PDF Download(4021KB)

Technical Explanation for Timers and Time Switches
CSM_Timer_Timeswitch_TG_E_7_3
Introduction
Sensors
What Is a Timer?
A Timer is a control device that outputs a signal at a preset time after an input signal is received.
Timer Mechanisms
Switches
(3) Timing Section
Output
Section
(4) Output Section
Power Supply
Section
Operating Modes of Timers
Example for the H3CR-A
(1)
(5)
(1) Time setting knob
(2) Time unit selector
(3) Time range selector
(4) Operating mode
selector
(2)
The following four basic operating modes are the most
commonly used.
ON-delay Operation (Mode A)
OFF-delay Operation (Mode D)
Operation
Modes
Power Supplies /
In Addition
Flicker Operation (Mode B)
Interval Operation (Mode E)
Others
Indications
The pointers on the Timer do not move along with time like the
hands of a clock do. You cannot see the progression of time.
Therefore, two operation indicators are provided on the upper
left of the Timer to identify the timer status.
(5) Run/Power Indicator (Green)
Run indicator: Indicates whether the time is being
measured or the time has reached.
Power indicator: Indicates whether power is being
supplied to the Timer.
Fundamentally, the indicators will be lit when the power is
being supplied. However, they will flash when the time is
being measured.
(6) Output Indicator (Orange)
Used to see the status of the output. Lit when a signal is
output.
The operating mode determines the output method that is
used when the set time has reached.
Energy Conservation Support /
Environment Measure Equipment
A variety of time ranges can be set with the H3CR-A using
Note the time unit selector and time range selector.
Motion / Drives
(3)
(4)
Automation Systems
The operating mode selector is
in the upper-right corner on the
H3CR-A.
Settings
(6)
Outputs signals
to output devices.
Control Components
Settings and Indications of Timers
Relays
(1) Power Supply Section
Supplies the applied voltage
to the internal components.
Timing
Section
Receives signals from input
devices and outputs the
signals to the timing section.
Input
Section
(2) Input Section
Safety Components
Measures the time and outputs
a signal to the output section
at specified time.
Common
1
Technical Explanation for Timers and Time Switches
Flicker Operation
ON-delay Operation
Sensors
Input
Input
Time counted out
Output
t
After t seconds
t
t
t
t
t
t
t
t
Output
Switches
With flicker operation, an output repeatedly turns ON and OFF
at the set time after an input is received.
Application: Automatic Control of Fountains
Safety Components
With ON-delay operation, the Timer receives an input and
then an output signal is output by switching the Timer contacts
after a set time delay.
This name is used because there is a delay between when the
input signal is received (i.e., turns ON) and when the output
signal is output.
ON-delay operation is the operating mode most often used for
automated machines.
Relays
The water is
repeatedly released
and stopped at
intervals of two
minutes.
Application: Pushbutton Signals
When the pedestrian
pushbutton is pressed for a
traffic signal, the signal light
changes from red to green
after a delay.
Control Components
Interval Operation
Input
Automation Systems
OFF-delay Operation
t
Output
Input
Time counted out
t seconds
Application: Amusement Park Rides
Motion / Drives
Output
With interval operation, the output turns ON at the same time
as the input and the output turns OFF after a set time.
The ride operates
for five minutes
when 100 yen is
inserted.
Power Supplies /
In Addition
Application: Car Ceiling Lights
When you get in your car, the
ceiling light turns ON when the
door is opened. The light
remains lit for several seconds
after you get into the car and
close the door.
Energy Conservation Support /
Environment Measure Equipment
With OFF-delay operation, the output turns ON at the same
time as the input and then the output turns OFF when the
Timer contacts switch after the set time has expired. The set
time is calculated from when the input turns OFF.
This name is used because there is a delay between when the
input turns OFF and when the output turns OFF.
Others
Common
2
Technical Explanation for Timers and Time Switches
Timer Starting Methods
Sensors
There are two starting methods for the operating modes.
Power ON-delay
Safety Components
Signal ON-delay
Switches
Example: ON-delay Operation
Signal ON-delay operation: Measuring time starts when the
input section receives an input
while voltage is being applied
to the Timer power supply
section.
Power ON-delay operation: Measuring time starts when
voltage is applied to the Timer
power supply section.
Power
supply
Power
supply
Input
Output
t
Output
t
Relays
Control Components
Differences between Signal ON-delay Operation and
Power ON-delay Operation
(1) Accuracy* Operation will not be stable unless a brief
period elapses after the power supply is
turned ON to the timing section of the Timer.
Power supply start:Operation is unstable because
measuring time starts at the same time
that the power supply turns ON.
Therefore, deviation will occur in the
operation time immediately after
starting the Timer.
Signal start:
Stable time accuracy is ensured
because a voltage is already applied to
the Timer before starting the Timer.
The accuracy of the signal start is generally considered
better. For some models, however, such as the H3CR,
there is no change in accuracy.
Automation Systems
Motion / Drives
*Accuracy is the correctness of the time.
Power supply start (H3CR-A8)
Power Supplies /
In Addition
Gate input
Reset input
Start input
Signal start (H3CR-A)
Energy Conservation Support /
Environment Measure Equipment
(2) Terminal Arrangement
Power supply
Power supply
Others
• Models with a signal start require three external inputs, so
they have many terminals.
• Models with a power supply start (H3CR-A8) are the H3CR
Timers most often used for automated machinery.
Common
3
Technical Explanation for Timers and Time Switches
What Is a Time Switch?
Sensors
A Time Switch is a control device that turns a load ON and OFF at the set times.
Time Switch Mechanisms
Switches
(3) Timing Section
Output
Section
Input
Section
Receives signals from input
devices.
Safety Components
(2) Input Section
Timing
Section
Measures the time and outputs
a signal to the output section
at specified time.
(4) Output Section
Outputs signals
to output devices.
Power Supply
Section
Relays
(1) Power Supply Section
Supplies the applied voltage
to the internal components.
Control Components
However, most models of Time Switches do not have an input section.
If there is an input section, it is not used to output signals to the timing section, rather, it is used to control some of the functions of
the Time Switch, such as adjusting the time.
Settings and Indications of Time Switches
Settings
Automation Systems
Example for the H5F
Display
Present Day Indicator
H5F TIME SWITCH
SU MO TU WE TH FR SA
Operation Day Indicator
A Mode Key
Time Adjustment
Mode Indicator
B Hour Key
Displays the Present Time,
Operation Time, and Time Width
SU MO TU WE TH FR SA
Lit: Operation day
Not lit: Non-operation day
Flashing: Specified
operation day
S
Partial Operation on
Specified Day Indicator
I Timer/Pulse
output Key
H Output ON/OFF
Switch
OUT
TMR/ P
MODE
h
m/ P WD
CLR
SELECT
d
WRITE
ON
AUTO
OFF
+1h
HOLIDAY
TEST
G Clear/Summer
Time Key
D Write Key
E Day Shift/Program Test Key
F Select/Holiday Key
Output Indicator
Lit when control output is ON.
Power Indicator
Lit when power is supplied
to the Time Switch.
Function
C
Sets minutes or a pulse time width.
D
Writes the set data to memory or confirms settings with the program
check function.
E
Moves the cursor to specify a day or starts the program check
function.
F
Specifies or cancels a specified day or switches to holiday setting
mode.
G
Deletes the set data and initializes the day of operation or sets/clears
summer time.
H
ON:
Turns on the output regardless of the setting.
AUTO: Turns on/off the output according to the setting.
OFF: Turns off the output regardless of the setting.
Override and automatic return operation can be executed by using
this key in combination with the Write Key.
I
Selects timer operation or pulse-output operation.
+1h
AM
PM
Next Operation
Indicators
P
Pulse Width Unit Indicator
Summer Time Indicator
Lit when set to summer
time.
Operation Setting
Mode Indicator
Pulse Operation Indicator
Lit: Pulse-output operation
Not lit: Timer operation
Run mode:
Displays the direction (i.e., ON or OFF) and time
of the next output operation.
Operation time setting mode: Displays the program number for the setting.
Holiday setting mode:
Displays hday (hday) when the Time Switch
is in holiday setting mode.
Program check:
Displays test (test) during program check.
Common
Sets hours or switches between 12-hour (am/pm) and 24-hour
display.
s
m
P
Others
B
ON
PW
Power Supplies /
In Addition
A
Switches between time adjustment mode, the operation setting
modes, and run mode.
AM
PM
Energy Conservation Support /
Environment Measure Equipment
No.
C Minutes/Pulse Time Width Key
Motion / Drives
OUT
POWER
4
Technical Explanation for Timers and Time Switches
Operating Modes of Time Switches
Sensors
The operating mode determines the ON/OFF output method
that is used for the set times.
Timer Operation (ON/OFF Operation)
Timer Operation (ON/OFF Operation)
Switches
ON time
Pulse-output Operation
OFF time
With timer operation, the Time Switch controls the output
according to the set ON and OFF times.
Forced ON/OFF Operation
Safety Components
Application 1: Warm-up Operation for Packing Machine
Operating
Modes
Program Example
Override and Automatic Return Operation
Warm-up
operation
Start of work.
Power turned
ON by worker.
Partial Operation on Specified Day
Warm-up
operation
Relays
Power turned ON
by a Time Switch.
Holiday Setting
Start of work
Control Components
The packing machine can be
warmed up before the employees
come to work so that work can
begin immediately.
Automation Systems
Application 2: School Chimes
♪
♪
Motion / Drives
Program Example
10 s
10 s
10 s
Energy Conservation Support /
Environment Measure Equipment
The chimes can
be sounded at the
start of classes, at
the lunch break,
and at the end of
classes.
Power Supplies /
In Addition
Pulse-output Operation
Pulse width
Others
ON time
With pulse-output operation, the Time Switch outputs a pulse
of a specified time width at the set ON time.
Common
5
Technical Explanation for Timers and Time Switches
Override and Automatic Return Operation
With a Time Switch, the progression of time starts when a
voltage is applied to the power supply section.
* When the power supply section is OFF, time progresses and the settings are
retained, but no operations are performed to turn the output ON or OFF.
Terminal Arrangement
Example for the H5F-A/B
Switches
Regular program
Time Switch Starting Methods
Sensors
Forced ON/OFF Operation
Forced ON/OFF Operation is used to force the output ON or
OFF by using the output ON/OFF switch regardless of the
control output setting.
Power supply: 100 to 240 VAC
Output operation
Safety Components
Start of override and
automatic return operation
With override and automatic return operation, the output ON/
OFF switch and the Write Key are used to hold the control
output ON until the next OFF time.
Partial Operation on Specified Day
Load
Load
power supply
Relays
Program 1 Program 2
(special)
Regular program
Control Components
Operation on
operation day
Operation on
specified day
You can select days on which to execute only part of the set
operations.
Automation Systems
Holiday Setting
Operation on Operation on
operation day holiday
Regular program
Motion / Drives
Operation in
present week
Operation from
next week
Energy Conservation Support /
Environment Measure Equipment
It is possible to set an operation day in the present week as a
holiday (i.e., a non-operation day: output will be OFF
regardless of the settings). When that day has passed,
operation will continue according to the regular program, and
operation will be executed as normal on that day from the
following week.
Power Supplies /
In Addition
Others
Common
6
Technical Explanation for Timers and Time Switches
Explanation of Terms
Accuracy of Operating Time
The period of time during which the specified voltage is
applied to the operating circuit.
The difference in operating times measured when the Timer
repeats operation under the same conditions with a specified
set time.
OFF Time
Operating Time
Holding Time
The period of time from the completion of the time-limit
operation to the start of the reset operation.
where,
T max.: Maximum value of operating times measured at the same set time
T min.: Minimum value of operating times measured at the same set time
TMs: Maximum scale time (TMs is a set value in the case of a Digital Timer.)
Safety Components
The period of time from the application of the specified voltage
to the operation circuit until the completion of the time-limit
contact operation.
Formula for calculation (with operating time measured more
than 5 times):
Accuracy of operating time=± 1 × Tmax−Tmin ×100 (%)
2
TMs
Switches
The period of time between the moment that resetting begins
and the moment that the operating voltage is applied to the
operating circuit again. The OFF time is longer than the
resetting time.
Sensors
ON Time
The difference in the operating times appears as a shift from
the central value of operation, so the maximum or minimum
values divided by 2 and expressed as plus (+) and minus (-)
indication.
Resetting Time
Tmax
OFF time
Operating circuit
(= power supply)
Time-limit SPST-NO
contacts SPST-NC
Tmin
If the settings of an Analog Timer is changed while it is
performing time-limit operation, the following operation will
result.
T3−T1
T=T1+T2×
T3
Internal mechanism
Internal circuit
Operating
time
Holding Resetting
time
time
Setting Error
The difference between the actual operating time and scale
time.
Formula for calculation (measurement position can be any
scale position as long as it is set to 1/3 min. of the maximum
scale time):
TM−Ts
Setting error=
×100 (%)
TMs
For a Time Switch, the setting error is applied for the pulseoutput operating time.
A single time rating that combines the setting error, accuracy
of operating time, influence of temperature, and influence of
voltage.
This rating applies to all measurement results for
measurements made under the setting error, influence of
temperature, and influence of voltage conditions.
Power Supplies /
In Addition
Total Error (Time Switch)
To Automatically reset the Timer by interrupting the voltage
that is supplied to the operating circuit.
To reset the Timer by applying the required voltage to the
reset circuit.
Energy Conservation Support /
Environment Measure Equipment
TM: Average value of five or more measured operating times
Ts: Set time
TMs: Maximum scale time (TMs is a set value in the case of a Digital Timer.)
Self-reset
Electrical Reset
Motion / Drives
The resetting time of the Timer is the period of time during
which all the internal components including the contacts,
pointer, and the circuit components, such as the capacitor, of
the Timer are reset.
If the Timer is operated with an insufficient OFF time (i.e., the
OFF time is less than the rated resetting time), the normal
operation of the Timer cannot be expected. In such cases, the
Timer may operate with an insufficient operating time, operate
instantaneously, or not operate at all. Be sure that the OFF
time of the Timer is the same as or more than the rated
resetting time.
Final time-up time
Time elapsed
New setting
Previous setting
Automation Systems
T:
T1 :
T2 :
T3 :
Control Components
ON time
Relays
The period of time from the interruption of the voltage supplied to the
operating circuit during or after the time-limit operation until the return
of the Timer to its initial state.
Central value (T)
Cyclic Error (Error per Month) (Time Switches)
Others
The error time in the internal clock per month at an ambient
temperature of 25°C.
Common
7
Technical Explanation for Timers and Time Switches
Vibration Resistance (Malfunction)
The change in the operating time when the voltage of the
control power source changes within the allowable voltage
range.
Formula for calculation:
Variation due to voltage change
TMx1−TM1
=±
×100 (%)
TMs
The range of vibration during operation in which contacts that
are closed will not open by vibration for at least the specified
time (1 ms).
OFF Time Characteristics
Insulation Resistance
The resistance provided by an electrically insulating material
between charged metal parts and uncharged metal parts,
between control outputs and operating circuits, etc.
Dielectric Strength
The voltage level that will not cause insulation breakdown
when applied for 1 minute to the same location as in the
insulation resistance measurement.
Impulse Withstand Voltage (AC)
A voltage imposed between the operating power supply
terminals or between a charged terminal and non-charged
metal part to test the resistance to surge voltages. The
impulse withstand voltage imposed between the operating
power supply terminals is 3 kV and that imposed between a
charged terminal and non-charged metal part is 4.5 kV with
both using a ±1.2 × 50-μs standard waveform.
Noise Immunity
The malfunction and destruction resistance of the Timer
against external noise.
The noise immunity of the Timer is checked with a noise
simulator, an inductive load, an oscillating relay, and static
electric noise.
Energy Conservation Support /
Environment Measure Equipment
Mechanical Life Expectancy
The life expectancy of a Timer when the control output of the
Timer is operated under a no-load condition.
Power Supplies /
In Addition
The OFF time characteristics are determined by the charging
and discharging of a capacitor and resistor used in
combination as an Electronic Timer. The characteristics vary
from ±1.5% to ±5%.
The accuracy of operating time, setting error, influence of
voltage, influence of temperature, and OFF time characteristic
are used to express the precision of the Timer. Any of these
items may be ignored depending on the particular
specifications of the model.
The Motor Timer and Electric Timer indicate these items by
percentage values. The Count Timer indicates these items by
differential time values because the differential range of the
Timer's operating time is essentially constant due to operating
principles of the Timer. Furthermore, the total error can be
indicated to express all these items in the case of the Count
Timer.
The range of shock in which there is no damage to parts
during transport or use, and the operating characteristics are
still satisfied.
Motion / Drives
TM3: Average value of operating times measured with a 1-second OFF time.
TMx3: Average value of operating times measured with an OFF time that
causes the maximum deviation from TM3 within the specified OFF-time
range of one hour from the specified resetting time.
TMs: Maximum scale time (TMs is a set value in the case of a Digital Timer.)
Shock Resistance (Destruction)
Automation Systems
The change between the operating time for a given OFF time
and the operating time when the OFF time is changed.
Formula for calculation:
OFF time characteristic
TMx3−TM3
=±
×100 (%)
TMs
The range of shock during operation in which contacts that are
closed will not open by shock for at least the specified time (1
ms).
Control Components
where,
TM2: Average value of operating times measured at 20°C.
TMx2: Average value of operating times measured at the temperature that
causes the largest deviation from TM2 within the ambient operating temperature range.
TMs: Maximum scale time (TMs is a set value in the case of a Digital Timer.)
Shock Resistance (Malfunction)
Relays
The change in the operating time when the ambient
temperature changes within the ambient operating
temperature range.
Formula for calculation:
Variation due to temperature change
TMx2−TM2
=±
×100 (%)
TMs
The range of vibration in which there is no damage to parts
during transport or use, and the operating characteristics are
still satisfied.
Safety Components
Influence of Temperature
Vibration Resistance (Destruction)
Switches
where,
TM1: Average value of operating times measured at rated power supply voltage
TMx1: Average value of operating times measured at the voltage that causes
the largest deviation from TM1 within the allowable voltage range.
TMs: Maximum scale time (TMs is a set value in the case of a Digital Timer.)
Sensors
Influence of Voltage
Electrical Life Expectancy
Others
The life expectancy of a Timer when the control output of the
Timer is operated to switch the specified voltage/current load
connected to the control output.
The electrical or mechanical life of the Timer is generally
indicated by the operating times of the control output. The
electrical life is indicated by the operating times of the control
output connected to a load and the mechanical life is indicated
by the operating times of the control output with no load. The
electrical life is shorter than the mechanical life. The lighter the
load is, the longer the electrical life will be. Therefore, to
prolong the electrical life of the Timer, use the Timer to switch
heavy loads via relays instead of directly switching them with
the control output.
Common
8
Technical Explanation for Timers and Time Switches
Further Information
Symbols Used in Internal Connection Diagram
Symbol used in
catalogs
or
Name
Normally open contacts
(A pair of contacts
which are normally
open when no relay
input is applied.)
Time-limit
operation
, timelimit
resetting
contacts
Normally closed
contacts (A pair of
contacts which are
normally closed when
no relay input is
applied.)
or
Manually
operated,
automatic
resetting
contact
Symbol used in
catalogs
Symbol defined by
JIS
A
A
B
B
Description
A: NO contacts
B: NC contacts
A
A
B
B
Contacts that reset
when the operator
releases their hand.
These contacts are
used, for example, to
operate a pushbutton
switch. (Same for
pushbutton, pull, and
rotating switches.)
Safety Components
NC
contacts
Symbol
Description
Switches
NO
contacts
Symbol defined by
JIS
Sensors
Symbol
Name
A: NO contacts
B: NC contacts
A
A
B
B
A
A
MS
Relay
A: NO contacts
B: NC contacts
An electromagnetic
relay
X
LED
A: NO contacts
B: NC contacts
B
SM
X
Automation Systems
Time-limit
resetting
contacts
B
A miniature motor
which operates in
synchronization with
the power supply
frequency.
Control Components
Time-limit
operating
contacts
A
Synchron
ous motor
Relays
Transfer
contacts
Transfer contacts (NO
and NC contacts that
have a common contact
terminal are collectively
called "transfer
contacts".)
The contacts shown in
A and B are all transfer
contacts. The NC
contact is either on the
right side or on the
upper side.
Used to indicate the
operating status of the
Timer.
B
Motion / Drives
Energy Conservation Support /
Environment Measure Equipment
Power Supplies /
In Addition
Others
Common
9
Technical Explanation for Timers and Time Switches
Inrush Currents for Timers and Time Switches
Sensors
“---” indicates a constant current and therefore the corresponding values are omitted from the table. All the values are approximate
values and should therefore only be used as a guide.
Timers (Major Models)
Voltage
Applied
voltage
Inrush
current
(peak
value)
Time
(see
note) *
H3CA-A series
264 VAC
1.6 A
0.6 ms
200/220/240 VAC
264 VAC
1.5 A
0.6 ms
100/110/120 VAC
132 VAC
780 mA
5 ms
24 VDC
---
---
---
200/220/240 VAC
264 VAC
1.6 A
1.6 ms
100/110/120 VAC
132 VAC
1.5 A
5 ms
24 VDC
26.4 VDC
1.2 A
2 ms
100 to 240 VAC or
100 to 125 VDC
264 VAC
780 mA
1.8 ms
137.5 VDC
310 mA
3.2 ms
24 to 48 VAC or
12 to 48 VDC
26.4 VAC
830 mA
2.4 ms
26.4 VDC
570 mA
6.3 ms
100 to 240 VAC or
100 to 125 VDC
264 VAC
1.76 A
0.1 ms
137.5 VDC
550 mA
0.2 ms
26.4 VAC
270 mA
35 ms
26.4 VDC
270 mA
31 ms
24 to 48 VAC or
12 to 48 VDC
26.4 VAC
370 mA
2.2 ms
26.4 VDC
250 mA
3.2 ms
100 to 240 VAC or
100 to 125 VDC
264 VAC
750 mA
1 ms
137.5 VDC
0.5 A
9.1 ms
24 to 48 VAC or
12 to 48 VDC
26.4 VAC
0.83 A
10 ms
26.4 VDC
0.57 A
9.4 ms
100/110/120 VAC
132 VAC
1.05 A
111 ms
200/220/240 VAC
264 VAC
1.07 A
119 ms
26.4 VAC
1.26 A
133 ms
26.4 VDC
0.85 A
137 ms
H3CA-8/-8-306
H3CA-8H/-8H-306
H3CR-A/-A8/-AP
H3CR-A8E
24 to 48 VAC/DC
H3CR-AS/-A8S
H3CR-F
S
series
H3CR-H
24 VDC
Approx.
0.168 A
134 ms
264 VDC
Approx.
3.64 A
46 ms
12 VDC
13.2 VDC
Approx.
2.62 A
418.67 ms
100 to 120 VAC
132A
Approx.
2.06 A
1320 μs
200 to 240 VAC
264 VAC
Approx.
2.38 A
677.33 μs
52.8 VAC
Approx.
1.81 A
1810 μs
24 VAC
Approx.
1.68 A
19.8 ms
24 VDC
Approx.
1.16 A
35.2 ms
52.8 VDC
Approx.
2.44 A
8.84 ms
253 VAC
3A
1 ms
26.4 VDC
0.5 A
4 ms
264 VAC
7.04 A
500 μs
24 to 240 VAC/DC
H3DK-M/S/F/G
H3DK-H
24 to 48 VAC/DC
H3DS
H3DT-N/L/A/F/G
24 to 230 VAC or
24 to 48 VDC
24 to 240 VAC/DC
24 VDC
336 mA
5.36 ms
264 VDC
4.92 A
704 μs
100 to 120 VAC
132 VAC
2.08 A
21.6 μs
200 to 240 VAC
264 VAC
4.08 A
23.2 μs
52.8 VAC
1.09 A
19.2 μs
H3DT-H
24 to 48 VAC/DC
24 VDC
668 mA
63.2 ms
52.8 VDC
1.96 A
15.2 ms
0.01 ms
52.8 VDC
0.73 A
112 ms
24 VDC
26.4 VDC
1.8 A
100 to 125 VDC
137.5 VDC
0.62 A
109 ms
12 VDC
13.2 VDC
1.5 A
0.01 ms
100/110/120 VAC
132 VAC
1.02 A
364 ms
6 VDC
6.6 VDC
1.1 A
0.05 ms
200/220/240 VAC
264 VAC
1.03 A
323 ms
5 VDC
5.5 VDC
1.1 A
0.05 ms
26.4 VAC
1.21 A
478 ms
24 VDC
26.2 VDC
1.8 A
0.01 ms
24 VAC/DC
100 to 125 VDC
24 to 230 VAC/DC
1.5 A
0.01 ms
6.6 VDC
1.1 A
0.05 ms
380 ms
5 VDC
5.5 VDC
1.1 A
0.05 ms
0.03 ms
200/220/240 VAC
264 VAC
1.2 A
0.5 ms
100/110/120 VAC
132 VAC
620 mA
0.4 ms
110 VDC
---
---
---
100 VDC
---
---
---
48 VDC
52.8 VDC
5A
1 ms
24 VDC
26.4 VDC
2.6 A
1 ms
12 VDC
13.2 VDC
1.3 A
1 ms
All specifications
except for 24 VAC
---
---
---
24 VAC
26.4 VAC
200 mA
3 ms
All specifications
except for 12 VDC
---
---
---
12 VDC
13.2 VDC
350 mA
0.4 ms
All specifications
except for 12 VDC
---
---
---
12 VDC
13.2 VDC
600 mA
1 ms
560 ms
0.71 A
384 ms
137.5 VDC
0.62 A
253 VAC
4.4 A
253 VDC
2.68 A
0.03 ms
26.4 VDC
203 mA
11 ms
200 to 230 VAC
200 VAC
Approx.
0.8 A
130 ms
100 to 120 VAC
100 VAC
Approx.
0.93 A
130 ms
48 VAC
Approx.
0.95 A
130 ms
48 VDC
Approx.
0.68 A
70 ms
24 VAC
Approx.
1.25 A
140 ms
24 VDC
Approx.
0.89 A
40 ms
24 VAC/DC
H3FA-SA
H3M series
H3RN series
H3Y series
H3YN series
Common
13.2 VDC
6 VDC
0.87 A
52.8 VDC
Others
12 VDC
26.4 VDC
48 VAC/DC
H3FA-A
Power Supplies /
In Addition
H3DE-H
46.27 ms
48 VDC
48 VDC
H3DE-MS/F/G
Approx.
4.69 A
Energy Conservation Support /
Environment Measure Equipment
M
series
24 VAC/DC
264 VAC
Motion / Drives
1.7 ms
Automation Systems
2.74 A
Time
(see
note) *
Control Components
264 VAC
24 to 240 VAC or
12 to 240 VDC
Inrush
current
(peak
value)
Relays
100 to 240 VAC
Applied
voltage
Voltage
Safety Components
H3AM-NS/-NSR
Model or series
Switches
Model or series
10
Technical Explanation for Timers and Time Switches
Time
(see
note) *
23 A
1 ms
110 VDC
8A
2 ms
12 to 24 V DC
26.4 VDC
15 A
6.5 ms
100 to 240 VAC
264 VAC
800 mA
12 to 48 VDC
52.8 VDC
400 mA
H5CX-A@-N
series
100 to 240 VAC
264 VAC
4.8 A
0.5 ms
H5CX-A@D-N
series
24 VAC or
12 to 24 VDC
26.4 VAC
9.5 A
1 ms
26.4 VDC
6.6 A
1 ms
H5CN series
H5CX-L@-N
series
H5CX-B@-N
series
4.8 A
1.1 ms
1 ms
240 VAC
0.7 A
0.5 ms
1 ms
H5L-A
5.3 A
0.4 ms
24 VAC or
12 to 25 VDC
6.4 A
1.4 ms
26.4 VDC
4.4 A
1.7 ms
4.4 A
1.7 ms
5.3 A
0.4 ms
6.4 A
1.4 ms
26.4 VDC
4.4 A
1.7 ms
H5CX-B series
12 to 24 V DC
(previous models)
26.4 VDC
6A
1.2 ms
100 to 240 VAC
264 VAC
4.6 A
0.4 ms
24 VAC or
12 to 24 VDC
26.4 VAC
9.5 A
1 ms
26.4 VDC
6.6 A
1 ms
---
---
---
100 to 240 VAC
264 VAC
3.1 A
0.2 ms
24 VDC
26.4 VDC
1.3 A
2.7 ms
100 to 240 VAC
264 VAC
3.1 A
0.2 ms
24 VDC
26.4 VDC
1.4 A
2.7 ms
100 to 240 VAC
H5S series
(previous models) 24 VDC
264 VAC
2.5 A
0.3 ms
26.4 VDC
1.1 A
3 ms
H5F series
264 VAC
2A
0.3 ms
H5S-W series
H5S-Y series
100 to 240 VAC
* The time of the inrush current is measured in the range shown in the following
waveform.
100%
(Peak Value)
30%
Measurement time
Time
Control Components
264 VAC
26.4 VAC
All specifications
Relays
100 to 240 VAC
H5CX-A/-L series
24
VAC or
(previous models)
12 to 24 VDC
H5CZ series
Time
(see
note) *
240 VAC
264 VAC
26.4 VDC
Inrush
current
(peak
value)
100 to 200 VAC
26.4 VAC
12 to 24 VDC
Applied
voltage
H4KV-DSA
100 to 200 VAC
(previous models)
100 to 240 VAC
H4KV-DSA-R
Voltage
Safety Components
264 VAC
100 VDC
Model or series
Switches
100 to 240 VAC
H5AN series
Time Switches (Major Models)
Inrush current
Voltage
Inrush
current
(peak
value)
Sensors
Model or series
Applied
voltage
Automation Systems
Motion / Drives
Energy Conservation Support /
Environment Measure Equipment
Power Supplies /
In Addition
Others
Common
11
Technical Explanation for Timers and Time Switches
Troubleshooting
Problem
The inrush current when the power supply voltage was
applied may have damaged the sensor output.
The top part of the display on a Timer
with a memory backup is missing.
If the power supply is not connected and power is
interrupted for 10 minutes or longer, the measured
value or display will not be dependable and
unnecessary outputs may appear.
Always connect a battery when you use a Timer with a
memory backup. If the battery voltage is 3 V, you can
use various type of batteries.
The memory backup time will depend on the capacity
of the battery.
Timers
Switches
Solution
Use an MY or other relay to turn the power supply to the
Timer ON/OFF.
(Use a suitable contact capacity.)
Sensors
Probable cause
A sensor was used to turn the power
supply to the Timer ON and OFF, but
the sensor output was damaged.
Safety Components
Relays
Control Components
Automation Systems
Motion / Drives
Energy Conservation Support /
Environment Measure Equipment
Power Supplies /
In Addition
Others
Common
12