TRU Design Aids 2

DESIGN AIDS 2
CONDUCTOR
INSULATED WIRE TEMPERATURE RATING (AMPS)
AWG
Diameter
50°C
80°C
90°C
105°C
125°C
150°C
200°C
250°C
30
0.0124
1.3
2.0
2.0
3.0
3.5
4.3
4.8
5.9
28
0.0146
2.0
3.0
3.0
4.0
4.5
5.5
6.3
8.0
26
0.0188
3.0
4.0
4.0
5.0
6.0
7.0
9.0
11
24
0.0235
4.5
5.5
5.5
7.0
8.5
10
12
14
22
0.0296
6.0
7.5
7.5
10
11
13
16
20
20
0.0376
8.0
10
10
13
14
18
22
27
18
0.0403
11
14
14
18
19
25
30
36
16
0.0531
16
19
19
24
26
34
38
45
14
0.0667
22
27
27
33
37
45
50
57
12
0.0856
30
36
36
45
50
60
65
75
10
0.1080
40
47
47
58
65
80
90
100
8
0.1610
60
65
65
80
90
105
125
145
6
0.2020
80
95
95
110
125
145
165
205
4
0.2550
105
125
125
155
170
190
220
270
2
0.3310
135
160
160
200
220
240
280
350
1
0.3670
165
195
195
245
270
290
340
430
1/0
0.4160
195
230
230
290
320
340
400
510
2/0
0.4690
225
260
260
330
370
390
465
590
Chart approximates the current carrying capacity of a single 19-strand copper conductor in free air at 30° ambient temperature.
STANDARD FREQUENCY DESIGNATIONS
HF
3 MHz - 30 MHz
VHF
30 MHz - 300 MHz
UHF
300 MHz - 1 GHz
L
1 GHz - 2 GHz
S
RECOMMENDED TORQUE VALUES
Connector
Type
Torque Nominal
Value (in-lbs)
Connector
Type
Torque Nominal
Value (in-lbs)
1.85 mm
7
N
23
SMA
9
SC
23
2.4 mm
9
HN
24
2 GHz - 4 GHz
2.9 mm
9
MEIA™-875
70
C
4 GHz - 8 GHz
3.5 mm
9
LC/LT
75
X
8 GHz - 12 GHz
7 mm
9
MEIA™-1625
165
ATNC
23
7-16
246
Ku
12 GHz - 18 GHz
TNC
23
K
18 GHz - 27 GHz
Ka
27 GHz - 40 GHz
mm
40 GHz - 100 GHz
TRU Corporation
245 Lynnfield Street, Peabody, MA 01960 1-800-COAX-TRU (1-800-262-9878)
www.trucorporation.com