Download

CJ-Series Analog I/O Unit
CJ1W-AD/DA/MAD
CSM_CJ1W-AD_DA_MAD_DS_E_5_1
Consistent Microsecond Throughput:
Models with Direct Conversion Join
the Lineup
• Analog Input Units for converting analog input signals into
binary data
• Analog Output Units for converting binary data into analog
output signals
CJ1W-AD042
CJ1W-DA042V
Features
Analog Input Units
• Input up to eight analog signals with one Unit.
• Functions include line disconnection detection, averaging, peak value holding, offset/gain adjustment, and scaling.
(Offset/gain adjustment is not supported by the CJ1W-AD042. Scaling is supported only by the CJ1W-AD042.)
• High-speed A/D conversion in 20 μs/point with direct conversion function * (CJ1W-AD042 only).
Analog Output Units
• Output up to eight analog signals with one Unit.
• Functions include output holding, offset/gain adjustment, and scaling. (Offset/gain adjustment is not supported by the CJ1W-DA042V. Scaling
is supported only by the CJ1W-DA08V/DA08C/DA042V.)
• High-speed D/A conversion in 20 μs/point with direct conversion function * (CJ1W-DA042V only).
Analog I/O Units
• Input up to four analog signals and output up to two analog signals with one Unit.
• Functions include line disconnection detection, input averaging, scaling, input peak value holding, output holding, ratio conversion, and offset/
gain adjustment.
* Direct Conversion Instructions for High-speed type can be used to create a consistent response time from input through data processing and
output. With the Machine Automation Controller NJ-series, the direct conversion function cannot be used. This function is supported only by the
CJ-series CPU Unit.
System Configuration
Analog Input Unit
CPU Unit
Analog Output Unit
RUN
ERR/ALM
INH
PROGRAMMABLE
PRPHL
CONTROLLER
COMM
SYSMAC
CJ1G-CPU44
AD081-V1
RUN
ERC
ERH
ADJ
B1
DA041
RUN
ERC
ERH
ADJ
A1
B1
A1
OPEN
MCPWR
BUSY
MACH
MACH
No.
1
x10
No.
1
x10
x10
0
x10
0
PERIHERAL
1 2
1 2
MODE
MODE
PORT
Sensor
Temperature
Pressure
Speed
Flow rate
Regulator
(Temperature control)
Preamp
Servocontroller
M
(Position control)
Voltage
Current
Power
Power factor
Transducer
Variable speed
controller
M
(Speed control)
Chart recorder
Sensor
Note: The above diagram is an installation example for the CJ1W-AD081-V1 Analog Input Units and CJ1W-DA041 Analog Output Units.
1
CJ1W-AD/DA/MAD
Ordering Information
International Standards
• The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus,
UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
• Contact your OMRON representative for further details and applicable conditions for these standards.
Analog Input Units
Unit type
Product
name
I/O
points
Signal
range
selection
Analog
Input
Unit
High-speed type
CJ1
Special
I/O Units
Analog
Input
Units
4
inputs
8
inputs
Set
separately
for each
input
Signal
range
Resolution
1 to 5 V (1/10,000),
0 to 10 V (1/20,000),
-5 to 5 V (1/20,000),
-10 to 10 V (1/40,000),
and
4 to 20 mA (1/10,000)
1 to 5 V,
0 to 5 V,
0 to 10 V,
-10 to 10 V,
4 to 20
mA
4
inputs
Conversion
period
20 μs/1 point,
25 μs/2 points,
30 μs/3 points,
35 μs/4 points
The Direct
conversion
is provided.
*1
Accuracy at
ambient
temperature
of 25°C
Current
No. of
consumption
External
unit
(A)
connection numbers
allocated 5 V 24 V
Voltage:
±0.2% of
F.S.
Current:
±0.4% of
F.S.
0.52
Removable
terminal
block
---
Model
CJ1W-AD042
Standards
UC1, CE
1
CJ1W-AD081-V1
1/4,000
(Settable
to
1/8,000)
*2
1 ms/point
(250 μs/point
can also be
set.)
*2
Voltage:
±0.2% of F.S.
Current:
±0.4% of F.S.
*3
0.42
UC1, N,
L, CE
--CJ1W-AD041-V1
*1 With the Machine Automation Controller NJ-series, the direct conversion function using the AIDC instruction cannot be used.
*2 The resolution and conversion speed cannot be set independently. If the resolution is set to 1/4,000, then the conversion speed will be 1 ms/
point.
*3 At 23 ±2°C
Analog Output Units
Unit type
Product
name
I/O
points
Signal
range
selection
Signal
range
Accuracy at
No. of
External
ambient
unit
Conversion
External
Resolution
power
temperature connection
numbers
period
supply
of 25°C
allocated
Analog
Output
Unit
High-speed type
CJ1
Special
I/O Units
Analog
Output
Units
4
outputs
1 to 5 V (1/10,000),
0 to 10 V (1/20,000),
and
−10 to 10 V (1/40,000)
1 to 5 V,
8
0 to 5 V,
Set
outputs separately 0 to 10 V, 1/4,000
for each −10 to 10 V (Settable
to
output
1/8,000)
*2
8
4 to 20
outputs
mA
20 μs/
1 point,
25 μs/
2 points,
30 μs/
3 points,
35 μs/
4 points
The Direct
conversion is
provided.
*1
±0.3% of
F.S.
---
Current
consumption
(A)
5V
24 V
0.40
---
Model
Standards
CJ1W-DA042V UC1, CE
24 VDC
+10%
1 ms/point
(Settable
±0.3% of
to 250 μs/
F.S.
point)
*2
−15% ,
Removable
140 mA 1
terminal
max.
block
24 VDC
0.14
*3
CJ1W-DA08V
UC1, N,
L, CE
0.17
*3
CJ1W-DA08C
UC1, N,
CE
0.2
*3
CJ1W-DA041
0.14
+10%
−15%
,
170 mA
max.
24 VDC
4
outputs
2
outputs
1 to 5 V,
0 to 5 V,
0 to 10 V, 1/4,000
−10 to 10 V,
4 to 20 mA
1 ms/
point
Voltage:
±0.3% of
F.S.
Current:
±0.5% of
F.S.
+10%
−15%
,
200 mA
max.
24 VDC
+10%
−15%
,
140 mA
max.
UC1, N,
L, CE
0.12
0.14
*3
CJ1W-DA021
*1 With the Machine Automation Controller NJ-series, the direct conversion function using the AIDC instruction cannot be used.
*2 The resolution and conversion speed cannot be set independently. If the resolution is set to 1/4,000, the conversion speed will be 1 ms/point.
*3 This is for an external power supply, and not for internal current consumption.
2
CJ1W-AD/DA/MAD
Analog I/O Units
Product
name
I/O
points
Analog
I/O
Units
4
inputs
Unit type
CJ1
Special
I/O Units
2
outputs
Signal
range
selection
Set
separately
for each
input and
output
Signal
range
1 to 5 V,
0 to 5 V,
0 to 10 V,
−10 to 10 V,
4 to 20 mA
Accuracy at
Conversion
ambient
Resolution
period
temperature
of 25°C
1/4,000
(Settable
to
1/8,000)
External
connection
Voltage:
±0.2% of F.S.
1 ms/
Current:
point
±0.2% of F.S. Removable
(Settable
terminal
to 500 μs/ Voltage:
block
±0.3% of F.S.
point)
Current:
±0.3% of F.S.
Current
No. of
consumption
unit
(A)
numbers
allocated 5 V
24 V
1
0.58
−
Model
Standards
CJ1W-MAD42
UC1, N,
L, CE
Note: The resolution and conversion speed cannot be set independently. If the resolution is set to 1/4,000, then the conversion speed will be 1
ms/point.
Accessories
Model
Accessories
CJ1W-AD081-V1/AD041-V1
CJ1W-DA08V/DA08C/DA041/DA021
CJ1W-DA042V
CJ1W-MAD42
None.
CJ1W-AD042
Four jumpers
(For a current input, a jumper is used to connect the current input positive terminal and the voltage input positive terminal.)
Mountable Racks
NJ system
Model
CJ1W-AD042
CJ system (CJ1, CJ2)
CPU Rack
Expansion Rack
CPU Rack
Expansion
Backplane
7 Units *4
10 Units *5
(per Expansion
Rack)
8 Units *1
9 Units *2
(per Expansion
Backplane)
9 Units *4
10 Units *5
(per Expansion
Rack)
10 Units *1
10 Units *2
(per Expansion
Backplane)
7 Units *1
8 Units *2
(per Expansion
Backplane)
CJ1W-AD081-V1
CJ1W-AD041-V1
CJ1W-DA042V
CJ1W-DA08V
CJ1W-DA08C
10 Units *4
10 Units *5
(per Expansion
Rack)
7 Units *4
10 Units *5
(per Expansion
Rack)
CJ1W-DA041
CP1H system
CP1H PLC
NSJ system
NSJ Controller
Expansion
Backplane
9 Units *2
(per Expansion
Backplane)
2 Units *3
Not supported
10 Units *2
(per Expansion
Backplane)
CJ1W-DA021
CJ1W-MAD42
8 Units *2
(per Expansion
Backplane)
Note: It may not be possible to mount this many Units to a Rack depending on the current consumption of the other Units.
*1 This is the number of Units for a CJ2H-CPU6@ CJ2H CPU Unit (without EtherNet/IP) and a CJ1W-PA205@ or CJ1W-PD025 Power Supply Unit.
*2 This is the number of Units for a CJ1W-PA205@ or CJ1W-PD025 Power Supply Unit.
*3 A CP1W-EXT01 CJ Unit Adaptor is required.
*4 This is the number of Units for a NJ501 CPU Unit, and a NJ-PA3001 or NJ-PD3001 Power Supply Unit.
*5 This is the number of Units for a NJ-PA3001 or NJ-PD3001 Power Supply Unit.
3
CJ1W-AD/DA/MAD
Individual Specifications
Analog Input Units CJ1W-AD041-V1/AD081-V1/AD042
Specifications
Item
CJ1W-AD041-V1
CJ1W-AD081-V1
Unit type
CJ-series Special I/O Unit
Isolation *1
Between I/O and Controller signals: Photocoupler
(No isolation between I/O signals.)
External terminals
18-point detachable terminal block (M3 screws)
Power consumption
420 mA max. at 5 VDC
Dimensions (mm)
31 × 90 × 65 mm (W × H × D)
Weight
140 g max.
General specifications
Conforms to general specifications for CJ Series.
Number of analog inputs
4
Input signal range *2
1 to 5 V
0 to 5 V
0 to 10 V
−10 to 10 V
4 to 20 mA
*3
Maximum rated input
(for 1 point) *5
Voltage Input: ±15 V
Current Input: ±30 mA
Input impedance
Voltage Input: 1 MΩ min.
150 g max.
8
Accuracy *7
Current Input: 250 Ω (rated value)
1 to 5 V
10,000
0 to 10 V
20,000
−5 to 5 V
20,000
−10 to 10 V
40,000
4 to 20 mA
10,000
16-bit binary data
25°C *8
Voltage Input: ±0.2% of F.S.Current Input: ±0.4% of F.S.
0°C to 55°C
Voltage Input: ±0.4% of F.S.Current Input: ±0.6% of F.S.
A/D conversion period *9
1 ms/250 μs per point *6
20 μs/1 point, 25 μs/2 points,
30 μs/3 points, 35 μs/4 points
Mean value processing
Stores the last "n" data conversions in the buffer, and stores the mean value
of the conversion values.
Buffer number: n = 2, 4, 8, 16, 32, 64
Stores the last "n" data conversions
in the buffer, and stores the mean
value of the conversion values.
Buffer number:
n = 2, 4, 8, 16, 32, 64, 128, 256, 512
Peak value holding
Stores the maximum conversion value while the Peak Value Hold Bit is ON.
Scaling
Input
functions
4
1 to 5 V
0 to 10 V
−5 to 5 V
−10 to 10 V
4 to 20 mA
*4
4,000/8,000 *6
Converted output data
Between I/O and Controller signals:
Digital isolator (No isolation between
I/O signals.)
520 mA max. at 5 VDC
Input
specifications
Resolution
CJ1W-AD042
---
Setting values in any specified unit
within a range of ±32,000 as the upper
and lower limits allows A/D conversion to
be executed and analog signals to be
output with these values as full scale.
Input disconnection detection
Detects the disconnection and turns ON the Disconnection Detection Flag. *10
Offset/gain adjustment
Supported
Direct conversion
---
---
A/D conversion is performed and the
converted value is refreshed when
the ANALOG INPUT DIRECT CONVERSION instruction (AIDC) is executed. This instruction is supported
by the CJ2H-CPU@@ (-EIP) CPU
Units with unit version 1.1 or later,
and CJ2M-CPU@@.
CJ1, NJ501, and CP1H CPU Units
and NSJ Controllers do not support
direct conversion.
*1 Do not apply a voltage higher than 600 V to the terminal block when performing withstand voltage test on this Unit. Otherwise, internal elements
may deteriorate.
*2 Input signal ranges can be set for each input.
*3 Voltage input or current input are chosen by using the voltage/current switch at the back of the terminal block.
*4 To use a current input, connect the positive current input terminal and positive voltage input terminal with the enclosed short bar.
*5 The Analog Input Unit must be operated according to the input specifications provided here. Operating the Unit outside these specifications
will cause the Unit to malfunction.
*6 The resolution can be set to 8,000 and the conversion period to 250 μs in the setting. There is only one setting for both of these, i.e., they are
both enabled or disabled together.
*7 The accuracy is given for full scale. For example, an accuracy of ±0.2% means a maximum error of ±8 (BCD) at a resolution of 4,000.
For the CJ1W-AD041-V1/ AD081-V1, the default setting is adjusted for voltage input. To use current input, perform the offset and gain
adjustments as required.
*8 For the CJ1W-AD041-V1/ AD081-V1, 23±2°C.
*9 The A/D conversion period is the time required from when the Analog Input Unit receives the analog signal until it stores the converted value
in internal memory. It takes at least one cycle for the converted data to be stored in the CPU Unit. (The direct conversion function of the CJ1WAD042 is can be used to input data immediately to the CPU Unit.)
*10 Line disconnection detection is supported only when the range is set to 1 to 5 V or 4 to 20 mA. If there is no input signal when the 1 to 5 V or
4 to 20 mA range is set, the Line Disconnection Flag will turn ON.
4
CJ1W-AD/DA/MAD
Analog Output Units CJ1W-DA021/DA041/DA08V/DA08C/DA042V
Specifications
Item
CJ1W-DA021
CJ1W-DA041
CJ1W-DA08V
CJ1W-DA08C
Unit type
CJ-series Special I/O Unit
Isolation *1
Between I/O and Controller signals: Photocoupler (No isolation between I/O signals.)
External terminals
18-point detachable terminal block (M3 screws)
Power consumption
5 VDC, 120 mA max.
5 VDC, 140 mA max.
CJ1W-DA042V
Between I/O and Controller signals: Digital isolator (No isolation between I/O signals.)
5 VDC, 400 mA max.
+10%
24 VDC −15% (inrush current: 20 A max., pulse width: 1 ms min.)
External power supply *2
140 mA max.
200 mA max.
Dimensions (mm)
31 × 90 × 65 mm (W × H × D)
Weight
150 g max.
General specifications
---
8
8
4
Output signal range *3
1 to 5 V/4 to 20 mA
0 to 5 V
0 to 10 V
−10 to 10 V
1 to 5 V
0 to 5 V
0 to 10 V
−10 to 10 V
4 to 20 mA
1 to 5 V
0 to 10 V
−10 to 10 V
Output impedance
0.5 Ω max. (for voltage output)
0.5 Ω max.
(for voltage output)
---
0.5 Ω max.
(for voltage output)
Max. output current (for 1
point)
12 mA (for voltage output)
2.4 mA
(for voltage output)
---
2 mA
(for voltage output)
Maximum permissible
load resistance
600 Ω (current output)
Resolution
4,000
Set data
Accuracy
*4
4
---
350 Ω
4,000/8,000 *8
--1 to 5 V
10,000
0 to 10 V
20,000
-10 to 10 V
40,000
16-bit binary data
25°C
Voltage output: ±0.3% of F.S.
Current output: ±0.5% of F.S.
±0.3% of F.S.
±0.3% of F.S.
0°C to 55°C
Voltage output: ±0.5% of F.S.
Current output: ±0.8% of F.S.
±0.5% of F.S.
±0.6% of F.S.
1.0 ms or 250 μs per point *8
±0.3% of F.S.
±0.5% of F.S.
20 μs/1 point,
25 μs/2 points,
30 μs/3 points,
35 μs/4 points
D/A conversion period *5
1.0 ms per point
Output hold function
Outputs the specified output status (CLR, HOLD, or MAX) under any of the following circumstances.
• When the Conversion Enable Bit is OFF. *6
• In adjustment mode, when a value other than the output number is output during adjustment. *7
• When output setting value error occurs or Controller operation stops.
• When the Load is OFF.
Scaling
Output
functions
--170 mA max.
Conforms to general specifications for CJ-series Series.
Number of analog outputs 2
Output
specifications
140 mA max.
---
Offset/gain adjustment
Supported only for a conversion period of
1 ms and resolution of 4,000.
Setting values in any specified unit within a
range of ±32,000 as the upper and lower
limits allows D/A conversion to be executed and analog signals to be output with
these values as full scale.
Supported
Direct conversion
Setting values in any specified
unit within a range of ±32,000
as the upper and lower limits
allows D/A conversion to be
executed and analog signals to
be output with these values as
full scale.
---
---
D/A conversion is performed
and the output value is refreshed when the ANALOG
OUTPUT DIRECT CONVERSION instruction (AODC) is executed. This instruction is
supported by the CJ2HCPU@@ (-EIP) CPU Units with
unit version 1.1 or later, and
CJ2M-CPU@@.
CJ1, NJ501, and CP1H CPU
Units and NSJ Controllers do
not support direct conversion.
*1 Do not apply a voltage higher than 600 V to the terminal block when performing withstand voltage test on this Unit.
*2 The maximum number of Analog Output Units that can be mounted to one Rack varies depending on the current consumption of the other
Units mounted to the Rack.
Select a 24 VDC power supply based on the surge current. The following OMRON external power supplies with a power rating of 50 W are
recommended.
Manufacturer
OMRON
Model number
Specifications
S8VS-06024
100 to 240 VAC, 60 W
S8VS-12024
100 to 240 VAC, 120 W
S8VM-05024
100 to 240 VAC, 50 W
S8VM-10024
100 to 240 VAC, 100 W
*3 Output signal ranges can be set for each output.
*4 The accuracy is given for full scale. For example, an accuracy of ±0.3% means a maximum error of ±60 mV for a −10 to 10 V range. For the
CJ1W-DA021/041, the accuracy is at the factory setting for a current output. When using a voltage output, adjust the offset gain as required.
5
CJ1W-AD/DA/MAD
*5 The D/A conversion period is the time required for the Analog Output Unit to convert and output the data that was received from the CPU Unit.
It takes at least one cycle for the data stored in the CPU Unit to be read by the Analog Output Unit. (The direct conversion function of the CJ1WDA042V can be used to output data immediately from the CPU Unit.)
*6 When the operation mode for the CPU Unit is changed from RUN mode or MONITOR mode to PROGRAM mode, or when the power is turned
ON, the Output Conversion Enable Bit will turn OFF. The output status specified according to the output hold function will be output.
*7 The CJ1W-DA042V does not have an Adjustment Mode.
*8 The CJ1W-DA08V/08C can be set to a conversion cycle of 250 μs and a resolution of 8,000 using the setting.
Analog I/O Unit CJ1W-MAD42
Specifications
Item
CJ1W-MAD42
Unit type
CJ-series Special I/O Unit
Isolation
Between I/O and Controller signals: Photocoupler
(No isolation between I/O signals.)
External terminals
18-point detachable terminal block (M3 screws)
Current consumption
580 mA max. at 5 V DC
Dimensions (mm)
31 × 90 × 65 mm (W × H × D)
Weight
150 g max.
General specifications
Conforms to general specifications for CJ-series Series.
Input Specifications and Functions
Item
Voltage input
Current input
Number of analog inputs
4
Input signal range *1
1 to 5 V
0 to 5 V
0 to 10 V
−10 to 10 V
4 to 20 mA *2
Maximum rated input (for 1
point) *3
±15 V
±30 mA
Input impedance
1 MΩ min.
250 Ω (rated value)
Resolution
4,000/8,000 *7
Converted output data
Accuracy *4
25°C
0°C to 55°C
16-bit binary data
±0.2% of F.S.
±0.4% of F.S.
A/D conversion period *5
1.0 ms/500 μs per point *7
Mean value processing
Stores the last "n" data conversions in the buffer, and stores the mean value of the conversion values.
Buffer number: n = 2, 4, 8, 16, 32, 64
Peak value holding
Stores the maximum conversion value while the Peak Value Hold Bit is ON.
Scaling
Enabled only for conversion period of 1 ms and resolution of 4,000. Setting any values within a range of
±32,000 as the upper and lower limits allows the A/D conversion result to be output with these values as full
scale.
Input disconnection detection Detects the disconnection and turns ON the Disconnection Detection Flag.
Offset/gain adjustment
Supported
6
CJ1W-AD/DA/MAD
Output Specifications
Item
Voltage output
Current output
Number of analog outputs
2
Output signal range *1
1 to 5 V
0 to 5 V
0 to 10 V
−10 to 10 V
4 to 20 mA
Output impedance
0.5 Ω max.
−
Maximum external output
current (for 1 point)
2.4 mA
−
Maximum allowed load
resistance
−
600 Ω
Resolution
4,000/8,000 *7
Set data
Accuracy *4
16-bit binary data
25°C
±0.3% of F.S.
±0.3% of F.S.
0°C to 55°C
±0.5% of F.S.
±0.6% of F.S.
D/A conversion period *5
1.0 ms/500 μs per point
Output hold function
Outputs the specified output status (CLR, HOLD, or MAX) under any of the following circumstances.
• When the Conversion Enable Bit is OFF. *6
• In adjustment mode, when a value other than the output number is output during adjustment.
• When output setting value error occurs or Controller operation stops.
• When the Load is OFF.
Scaling
Enabled only for conversion period or 1 ms and resolution of 4,000. Setting any values within a range of
±32,000 as the upper and lower limits allows D/A conversion to be executed and analog signals to be output
with these values as full scale.
Ratio conversion function *5
Stores the results of positive and negative gradient analog inputs calculated for ratio and bias as analog output
values.
Positive gradient: Analog output = A × Analog input + B
(A: 0 to 99.99, B: 8000 to 7FFF hex)
Negative gradient:Analog output = F − A × Analog input + B
(A: 0 to 99.99, B: 8000 to 7FFF hex, F: Output range maximum value)
Offset/gain adjustment
Supported
*1 Input and output signal ranges can be set for each input and output.
*2 Voltage input or current input are chosen by using the voltage/current switch at the back of the terminal block.
*3 The Analog I/O Unit must be operated according to the input specifications provided here. Operating the Unit outside these specifications will
cause the Unit to malfunction.
*4 The accuracy is given for full scale. For example, for an input, an accuracy of ±0.2% means a maximum error of ±8 (BCD) at a resolution of
4,000. For an output, an accuracy of ±0.3% means a maximum error of ±60 mV for a −10 to 10 V range.
*5 The A/D conversion period is the time required from when the Analog Input Unit receives the analog signal until it stores the converted value
in internal memory. It takes at least one cycle for the converted data to be stored in the CPU Unit.
The D/A conversion period is the time required for the Analog Output Unit to convert and output the data that was received from the CPU Unit.
It takes at least one cycle for the data stored in the CPU Unit to be read by the Analog Output Unit.
*6 When the operation mode for the CPU Unit is changed from RUN mode or MONITOR mode to PROGRAM mode, or when the power is turned
ON, the Output Conversion Enable Bit will turn OFF. The output status specified according to the output hold function will be output.
*7 By means of the setting, the resolution can be changed to 8,000, and the conversion period can be changed to 500 μs.
7
CJ1W-AD/DA/MAD
External Interface
Analog Input Units CJ1W-AD041-V1/AD081-V1/AD042
Components
Front
With Terminal Block
With Terminal Block Removed
Indicators *1
MACH
No.
x10 1
Terminal block
B1
A1
78
456
78
456
456
456
x10 0
Voltage/current
switch *2
23
ON
1
2
ON
1
2
23
901
x10 0
78
901
78
ON
1
x10 1
901
No.
RUN
ERC
ERH
ADJ
A1
23
MACH
B1
901
Unit number
setting switch
AD081-V1
23
RUN
ERC
ERH
ADJ
2
AD081-V1
O
N
O
N
ON
MODE
1
2
1 2
1 2
MODE
Terminal block
DIN Track
mounting pin
Operating mode switch *2
Side
Terminal block lock lever
(pull down to release terminal block)
Slider
Expansion connector
*1 The ADJ LED is not provided with the CJ1W-AD042.
*2 These switches are not mounted for the CJ1W-AD042.
Slider
Indicators
The indicators show the operating status of the Unit. The following table shows the meanings of the indicators.
LED
Meaning
RUN (green)
Operating
ERC (red)
Error detected by Unit
Indicator
Lit
Not lit
Lit
Not lit
ERH (red)
ADJ (yellow) *
Error in the CPU Unit
Adjusting
Lit
Not lit
Flashing
Not lit
Operating status
Operating in normal mode.
Unit has stopped exchanging data with the CPU Unit.
Alarm has occurred (such as disconnection detection) or initial
settings are incorrect.
Operating normally.
Error has occurred during data exchange with the CPU Unit.
Operating normally.
Operating in offset/gain adjustment mode.
Other than the above.
* The ADJ LED is not provided with the CJ1W-AD042.
8
CJ1W-AD/DA/MAD
Input Circuits
The following diagrams show the internal circuit of the analog input section.
CJ1W-AD041-V1/AD081-V1
15 kΩ
Input (+)
CJ1W-AD042
15 kΩ
250 Ω
1 MΩ
15 kΩ
15 kΩ
Input (–)
AG
(analog 0 V)
Input circuit
and
conversion
circuit
Voltage/
current
input switch
Current
Input (+)
250 Ω
Voltage
Input (+)
2.2 kΩ
Input circuit
and
conversion
circuit
510 kΩ
2.2 kΩ
Input (–)
1 MΩ
AG (common to all inputs)
510 kΩ
AG
(analog 0 V)
AG (common to all inputs)
Terminal Arrangement
The signal names corresponding to the connecting terminals are as shown in the following diagram.
CJ1W-AD041-V1
Input 2 (+)
CJ1W-AD081-V1
B1
A1
Input 2 (−)
B2
Input 4 (+)
B3
Input 4 (−)
B4
AG
B5
N.C.
B6
N.C.
B7
N.C.
B8
N.C.
B9
A2
A3
A4
A5
A6
A7
A8
Input 2 (+)
B1
Input 2 (−)
B2
Input 4 (+)
B3
Input 4 (−)
B4
AG
B5
Input 6 (+)
B6
Input 6 (−)
B7
Input 8 (+)
B8
Input 8 (−)
B9
Input 1 (+)
Input 1 (−)
Input 3 (+)
Input 3 (−)
AG
N.C.
N.C.
N.C.
A9
N.C.
A1
Current Input 1 (+)
A2
Voltage Input 1 (+)
A3
Input 1 (−)
A4
AG
A5
Current Input 3 (+)
A6
Voltage Input 3 (+)
A7
Input 3 (−)
A8
AG
A9
N.C.
A1
Input 1 (+)
A2
Input 1 (−)
A3
Input 3 (+)
A4
Input 3 (−)
A5
AG
A6
Input 5 (+)
A7
Input 5 (−)
A8
Input 7 (+)
A9
Input 7 (−)
CJ1W-AD042
Current Input 2 (+)
B1
Voltage Input 2 (+)
B2
Input 2 (−)
B3
AG
B4
Current Input 4 (+)
B5
Voltage Input 4 (+)
B6
Input 4 (−)
B7
AG
B8
N.C.
B9
Note: 1. Set the analog input number that you use and input signal range for each analog input, using the memory area or support software. The
input signal range can be set separately for each input number.
2. The AG terminals are connected to the 0 V analog circuit in the Unit. Connecting shielded input lines can improve noise resistance.
3. Do not connect anything to NC terminals.
4. To use a current input with the CJ1W-AD042, connect the positive current input terminal and positive voltage input terminal with the
enclosed short bar.
5. Connect a surge suppressor to inductive loads in the system (e.g., magnetic contactors, relays, and solenoids).
9
CJ1W-AD/DA/MAD
Analog Output Units CJ1W-DA021/041/08V/08C/DA042V
Components
Front
Side
Slider
With Terminal Block
Indicators *1
DA041
RUN
ERC
ERH
ADJ
x10 1
78
23
No.
456
MACH
A1
901
Unit number
switches
B1
901
456
78
23
x10 0
O
N
Expansion
connector
1 2
MODE
Terminal block
Terminal block lock lever
(pull down to release terminal block)
Slider
Operating mode switch
*2
DIN Track mounting pin
*1 The ADJ LED is not provided with the CJ1W-DA042V.
*2 This switch is not mounted for the CJ1W-DA08V, CJ1W-DA08C and CJ1W-DA042V.
Indicators
The indicators show the operating status of the Unit. The following table shows the meanings of the indicators.
LED
Meaning
RUN (green)
Operating
ERC (red)
Error detected by Unit
ERH (red)
ADJ (yellow) *
Error in the CPU Unit
Adjusting
Indicator
Lit
Not lit
Lit
Not lit
Lit
Not lit
Flashing
Not lit
Operating status
Operating in normal mode.
Unit has stopped exchanging data with the CPU Unit.
Alarm has occurred or initial settings are incorrect.
Operating normally.
Error has occurred during data exchange with the CPU Unit.
Operating normally.
Operating in offset/gain adjustment mode.
Other than the above.
* The ADJ LED is not provided with the CJ1W-DA042V.
10
CJ1W-AD/DA/MAD
Output Circuits
The following diagrams show the internal circuit of the analog output section.
CJ1W-DA021/DA041/DA08V/DA08C
Voltage Output Circuits
Current Output Circuits
Current output section
Voltage output section
Output
switch and
conversion
circuit
AMP
Voltage
output (+)
Voltage
output (–)
Output
switch and
conversion
circuit
Current
output (+)
AMP
AMP
Current
output (−)
AG (common to all outputs)
CJ1W-DA042V
Voltage Output Circuits
Output
switch and
conversion
circuit
AMP
Voltage
output (+)
Voltage
output (–)
AG (common to all outputs)
Terminal Arrangement
The signal names corresponding to the connecting terminals are as shown in the following diagram.
CJ1W-DA021
Voltage output 2 (+)
CJ1W-DA041
B1
A1
Output 2 (−)
B2
Current output 2 (+)
B3
N.C.
B4
N.C.
B5
N.C.
B6
A2
A3
A4
N.C.
B7
N.C.
B8
0V
B9
N.C.
Output 2 (−)
B2
Output 4 (+)
B3
Output 4 (−)
B4
A2
Output 6 (+)
B5
Output 6 (−)
B6
Output 8 (+)
B7
Output 8 (−)
B8
0V
B9
Output 4 (−)
B5
Current output 4 (+)
B6
N.C.
B7
N.C.
B8
0V
B9
Output 3 (−)
Output 2 (+)
B1
Output 2 (−)
B2
N.C.
B3
Output 4 (+)
B4
Output 4 (−)
B5
N.C.
B6
N.C.
B7
N.C.
B8
N.C.
B9
Output 5 (+)
Output 5 (−)
Output 7 (+)
A8
Output 7 (−)
A9
24 V
A1
Voltage output 1 (+)
A2
Output 1 (−)
A3
Current output 1 (+)
A4
Voltage output 3 (+)
A5
Output 3 (−)
A6
Current output 3 (+)
A7
N.C.
A8
N.C.
A9
24 V
A1
Output 1 (+)
A2
Output 1 (−)
A3
N.C.
A4
Output 3 (+)
A5
Output 3 (−)
A6
N.C.
A7
N.C.
A8
N.C.
A9
N.C.
CJ1W-DA042V
Output 1 (−)
Output 3 (+)
A7
B4
Output 1 (+)
A4
A6
Voltage output 4 (+)
24 V
A3
A5
B3
N.C.
B1
A1
Current output 2 (+)
N.C.
CJ1W-DA08V (Voltage Output)
and CJ1W-DA08C (Current Output)
Output 2 (+)
B2
N.C.
N.C.
A9
Output 2 (−)
Current output 1 (+)
A6
A8
B1
Output 1 (−)
A5
A7
Voltage output 2 (+)
Voltage output 1 (+)
Note: 1. Set the analog input number that you use and input signal range for each analog input, using the memory area or support software. The
input signal range can be set separately for each input number.
2. The N.C. terminals are not connected to internal circuit.
3. Use a separate power supply from the one used for Basic I/O Units. Faulty Unit operation may be caused by noise if power is supplied
from the same source. (This does not apply to CJ1W-DA042V.)
4. Connect a surge suppressor to inductive loads in the system (e.g., magnetic contactors, relays, and solenoids).
11
CJ1W-AD/DA/MAD
Analog I/O Unit CJ1W-MAD42
Components
Front
With Terminal Block
With Terminal Block Removed
Indicators
MAD42
MAD42
x10 1
78
456
x10 0
901
78
901
456
78
Voltage/current
switch
ON
1
2
ON
1
2
23
x10 0
A1
23
456
No.
456
MACH
78
Terminal block
B1
901
x10 1
901
No.
RUN
ERC
ERH
ADJ
A1
23
MACH
User
number
setting
switch
B1
23
RUN
ERC
ERH
ADJ
Terminal block
DIN Track
mounting pin
Terminal block lock lever
(pull down to release terminal bloc
Side
Slider
Expansion connector
Slider
Indicators
The indicators show the operating status of the Unit. The following table shows the meanings of the indicators.
LED
Meaning
RUN (green)
Operating
ERC (red)
Error detected by Unit
Indicator
Lit
Not lit
Lit
Not lit
ADJ (yellow)
ERH (red)
Adjusting
Error in the CPU Unit
Flashing
Not lit
Lit
Not lit
Operating status
Operating in normal mode.
Unit has stopped exchanging data with the CPU Unit.
Alarm has occurred (such as disconnection detection) or initial
settings are incorrect.
Operating normally.
Operating in offset/gain adjustment mode.
Other than the above.
Error has occurred during data exchange with the CPU Unit.
Operating normally.
12
CJ1W-AD/DA/MAD
I/O Circuit
The following diagrams show the internal circuit of the analog I/O section.
Input Circuits
15 kΩ
Input (+)
15 kΩ
250 Ω
1 MΩ
15 kΩ
15 kΩ
Input (–)
Voltage/
current
input switch
AG
(analog 0 V)
Input circuit
and
conversion
circuit
1 MΩ
AG (common to all inputs)
Voltage Output Circuits
Output
switch and
conversion
circuit
Current Output Circuits
AMP
Voltage
output (+)
Voltage
output (–)
AG (common to all outputs)
Output
switch and
conversion
circuit
AMP
AMP
Current
output (+)
Current
output (–)
Terminal Arrangement
The signal names corresponding to the connecting terminals are as shown in the following diagram.
CJ1W-MAD42
Voltage output 2 (+)
B1
Output 2 (–)
B2
Current output 2 (+)
B3
N.C.
B4
Input 2 (+)
B5
Input 2 (–)
B6
AG
B7
Input 4 (+)
B8
Input 4 (–)
B9
A1
Voltage output 1 (+)
A2
Output 1 (–)
A3
Current output 1 (+)
A4
N.C.
A5
Input 1 (+)
A6
Input 1 (–)
A7
AG
A8
Input 3 (+)
A9
Input 3 (–)
Note: 1. Set the analog input number that you use and input signal range for each analog input, using the memory area or support software. The
input signal range can be set separately for each input number.
2. The AG terminal (A7, B7) is connected to the 0 V analog circuit in the Unit. Connecting shielded input lines can improve noise resistance.
3. The N.C. terminals (A4, B4) are not connected to internal circuit.
Wiring Vasic I/O Units with Terminal Blocks
Crimp terminals
Use crimp terminals (M3) having the dimensions shown below.
6.2 mm max.
6.2 mm max.
13
CJ1W-AD/DA/MAD
Dimensions
(Unit: mm)
CJ1W-AD041-V1/081-V1/AD042
CJ1W-DA021/041/08V/08C/DA042V
CJ1W-MAD42
89
31
65
2.7
Terminal Block
Dimensions
17.5
8.2
AD081-V1
RUN
ERC
ERH
ADJ
B1
A1
6.4
78
456
x10 1
901
No.
7.62
23
MACH
901
23
x10 0
456
78
90
74.77
O
N
1 2
MODE
2.7
Note: The appearance varies with the model.
Related Manuals
Manual name
CJ-series Analog I/O
Units Operation Manual
for NJ-series CPU Unit
Cat. No.
W490
CS/CJ Series Analog I/O
W345
Units Operation Manual
Manual name
Application
Description
CJ1W-AD0@@-@@
CJ1W-DA0@@@
CJ1W-MAD42
Learning about the functions
and usage of CJseries Analog
Input Units, Analog Output
Units, and Analog I/O Units for
using them in an NJ-series
configuration.
The functions and usage of the CJseries Analog Input Units, Analog
Output Units, and Analog I/O Units for
using them in an NJ-series
configuration are described.
CS1W-AD041-V1/081-V1/161
CS1W-DA041/08V/08C
CS1W-MAD44
CJ1W-AD041-V1/081-V1/042
CJ1W-DA021/041/08V/08C/042V
CJ1W-MAD42
Learning about the functions
and usage of CJseries Analog
Input Units, Analog Output
Units, and Analog I/O Units.
The functions and usage of the CJseries Analog Input Units, Analog
Output Units, and Analog I/O Units for
using them in a CJ-series configuration
are described.
14
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2015.7
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2015 All Right Reserved.