No. 77 - Residual voltage on load side of an open circuit breaker

www.usa.siemens.com/techtopics
TechTopics No. 77
Residual voltage on load side of an open circuit breaker
Siemens is occasionally asked to comment on the existence of
a voltage on the load side of an open circuit breaker. For
convenience, this will be called “residual voltage.” Most often,
this is a result of measurements made during commissioning a
project, when there is no load on the switchgear bus and the
main circuit breaker is in the connected position and open,
with the incoming source (the line side of the main circuit
breaker) energized. Any feeder or tie circuit breakers connected
to the main bus are open.
In this situation, the open contacts of the circuit breaker
constitute a capacitor in series with the incoming source and
the load-side (main) bus. The main bus has capacitance to
ground, but in the situation described, has no other load as the
feeder and tie circuit breakers are open.
The resulting circuit is a simple capacitive voltage divider, as
illustrated in the schematic.
Consider a typical example, a lineup of 13.8 kV switchgear with
a main circuit breaker, eight feeder circuit breakers and one tie
circuit breaker arranged in a two-high (stacked) configuration.
In this example, the load-side main bus consists of
approximately 45 feet (about 14 meters) of copper bus. The
capacitance between the open contacts of the vacuum
interrupter, C1, is of the order of 15 picofarads (pf). The
capacitance of the main bus is of the order of 10 pf per meter
(refer to IEEE C37.015, clause B.2), or 140 pf for this example.
Figure 1: Schematic
Variables:
Vin
Incoming source voltage on the line
side of an open main circuit breaker
Vout
Voltage on main bus (load side of
main circuit breaker)
C1
Capacitance between the open
contacts of the vacuum interrupter
C 2
Capacitance of the switchgear main
bus to ground.
Vin
C1
Vout
C2
The voltage relationship for a capacitive
voltage divider is:
Vout = Vin
C1
(C1 + C2)
Answers for infrastructure.
In this example, when energized at 13.8 kV phase-phase (8 kV
phase-ground), the expected voltage on the load side of the
main circuit breaker (in this example, on the main bus) with all
feeder and tie circuit breakers open would be:
Vout = Vin (C1/(C1 + C2))
Vout = 8.0 kV (15/(15 + 140))
Vout = 8.0 kV (15/155)
Vout = 755 volts.
This is a very simplistic example and ignores several factors,
such as the capacitance of the circuit breaker conductors and
primary disconnect assemblies in the feeder circuit breaker
cubicles. These factors would increase the load-side
capacitance, reducing the resulting voltage (Vout) calculated.
However, this does not alter the basic concept that, in the
situation described, the open circuit breaker is essentially a
capacitor in series with the capacitance of the load-side
conductors to ground, and thus that there will be a voltage on
the load side of the circuit breaker.
The capacitance values cited are representative, but will vary
from installation to installation. The capacitance between the
open contacts of the vacuum interrupter will vary with the
diameter of the contacts and the gap between them. The bus
bar capacitance is an approximation based on a review of the
literature, but is believed to be representative. The figures
presented in the example are for purposes of illustration of the
physics phenomena rather than an attempt for precision.
What are the ramifications of this residual voltage? Siemens
believes this is an academic issue rather than a practical issue.
No person should be working on the main bus in this
condition, as this would violate numerous documents relating
to safety.
The standards for switchgear do not recognize an open circuit
breaker as an isolator. In an outdoor distribution circuit breaker
situation, air disconnect switches should be located on each
side of the circuit breaker to provide the isolation function
before maintenance is performed. In a drawout, metal-clad
switchgear situation, the circuit breaker should be withdrawn
from the connected position to the test or disconnected
position, as IEEE C37.20.2 recognizes this as the condition that
fulfills the function of an isolator.
The National Electric Code® (NEC)® ANSI/NFPA 70® also
recognizes an open circuit breaker does not provide an
isolating function. Specifically, article 490.22 says (in part):
490.22 Isolating Means. Means shall be provided to
completely isolate an item of equipment from all
ungrounded conductors. The use of isolating switches shall
not be required where there are other ways of de-energizing
the equipment for inspection and repairs, such as draw-outtype metal-enclosed switchgear units and removable truck
panels.
When a load is connected to the main bus, the residual voltage
largely disappears. To illustrate this, consider the previous
example, with one of the feeder circuit breakers closed, and
with a cable circuit of 20 meters (66 feet) length connected to
the feeder circuit breaker, but with the switch or circuit breaker
at the remote end open. Therefore, closing the feeder circuit
breaker only picks up the capacitance of the feeder circuit
cable. For the example, the cables must be shielded (in
accordance with NEC), for which typical cable capacitance is
200 pf/m to 400 pf/m (refer to IEEE C37.015, clause B.2).
For this situation, the residual voltage (Vout) becomes:
Vout = Vin (C1/(C1 + C2))
Vout = 8.0 kV (15/(4,000 + 15 + 140))
Vout = 8.0 kV (15/4,155)
Vout = 28 volts.
Occupational Safety and Health Administration (OSHA)
regulations and NFPA 70E® (Electrical Safety in the Workplace)
require that any circuit over 50 V be treated as energized until
it is isolated and safety grounds are installed. The description
of an Electrically Safe Work Condition in NFPA 70E is:
A state in which an electrical conductor or circuit part or
near has been disconnected from energized parts, locked/
tagged in accordance with established standards, tested to
ensure the absence of voltage, and grounded if determined
necessary.
Siemens considers it mandatory that safety grounds be applied
before any work is performed on equipment over 50 V. In
metal-clad switchgear, isolation requires withdrawal of the
drawout circuit breaker to the test or disconnected position.
Tests for the presence of voltage are required before any work
can be performed on the conductors. After it has been verified
that the conductors are de-energized, safety grounds are to be
applied.
Therefore, the processes required by OSHA and NFPA 70E will
place the equipment in an electrically safe work condition, and
eliminate any residual voltage.
The information provided in this document contains merely general
descriptions or characteristics of performance which in case of actual
use do not always apply as described or which may change as a result of
further development of the products. An obligation to provide the
respective characteristics shall only exist if expressly agreed in the terms
of contract.
All product designations may be trademarks or product names of
Siemens AG or supplier companies whose use by third parties for their
own purposes could violate the rights of the owners.
Siemens Industry, Inc.
7000 Siemens Road
Wendell, NC 27591
Subject to change without prior notice.
Order No.: E50001-F710-A252-X-4A00
All rights reserved.
© 2012 Siemens Industry, Inc.
For more information, contact: +1 (800) 347-6659
www.usa.siemens.com/techtopics