LITTELFUSE V510PA80A

Varistor Products
Base Mount
PA Varistor Series
®
The PA Series of transient surge suppressors are metal-oxide varistors
(MOVs) featuring a rigid base mount package construction, and are
useful in applications which are subject to vibration.
These UL and CSA recognized varistors are available in a wide range of
operating voltages, from 130V to 660V VM(AC)RMS . The base-mount
package has a quick-connect tab terminal that provides a fast, secure
lead attach. The mounting base forms the second electrical connection,
usually chassis ground. Meeting rigid NEMA standards, PA series
varistors have a creep and strike distance capability that minimizes
breakdown along the package surface.
See PA Series Device Ratings and Specifications table for part number
and brand information.
Features
• Wide Operating Voltage Range
VM(AC)RMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130V to 660V
• Creep and Strike Distance Capability Meets Rigid NEMA Standards
• Base Mount Construction Forms One Electrical Connection
• Quick Connect Tab Terminal
• No Derating Up to 85oC Ambient
AGENCY APPROVALS: Recognized under the components program of
Underwriters Laboratories. Certified by CSA.
AGENCY FILE NUMBERS: UL E75961, CSA LR91788.
132
w w w. l i t t e l f u s e . c o m
®
Varistor Products
Base Mount
PA Varistor Series
For ratings of individual members of a series, see Device Ratings and Specifications chart
Continuous:
PA SERIES
Steady State Applied Voltage:
AC Voltage Range (VM(AC)RMS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130 to 660
DC Voltage Range (VM(DC)) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175 to 850
Transient:
Peak Pulse Current (ITM)
For 8/20µs Current Wave (See Figure 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6500
Single Pulse Energy Range
For 10/1000µs Current Wave (WTM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 to 250
Operating Ambient Temperature Range (TA). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -55 to 85
Storage Temperature Range (TSTG) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -55 to 125
Temperature Coefficient (αV) of Clamping Voltage (VC) at Specified Test Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . <0.01
UNITS
V
V
A
J
C
O
C
%/OC
O
CAUTION: Stresses above those listed in “Absolute Maximum Ratings” may cause permanent damage to the device. This is a stress only rating and operation of the
device at these or any other conditions above those indicated in the operational sections of this specification is not implied.
Device Ratings and Specifications
MAXIMUM RATINGS (85 oC)
CONTINUOUS
SPECIFICATIONS (25 oC)
TRANSIENT
PEAK
CURRENT
(8/20µs)
VARISTOR VOLTAGE
AT 1mA DC
TEST CURRENT
MAX CLAMPING
VOLT V C AT TEST
CURRENT (8/20µs)
TYPICAL
CAPACITANCE
VRMS
VDC
ENERGY
(10/1000µs)
VM(AC)
VM(DC)
WTM
ITM
MIN
VN(DC)
MAX
VC
IP
f = 1MHz
(V)
(V)
(J)
(A)
(V)
(V)
(V)
(V)
(A)
(pF)
V130PA20A
130
175
70
6500
184
200
243
360
100
1900
V130PA20C
130
175
70
6500
184
200
220
325
100
1900
V150PA20A
150
200
80
6500
212
240
284
420
100
1600
V150PA20C
150
200
80
6500
212
240
243
360
100
1600
V250PA40A
250
330
130
6500
354
390
453
675
100
1000
V250PA40C
250
330
130
6500
354
390
413
620
100
1000
V275PA40A
275
369
140
6500
389
430
494
740
100
900
V275PA40C
275
369
140
6500
389
430
453
680
100
900
V320PA40A
320
420
160
6500
462
510
565
850
100
750
V320PA40C
320
420
160
6500
462
510
540
800
100
750
V350PA40A
350
460
165
6500
500
559
618
910
100
700
V350PA40C
350
460
165
6500
500
535
570
840
100
700
V420PA40A
420
560
170
6500
610
680
790
1160
100
600
V420PA40C
420
560
170
6500
610
680
690
1050
100
600
V480PA80A
480
640
180
6500
670
750
860
1280
100
550
V480PA80C
480
640
180
6500
670
750
790
1160
100
550
V510PA80A
510
675
190
6500
735
820
963
1410
100
500
V510PA80C
510
675
190
6500
735
820
860
1280
100
500
V575PA80A
575
730
220
6500
805
910
1050
1560
100
450
V575PA80C
575
730
220
6500
805
910
960
1410
100
450
V660PA100A
660
850
250
6500
940
1050
1210
1820
100
400
PART NUMBER
AND DEVICE
BRANDING
w w w. l i t t e l f u s e . c o m
133
2
VARISTOR
PRODUCTS
Absolute Maximum Ratings
Varistor Products
Base Mount
PA Varistor Series
Power Dissipation Ratings
100
PERCENT OF RATED VALUE
Should transients occur in rapid succession, the average power dissipation
required is simply the energy (watt-seconds) per pulse times the number
of pulses per second. The power so developed must be within the
specifications shown on the Device Ratings and Specifications table for
the specific device. Furthermore, the operating values need to be derated
at high temperatures as shown in Figure 1. Because varistors can only
dissipate a relatively small amount of average power they are, therefore,
not suitable for repetitive applications that involve substantial amounts of
average power dissipation.
90
80
70
60
50
40
30
20
10
0
-55
50
60
70
80
90
100
110
120
130
140 150
AMBIENT TEMPERATURE ( oC)
PERCENT OF PEAK VALUE
FIGURE 1. CURRENT, ENERGY AND POWER DERATING
CURVE
100
O1 = Virtual Origin of Wave
T = Time From 10% to 90% of Peak
T1 = Virtual Front time = 1.25 • t
T2 = Virtual Time to Half Value (Impulse Duration)
Example: For an 8/20µs Current Waveform:
8µs = T1 = Virtual Front Time
20µs = T2 = Virtual Time to Half Value
90
50
10
O1
T
TIME
T1
T2
FIGURE 2. PEAK PULSE CURRENT TEST WAVEFORM
Transient V-I Characteristics Curves
MAXIMUM PEAK VOLTS (V)
4,000
3,000
6,000
5,000
MAXIMUM CLAMPING VOLTAGE
V660PA80A
“A” SUFFIX
V575PA80A
130 TO 660VM(AC) RATING
V510PA80A
o
o
TA = -55 C TO 85 C
V480PA80A
V420PA80A
2,000
1,000
900
A40A
800
700
600
500
V320PA40A
400
V150PA20A
300
V130PA20A
200
-3
10
10-2
V275PA40A
V250PA40A
100
101
102
PEAK AMPERES (A)
103
FIGURE 3. CLAMPING VOLTAGE FOR V130PA20A V660PA100A
134
3,000
104
V660PA100C
V575PA80C
V510PA80C
V480PA80C
V420PA80C
2,000
1,000
900
800
700 V350PA40C
600
500
400 V320PA40C
300
10-1
MAXIMUM CLAMPINGVOLTAGE
“C”SUFFIX
130 TO 660VM(AC) RATING
TA = -55oC TO 85oC
4,000
MAXIMUM PEAK VOLTS (V)
6,000
5,000
V275PA40C
V250PA40C
V150PA20C
V130PA20C
200
10-3
10-2
10-1
100
101
102
PEAK AMPERES (A)
103
FIGURE 4. CLAMPING VOLTAGE FOR V130PA20C V660PA100C
w w w. l i t t e l f u s e . c o m
104
Varistor Products
Base Mount
PA Varistor Series
Pulse Rating Curves
1
2
DISC SIZE 20mm
V130PA20A -V320PA40C
10
103
SURGE CURRENT (A)
500
200
100
50
20
INDEFINITE
10
2
DISC SIZE 20mm
V420PA40A -V660PA100C
10
102 3
10
104
105
106
2,000
104
105
106
1,000
1
5,000
102
2,000
SURGE CURRENT (A)
10,000
1,000
500
2
200
VARISTOR
PRODUCTS
10,000
5,000
100
50
20
INDEFINITE
10
5
5
2
2
1
20
100
1,000
1
10,000
20
100
IMPULSE DURATION ( µs)
FIGURE 5. SURGE CURRENT RATING CURVES FOR
V130PA20A - V320PA40C
1,000
IMPULSE DURATION ( µs)
10,000
FIGURE 6. SURGE CURRENT RATING CURVES FOR
V420PA40A - V660PA100C
NOTE: If pulse ratings are exceeded, a shift of VN(DC) (at specified current) of more than ±10% could result.This type of shift, which normally results in a decrease of VN(DC),
may result in the device not meeting the original published specifications, but it does not prevent the device from continuing to function, and to provide transient protection
Mechanical Dimensions
H1, 2, 3
D
A
Q
J
b2
S
SEATING
PLANE
C
F
B
TC
ØP
2 HOLES
h
E
b
b3
T
ØD1
ØT
TAB
NOTES:
1. Tab is designed to fit 1/4” quick-connect terminal.
2. Case temperature is measured at TC on top surface of base
plate.
MILLIMETERS
INCHES
SYMBOL
MIN
NOM
MAX
MIN
NOM
A
-
-
14.3
-
-
0.570
-
b
-
-
6.6
-
-
0.260
1
MAX
NOTES
b2
3.94
4.06
4.18 0.155
0.160
0.165
-
b3
3.05
3.17
3.29 0.120
0.125
0.130
-
-
0.510
-
B
-
-
C
-
-
6.6
-
-
0.260
-
D
-
-
66.3
-
-
2.610
-
ØD1
-
-
33.5
-
-
1.320
-
-
11.2
-
-
E
F
7.50
12.9
-
0.440
-
-
7.62
7.75 0.295
0.300
0.305
-
h
-
0.8
1.0
-
0.030
0.040
-
3. H1 (130-150VRMS devices).
H2 (250-320VRMS devices).
H3 (420-660VRMS devices).
H1
-
-
25.6
-
-
1.010
3
H2
-
-
28.3
-
-
1.120
3
4. Electrical connection: top terminal and base plate.
H3
-
-
32.8
-
-
1.290
3
J
-
-
8.1
-
-
0.320
-
5. Typical weight: 30g.
ØP
5.6
-
6.0
0.220
-
0.240
-
Q
50.6
50.8
51.0
1.990
2.000
2.010
-
S
18.4
19.2
20.0
0.72
0.75
0.78
-
T
-
-
1.0
-
-
0.040
-
ØT
2.8
-
-
0.110
-
-
-
TC
-
3.2
-
-
0.126
-
2
w w w. l i t t e l f u s e . c o m
135
Varistor Products
Base Mount
PA Varistor Series
Suggested Hardware and Mounting Arrangements
TYPICAL NON-ISOLATED MOUNTING
TYPICAL ISOLATED MOUNTING
#10-32 PAN HEAD
SCREW
#6-32 SCREW
THERMAL
GREASE
LAYER
#6 FLAT WASHER
PHENOLIC SHOULDER
WASHER
SPACER
THERMAL
QUICK
CONNECT
#10 FLAT WASHER
VARISTOR
MOUNTING
SURFACE
LOCK WASHER
(NOTE 6)
THERMAL
GREASE
LAYER
#10-32 NUT
VARISTOR
MICA INSULATOR
MOUNTING
SURFACE
LOCK WASHER
#6-32 NUT
NOTE:
6. GE G623, Dow Corning, DC3, 4, 340, or 640 Thermal Grease recommended for best heat transfer.
1,000V Isolation Kit containing the following parts can be ordered by part #A7811055 (Qty).
(1) MICA insulation 1”/3.1”/0.005” thick
(2) Phenolic shoulder washer
(2) #6-32/3 / 4 screw
(2) #6 internal tooth lock washer
(1) 1/4 ” quick-connect terminal
(1) Spacer
(2) #6-32 nut
(2) #6 flat washer
Ordering Information
V XXX PA XX X
VARISTOR
CLAMPING VOLTAGE
SELECTION DESIGNATOR
A = Standard
C = Low Clamp Voltage Option
VM(AC)
130V to 660V
RELATIVE ENERGY INDICATOR
SERIES DESIGNATOR
136