.0 76.0 168.8 52.2 126.0 258.8 80.0 176.0 348.8 -31.1 -24.0 -11.2 -3.3 26.0 78.8 24.4 -30.6 -23.0 -9.4 -2.8 27.0 80.6 25.0 77.0 170.6 52.8 127.0 260.6 80.6 177.0 350.6 -30.0 -22.0 -7.6 -2.2 28.0 82.4 25.6 78.0 172.4 53.3 128.0 262.4 81.1 178.0 352.4 -29.4 -21.0 -5.8 -1.7 29.0 84.2 26.1 79.0 174.2 53.9 129.0 264.2 81.7 179.0 354.2 -28.9 -20.0 -4.0 -1.1 30.0 86.0 26.7 80.0 176.0 54.4 130.0 266.0 82.2 180.0 356.0 -28.3 -19.0 -2.2 -0.6 31.0 87.8 27.2 81.0 177.8 55.0 131.0 256.8 82.8 181.0 357.8 -27.8 -18.0 -0.4 0.0 32.0 89.6 27.8 82.0 179.6 55.6 132.0 269.6 83.3 182.0 359.6 -27.2 -17.0 1.4 0.6 33.0 91.4 28.3 83.0 181.4 56.1 133.0 271.4 83.9 183.0 361.4 -26.7 -16.0 3.2 1.1 34.0 93.2 28.9 84.0 183.2 56.7 134.0 273.2 84.4 184.0 363.2 -26.1 -15.0 5.0 1.7 35.0 95.0 29.4 85.0 185.0 57.2 135.0 275.0 85.0 185.0 365.0 -25.6 -14.0 6.8 2.2 36.0 96.8 30.0 86.0 186.8 57.8 136.0 276.8 85.6 186.0 366.8 -25.0 -13.0 8.6 2.8 37.0 98.6 30.6 87.0 188.6 58.3 137.0 278.6 86.1 187.0 368.6 -24.4 -12.0 10.4 3.3 38.0 100.4 31.1 88.0 190.4 58.9 138.0 280.4 86.7 188.0 370.4 -23.9 -11.0 12.2 3.9 39.0 102.2 31.7 89.0 192.2 59.4 139.0 282.2 87.2 189.0 372.2 -23.3 -10.0 14.0 4.4 40.0 104.0 32.2 90.0 194.0 60.0 140.0 284.0 87.8 190.0 374.0 -22.8 -9.0 15.8 5.0 41.0 105.8 32.8 91.0 195.8 60.6 141.0 285.8 88.3 191.0 375.8 -22.2 -8.0 17.6 5.6 42.0 107.6 33.3 92.0 197.6 61.1 142.0 287.6 88.9 192.0 377.6 -21.7 -7.0 19.4 6.1 43.0 109.4 33.9 93.0 199.4 61.7 143.0 289.4 89.4 193.0 379.4 -21.1 -6.0 21.2 6.7 44.0 111.2 34.4 94.0 201.2 62.2 144.0 291.2 90.0 194.0 381.2 -20.6 -5.0 23.0 7.2 45.0 113.0 35.0 95.0 203.0 62.8 145.0 293.0 90.6 195.0 383.0 -20.0 -4.0 24.8 7.8 46.0 114.8 35.6 96.0 204.8 63.3 146.0 294.8 91.1 196.0 384.8 -19.4 -3.0 26.6 8.3 47.0 116.6 36.1 97.0 206.6 63.9 147.0 296.6 91.7 197.0 386.6 -18.9 -2.0 28.4 8.9 48.0 118.4 36.7 98.0 208.4 64.4 148.0 289.4 92.2 198.0 388.4 -18.3 -1.0 30.2 9.4 49.0 120.2 37.2 99.0 210.2 65.0 149.0 300.2 92.8 199.0 390.2 -17.8 0.0 32.0 31 10.0 50.0 122.0 37.8 100.0 212.0 65.6 150.0 302.0 93.3 200.0 392.0 °C = °F = 5 9 (°F - 32) 9 ( x °C) + 32 5 NOTES 32 4 Tesseneer Drive, Highland Heights, Kentucky 41076-9753 GENERAL CABLE, ANACONDA and CAROL are trademarks of General Cable Technologies Corporation. ©2008. General Cable Technologies Corporation. Highland Heights, KY 41076 All rights reserved. Printed in USA Phone: 1.888.593.3355 Fax: 1.800.335.1270 International Tel.: +1.859.572.8000 International Fax: +1.859.572.8058 www.generalcable.com Form No. INS-0084-0908 35013