Family data sheet

Product family datasheet
QUICKTRONIC PROFESSIONAL M
ECG for CFL
Areas of application
_ Emergency lighting systems acc. to EN 50172 / DIN VDE
0108-100
_ Public buildings
_ Sports halls and factories
_ Suitable for luminaires of protection class I
__
Product benefits
_ Long lamp life
_ No adverse effect from frequent on/off switching
_ Automatic restart after lamp replacement
_ Perfect lamp start for applications with motion sensors
_ Separate installations thanks to optional cable clamp for K2 and K3 casings
_ VDE/VDE EMC certified system
Product features
_ Supply voltage: 220…240 V
_ Line voltage: 198…264 V
_ Line frequency: 0 Hz | 50 Hz | 60 Hz
_ Lamp start with optimum filament preheating
_ Energy Efficiency Index EEI: A2
_ Automatic shutdown of defective lamps and at end of life (EoL T.2)
_ Lamp operation: to EN 60929
_ Safety: to EN 61347-2-3
June 20, 2016, 16:48:09
QUICKTRONIC PROFESSIONAL M
© 2016, OSRAM GmbH. All rights reserved.
Page 1 of 8
Product family datasheet
Technical data
Electrical data
Product description
Input voltage
AC
Nominal
voltage
Mains
frequency
Input voltage
DC
QTP-D/E 2X10…13 1)
198…264 V
220…240 V
50…60 Hz
176…276 V 2)
QTP-T/E 1X18,2X18
198…264 V
220…240 V
50…60 Hz
176…264 V
QTP-T/E 1X26…42,2X26 1)
198…264 V
220…240 V
50…60 Hz
176…276 V
198…264 V
220…240 V
50…60 Hz
176…276 V 2)
198…264 V
220…240 V
50…60 Hz
176…276 V 2)
QTP-D/E 1X10…13
QTP-T/E 2X18
1)
1)
1) Optional cable clamp, see chapter ECG mountings - cable clamp
2) Minimum voltage for lamp ignition: 198 V
Light technical data
Product description
Starting
time
QTP-D/E 2X10…13 1)
1.0 s
QTP-T/E 1X18,2X18
QTP-T/E 1X26…42,2X26
1.0 s
1)
QTP-D/E 1X10…13 1)
QTP-T/E 2X18
1.0 s
1.0 s
1)
1.0 s
__
1) Optional cable clamp, see chapter ECG mountings - cable clamp
Dimensions & weight
Product description
Length
Width
Height
Mounting
hole
spacing,
length
Product
weight
Cable crosssection, input
side
QTP-D/E 2X10…13 1)
123.0 mm
79.0 mm
33.0 mm
111.0 mm
190.00 g
0.5…1.5 mm²
QTP-T/E 1X18,2X18
103.0 mm
67.0 mm
31.0 mm
94.0 mm
149.00 g
0.5…1.5 mm²
103.0 mm
67.0 mm
31.0 mm
94.0 mm
148.50 g
0.5…1.5 mm²
93.0 mm
58.0 mm
29.0 mm
84.0 mm
100.00 g
0.5…1.5 mm²
123.0 mm
79.0 mm
33.0 mm
129.5 mm
190.00 g
0.5…1.5 mm²
QTP-T/E 1X26…42,2X26
1)
QTP-D/E 1X10…13 1)
QTP-T/E 2X18
1)
Product description
Cable crosssection, output
side
QTP-D/E 2X10…13 1)
0.5…1.5 mm²
QTP-T/E 1X18,2X18
QTP-T/E 1X26…42,2X26
QTP-D/E 1X10…13
0.5…1.5 mm²
1)
1)
QTP-T/E 2X18 1)
0.5…1.5 mm²
0.5…1.5 mm²
0.5…1.5 mm²
1) Optional cable clamp, see chapter ECG mountings - cable clamp
June 20, 2016, 16:48:09
QUICKTRONIC PROFESSIONAL M
© 2016, OSRAM GmbH. All rights reserved.
Page 2 of 8
Product family datasheet
Product line drawing
QTP-D/E 2X10…13
QTP-T/E 1X18,2X18, QTP-T/E 1X26…42,2X26, QTP-T/E
2X18
__
QTP-D/E 1X10…13
June 20, 2016, 16:48:09
QUICKTRONIC PROFESSIONAL M
© 2016, OSRAM GmbH. All rights reserved.
Page 3 of 8
Product family datasheet
Temperatures & operating conditions
Product description
Ambient
temperature range
QTP-D/E 2X10…13 1)
-20…+50 °C
QTP-T/E 1X18,2X18
-20…+50 °C
QTP-T/E 1X26…42,2X26 1)
-20…+50 °C
QTP-D/E 1X10…13
1)
-20…+50 °C
QTP-T/E 2X18 1)
-20…+50 °C
1) Optional cable clamp, see chapter ECG mountings - cable clamp
Lifespan
Product description
QTP-D/E 2X10…13
ECG lifetime
1)
50000 h 2)
QTP-T/E 1X18,2X18
50000 h 2)
QTP-T/E 1X26…42,2X26 1)
50000 h 2)
QTP-D/E 1X10…13 1)
50000 h 2)
QTP-T/E 2X18
1)
50000 h 2)
1) Optional cable clamp, see chapter ECG mountings - cable clamp
2) At T
case
= 75°C at T point / 10% failure rate
c
__
Expected Lifetime
Product name
QTP-T/E 1X18,2X18
Lamp group
DULUX T/E 18 W
ECG ambient temperature [ta]
40
50
60
Temperature at tc-point [°C]
55
65
70
100000
100000
60000
ECG ambient temperature [ta]
40
50
60
Temperature at tc-point [°C]
55
65
70
100000
100000
60000
ECG ambient temperature [ta]
40
50
60
Temperature at tc-point [°C]
55
65
70
100000
100000
60000
ECG ambient temperature [ta]
40
50
60
Temperature at tc-point [°C]
55
65
70
100000
100000
60000
Lifetime [h]
Product name
Lamp group
DULUX D/E 26 W
Lifetime [h]
QTP-T/E
1X26…42,2X26
DULUX T/E 42 W
Lifetime [h]
DULUX T/E 26 W
Lifetime [h]
June 20, 2016, 16:48:09
QUICKTRONIC PROFESSIONAL M
© 2016, OSRAM GmbH. All rights reserved.
Page 4 of 8
Product family datasheet
Capabilities
Product description
Suitable for fixtures
with prot. class
End of lamp life
safety shutdown
QTP-D/E 2X10…13 1)
I / II
EOL T.2
QTP-T/E 1X18,2X18
I / II
EOL T.2
QTP-T/E 1X26…42,2X26 1)
I / II
EOL T.2
I / II
EOL T.2
I / II
EOL T.2
QTP-D/E 1X10…13
1)
QTP-T/E 2X18 1)
1) Optional cable clamp, see chapter ECG mountings - cable clamp
Certificates & standards
Product description
Approval marks – approval
EEI –
Energy
Label
Protection
class
QTP-D/E 2X10…13 1)
VDE / VDE-EMC / ENEC 10 / GOST / RCM
A2
III
QTP-T/E 1X18,2X18
VDE / VDE-EMC / ENEC 10 / GOST / RCM
A2 BAT
III
QTP-T/E 1X26…42,2X26 1)
VDE / ENEC 10 / VDE-EMC / GOST / RCM
A2 BAT
III
VDE / VDE-EMC / ENEC 10 / GOST / RCM
A2
III
VDE / VDE-EMC / ENEC 10
A2
III
QTP-D/E 1X10…13
1)
QTP-T/E 2X18 1)
__
1) Optional cable clamp, see chapter ECG mountings - cable clamp
June 20, 2016, 16:48:09
QUICKTRONIC PROFESSIONAL M
© 2016, OSRAM GmbH. All rights reserved.
Page 5 of 8
Product family datasheet
Wiring Diagram
QTP-D/E 2X10…13, QTP-T/E 2X18
QTP-T/E 1X18,2X18, QTP-T/E 1X26…42,2X26
QTP-T/E 1X18,2X18, QTP-T/E 1X26…42,2X26
QTP-D/E 1X10…13
__
Application advice
For more detailed application information and graphics please see product datasheet.
June 20, 2016, 16:48:09
QUICKTRONIC PROFESSIONAL M
© 2016, OSRAM GmbH. All rights reserved.
Page 6 of 8
Product family datasheet
Sales and Technical Support
Sales and Technical Support www.osram.com
Country specific information
Product description
Product code
METEL code
SEG number
STK number
UK Org
QTP-D/E 2X10…13
4008321181596
OSRQTPDE2X1013
7980277
4031139
-
QTP-T/E 1X18,2X18
4008321537065
-
7980338
4030041
-
QTP-T/E
1X26…42,2X26
4008321537089
-
7980339
4030031
-
QTP-D/E 1X10…13
4008321181572
OSRQTPDE1X1013
7980275
4031141
-
QTP-T/E 2X18
4008321181619
OSRQTPTE2X18
-
-
-
Download Data
File
Certificates
ENEC-Marks approval
__
Certificates
EMC-Marks approval QTP-M
Certificates
INOTEC
Certificates
Manufacturer´s declaration LampECG combinations: Frequent switching
Certificates
VDE-EMC-Certificate QTP DL_TE
Declarations of conformity
CE conformity
Operating instructions
EAC QTP-DE + QTP-TE
CAD data 3-dim
CAD QTP-DE
CAD data 3-dim
CAD QTP-DE
CAD data PDF
123x79x33 9900041
CAD data PDF
CAD QTP-DE
Product Datasheet
ECG lifetime - QUICKTRONIC non DIM
CAD data 3-dim
93x58x29 9900039
June 20, 2016, 16:48:09
QUICKTRONIC PROFESSIONAL M
© 2016, OSRAM GmbH. All rights reserved.
Page 7 of 8
Product family datasheet
CAD data 3-dim
93x58x29 9900039
CAD data 3-dim
93x58x29 9900039
CAD data PDF
93x58x29 9900039
Logistical Data
__
Product code
Product description
Packaging unit (Pieces/Unit)
Dimensions (length x width x
height)
Volume
Gross weight
4008321181596
QTP-D/E 2X10…13
Shipping carton box
20
428 mm x 78 mm x 257 mm
8.58 dm³
4017.67 g
4008321537065
QTP-T/E 1X18,2X18
Shipping carton box
20
360 mm x 101 mm x 230 mm
8.36 dm³
3266.00 g
4008321537089
QTP-T/E 1X26…42,2X26
Shipping carton box
20
355 mm x 96 mm x 220 mm
7.50 dm³
3192.00 g
4008321181572
QTP-D/E 1X10…13
Shipping carton box
20
315 mm x 66 mm x 196 mm
4.07 dm³
2127.00 g
4008321181619
QTP-T/E 2X18
Shipping carton box
20
428 mm x 78 mm x 257 mm
8.58 dm³
4072.25 g
The mentioned product code describes the smallest quantity unit which can be ordered. One shipping unit can contain one or
more single products. When placing an order, for the quantity please enter single or multiples of a shipping unit.
Disclaimer
Subject to change without notice. Errors and omission excepted. Always make sure to use the most recent release.
June 20, 2016, 16:48:09
QUICKTRONIC PROFESSIONAL M
© 2016, OSRAM GmbH. All rights reserved.
Page 8 of 8