© Siemens AG 2016 Flow Measurement SITRANS F US Inline SITRANS FUE950 energy calculator ■ Overview ■ Application The SITRANS FUE950 is able to handle 3 kinds of applications, means energy calculation in: • District heating applications • Chilled water applications • Combined cooling/heating applications Energy metering in heating, hot water applications (code "A" and "B") 3 s INFOCAL 5 SITRANS FUE950 is a universal thermal energy calculator, which meets the requirements EN 1434 and has the MID and PTB K7.2 approval for energy metering with the media water. SITRANS FUE950 has been developed for the SITRANS FUS380/ FUE380 and alternatively MAG 5000/6000 or FST020. SITRANS FUE950 is modular in construction and can by order be fitted with optional modules depending on the application. The FUE950 supports none of the SITRANS FX, FC products and only some of the FUS clamp-on products. Heat Energy metering in cooling, chilled water applications (code "C" and "D") s INFOCAL 5 ■ Benefits Basic functions • Prepared for heating, cooling measurement • Approval for MID for heat metering and PTB K7.2 for cooling • High-accuracy thermal energy metering, meets EN1434 requirements • Measured temperature range -20 … +190 °C (-4 … +374 °F) • Instantaneous values for energy/volume flow • Battery or mains powered • Battery version with battery lifetime of typically up to 10 years • Optical data interface • Real date and time • Auto-detection of 2-wire or 4-wire temperature sensors Additional functions • Individual tariff functions • Advanced functions for cooling/heating applications or the combination • Memory for 24 periods (months, weeks, days) • Data logger function • Expandable functionality with 2 optional plug and play add-on modules • Communication over M-Bus, RS 485 or RS 232 Add-on modules • Plug-in module with 2 extra pulse inputs • Plug-in module with 2 pulse outputs • Plug-in module with combination of input and output pulses • Plug-in module for M-Bus communication • Plug-in module for RS 232 or RS 485 communication • Plug-in module with 2 passive current outputs (4 ... 20 mA) 3/302 Siemens FI 01 · 2016 V2 V1 Cooling Energy metering in combined cooling/heating applications (code "E" and "F") s INFOCAL 5 Cooling 7+ 7& Heat © Siemens AG 2016 Flow Measurement SITRANS F US Inline SITRANS FUE950 energy calculator Data logger memory (LOG) ■ Design SITRANS FUE950 has an easy-read 8-digit LCD display with associated pictograms for the various functions. As the display has been made for several applications, some figures/symbols not used for normal district heating applications will be shown. SITRANS FUE950 has a push button for simple operation and provides user-friendly control via the various display menu loops. The display will always be configured for the application chosen, and for the selected display settings. The integrator has an IP54 plastic housing and is designed for wall or panel mounting. The housing comes with prepared rubber gaskets cable entries for fast and easy installation. The LOG of the calculator is stored every 24 hours with all cumulative values in the EEPROM. The storage frequency can be selected from various storage intervals (5, 6, 10, 12, 15, 20, 30, 60 minutes or the default setting of 24 hours). The data which are stored in the LOG could be read out using a software tool and can be used for evaluations. Extract of possible LOG settings Storage interval Values Number of Recording data records period 5 minutes • Error status • Overload time temperature • Overload time flow rate • Forward temperature • Return temperature • Date and time • Energy • Tariff energy 1 • Tariff energy 2 • Tariff definition 1 • Tariff definition 2 • Volume • Error day counter 440 36.6 hours 440 110 hours 440 18.3 days 440 440 days 15 minutes Operation menu loop structure 1 hour The FUE950 display has six menu loops and the menus are numbered in the display from 1 to 6. Some display menus consist of two values (to maximum seven) that are shown alternately at 4second intervals. 24 hours (default setting) The main menu loop no. 1 with the current data, e.g. for energy, volume, flow rate and temperature, is preprogrammed as default setting. In the combined heating/cooling configuration the menu loop no. 5 (tariff menu loop) will be activated additionally. Display and output pulses Units: MWh, GJ, Gcal, MBtu, m3, gal, m3/h, GPM, °C, °F and kW; all decimal points are statically (the unit "gal" is shown with factor x 100). The display unit and the last fractional digit are typical used for the pulse outputs. ■ Function Technical principle Calculation of energy is based on the following formula: Energy = Volume x (THot - TCold) x Kfactor (Ti) Volume: Volume [m3] of a given amount of volume pulses THot: Measured temperature in the hot line TCold: Measured temperature in the cold line Kfactor (Ti): Thermal coefficient of media enthalpy and heat content The energy calculation is made by a counter and depends on temperature difference, pulse input frequency and legal requirements. The calculator always carries out at least one energy calculation every 2 seconds. If the connected flowmeter has not sent enough pulses the energy calculation and flow indication is also based on the 8 seconds value. Data memory The FUE950 has a history memory of 24 periods (months, weeks, days). The following values are stored monthly, weekly or daily in the EEPROM on the programmed day of 1…31 (via software tool). • Date/Time • Volume • Energy • Error day counter • Tariff energy 1 • Maximum monthly flow rate • Tariff energy 2 • Maximum monthly power • Tariff definition 1 • Date of maximum monthly flow rate • Tariff definition 2 • Date of maximum monthly power • Pulse counter input 1 • Pulse counter input 2 Maximal Values The integrator creates max. values for power and flow rate based on consumption time, which are stored in the EEPROM. The integration intervals are adjustable to 6, 15, 30 or 60 minutes and 24h. Default setting is 60 minutes. Tariff/Accounting date function The calculator includes two independent memories in which the accumulated energy at two programmable tariff dates are stored. • Last accounting date • Last but one accounting date Values stored • Energy • Volume • Tariff counter 1 • Tariff counter 2 • Pulse counter 1 • Pulse counter 2 • Date The integrator offers two optional tariff memories for monitoring plant load states. Here it concerns threshold value tariffs. Extensive tariff conditions make it possible to adapt the calculator individually to the required customer-specific applications. Both tariffs are separately configurable and independent from each other. Energy or time can be measured alternatively per tariff register dependent on the tariff mode adjusted in each case. With the "time triggered tariff function" the switch-on time and the switch-off time are adjustable independent from each other for each day of the week in steps of 15 minutes. • Operation hours Siemens FI 01 · 2016 3/303 3 © Siemens AG 2016 Flow Measurement SITRANS F US Inline SITRANS FUE950 energy calculator The following tariff limit types of the tariff function are possible: (This example applies to the display at 1 fractional digits after comma) 3 Pulse input module Type Description Limit Limit resolution dT Temperature difference 1 ... 190 °C 1 °C Two pulse inputs are available. The pulse value and the unit is configurable for energy, water, gas or electrical meter by parameterization software. Data are separate cumulated in different registers and are also stored on the two accounting day's (Tariff registers). -dT Negative temperature difference 1 ... 190 °C 1 °C Combined Pulse Input/Output module TR Return temperature (low) 1 ... 190 °C 1 °C TV Forward temperature (high) 1 ... 190 °C 1 °C P Power 10 ... 2 500 kW 10 kW Two pulse inputs combined with one pulse output are available on one module. The pulse inputs are configurable with value and the unit by parameterization software. Q Flow 1 ... 255 m3/h FE "Theoretically forward energy" with return temperature of 0 °C Z "Time triggered" counting energy E "External" counting energy 1 m3/h Error handling and memory Events such as changes and faults are stored in a non-volatile memory with a capacity of up to 127 entries. The following events are recorded: • Checksum error • Temperature measurement error • Error hours • Start and end of test mode If SITRANS FUE950 records an error, this will be automatically indicated by a "alarm symbol" on the display. To protect the reading data, all the relevant data are saved in a non-volatile memory (EEPROM). This memory saves the measured values, device parameters and types of error at regular intervals. The following events are recorded: • Temperature sensor error • Swapped hot and cold temperature sensors • Battery low warning • Power supply failure • Optical communication warning • RAM checksum error Outputs/Inputs/Communication Communication interfaces: SITRANS FUE950 is fitted with an optical infra-red send/receive port in accordance with EN1434/IEC 61107, protocol standard, EN 1434/EN 60870-3 (M-Bus protocol). A specific optical head with a permanent magnet (IrDA-adapter) in accordance with EN 1434 can be used for readout data or communication with the parameterization software. 2 ports for optionally plug-in modules The calculator features 2 ports for the plug-in modules. One slot is for the function modules and the other for the communication modules. Communication modules The following communication modules are available as options: RS 232 module, RS 485 module and M-Bus module. The RS 232 and RS 485 communication modules are serial interfaces and permit data exchange with the calculator. For this purpose a special data cable is necessary. The M-Bus module is a serial interface for communication with external devices (M-Bus Master/Centre). According to the M-Bus structure a number of calculators can be connected to a control centre. 3/304 Siemens FI 01 · 2016 The pulse output is also programmable using the parameterization software. Pulse output The calculator provides levels for two optional external pulse outputs, which can be freely programmed using the parameterization software tool. Default setting is one pulse which occurs per change in the least significant digit in the display with the unit and resolution selected by the device ordering. Possible pulse output values • Energy (default setting) • Volume (default setting) • Tariff energy 1 • Tariff energy 2 • Tariff condition 1, limit switch • Tariff condition 2, limit switch • Energy error • Volume error • Volume with specific resolution (0.1, 1.0, 10 or 100) • Energy with specific resolution (0.1, 1.0, 10 or 100) Combined current output module Optional module with 2 passive 4 ... 20 mA outputs. Possible output values: • Power (default setting for output #1) • Flow (default setting for output #2) • Hot, cold or difference temperature The settings can be configured by parameterization software. The current output module occupies both ports, means no other plug-in module will possible to plug in. Module combinations The calculator has a group of extension modules for communication and another group of extension modules for additional functionality. These modules are available first selected within the calculator, or for retrofitting in the field. One single function module as well as one single communication module out of following modules is selectable. Function modules: • Pulse input module, 2 inputs • Pulse output module, 2 outputs • Combined pulse module 2 inputs, 1 output • Combined current output module, 2 x passive 4 ... 20 mA (occupies both ports) Communication modules: • M-Bus (M-Bus protocol according EN 1434-3) • RS 232 (M-Bus protocol according EN 1434-3) • RS 485 (M-Bus protocol according EN 1434-3) © Siemens AG 2016 Flow Measurement SITRANS F US Inline SITRANS FUE950 energy calculator ■ Integration User interface (always included) SITRANS FUE950 is a multi-purpose energy calculator for media water which meets the requirements of EN 1434. Further, the energy calculator has been specially developed to process volume pulses from SITRANS FUS380/FUE380 or alternatively MAG 5000/6000 or FST020 transmitter. Display 8-digit LCD display with associated pictograms/symbols Units MWh, GJ, Gcal, MBtu, m3, m3/h, GPM, gal, °C, °F, kW, MBtu/h (gal is shown with factor x 100) Totalizer value range 99 999 999 or 9 999 999.9 (0 and 1 digit after comma). Display digits: Flow in 6 digits; Volume, power and energy in 8 digits Values Power, energy, volume, flow rate, temperatures Push button Single push button for the menu controlling Optical interface IrDA interface ZVEI optical interface with M-Bus protocol as per EN 1434, connection via separate IrDA-adapter baud rate: 300 or 2400 ■ Technical specifications Approval MID approved in accordance with energy meter EN 1434 and PTB K7.2 (German national cooling approval) Approved temperature range • Heating 0 ... 180 ºC (32 ... 356 °F) • Cooling 0 ... 105 °C (32 ... 221 °F) Absolute temperature range -20 ... +190 °C (-4 ... -374 °F) Rated operation conditions Differential temperature 3 ... 177 K (starting at 0.1 K) Enclosure • Cooling 3 ... 102 K Material Measuring accuracy Meets requirements of EN 1434 Typically max. (0.5 + 3K/) [%] of measured value • Housing C Lexan 141R (or similar); colors: light gray (top part) and black (bottom part) • Pipe/wall fitting PA 6.6 GF25 (or similar) Volume: 1 s, temperature: 4 s • Other plastic parts ABS Cycolac GPM500 (or similar) • Mains versions Volume: 1/8 s, temperature: 2 s • Gaskets Neoprene and rubber cable bushings: EPDM 50 Flow range Depends on pulse input value (IN0), see "Selection and Ordering data". • Rubber cable bushings EPDM 50 • Heating Measuring rates • Battery type D-cell Power range value Depends on pulse input value as follows: Pulse input value (l/P or gal/P) Max power [kW] 1 2.5 5 10 25 50 100 250 *) 500 *) 1 000 *) 15 000 15 000 15 000 150 000 150 000 150 000 1 500 000 1 500 000 1 500 000 15 000 000 Temperature • Ambient 5 ... 55 °C (41 … 131 °F) • Storage -25 ... +70 °C (-13 … +158 °F) Relative ambient humidity < 93 % Environment class *) not available for gal/pulse • Mechanic class M1/M2 • Electromagnetic class E1/E2 (MID) or C (DIN EN 1434) Temperature input (always included) Function The temperature sensors must be connected to terminals 1-5 and 6-2 (TH) and 3-7 and 8-4 (TC) depending on cable type (2-wire or 4-wire). Temperature range Absolute measuring range -20 ... 190 °C (-4 … 374 °F) for TH and TC Temperature difference Start 0.1 K, min. 3 K, max. 177 K Measurement cut-off 0.125 K 16-bit digital resolution AD converter Display resolution TH and TC: 0.1 K , T: 0.1 K Sensor types Pt100 or Pt500 as 2-wire or 4wire; Standard is Pt500. Sensor cable length: up to 10 m (according EN 1434 and MIDtype approval). Sensor connection 4-wire or 2-wire; auto detection of connection version Max. error Typical accuracy of FUE950 2.0 1.5 EN 1434 1.0 0.5 0 -0.5 Flow input (IN0) (always included) -1.0 Function -1.5 -2.0 IP54 in accordance with IEC 529 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 ∆Θ Used as standard for flow input of the external flowmeter. The input is marked as 10 (+ Flow Pulse), 11 (- Gnd) on the terminal strip. Note: The pulse input value selection must be the same as the pulse output setting of the flowmeter. Siemens FI 01 · 2016 3/305 3 © Siemens AG 2016 Flow Measurement SITRANS F US Inline SITRANS FUE950 energy calculator 3 Pulse value 1 ... 1 000 l/pulse or 1 ... 100 gal/pulse, selection by corresponding Order code. Will be shown at the device label Pulse frequency 100 Hz (200 Hz) Pulse ON-time 3 ms Pulse OFF-time 2 ms Type Active pulse input Terminal voltage 3.6 V DC (supplied internally by FUE950) Flowmeter installation place The flowmeter installation place can be in the hot line or cold line ("forward or return pipe") selected by corresponding Order code. The "installation place" will be shown at the device display and nameplate Connected cable Max. 10 m (shielded cables are highly recommended) Possible pulse output selection Pulse input Function Add-on module for two additional counters. The pulse input 1 is marked as I1, 'gnd' and the input 2 as I2, 'gnd' on the terminal strip and indicated in the display as separate registers IN1 and IN2 and can also be transferred via the communication modules. Type Passive "open collector" pulse inputs, outputs not potential isolated to each other, data are separate cumulated in different registers and are also stored on the two accounting day's. Pulse value Pulse value and the unit are configurable for energy, water, gas or electrical meter by a software tool Default: Pulse input 0.1 m3 or 1 gal (if unit 'gal' is ordered with the Z-option "L05") Pulse frequency 8 Hz Pulse length 10 ms External voltage supply 3 V DC (supplied internally by FUE950) Current based on Ri = 2.2 M Cable length < 10 m connection limit Ports for option modules Type The calculator features 2 ports for optional plug-in modules. Function modules (Port 1 or 2) • Pulse input module, 2 inputs (In1, In2) • Pulse output module, 2 outputs (Out1, Out2) • Combination module of 2 inputs (In1, In2) and 1 output (Out1) Current output module (Port 1) 2 passive 4 ... 20 mA (#1, #2) (occupies both port 1 and 2) Communication modules (Port 1 or 2) M-Bus, RS 232 or RS 485 (M-Bus protocol, according EN 1434-3) Pulse output Function The module contains connections for 2 pulse outputs, which can be programmed as desired using a software tool. The pulse outputs are marked as standard as O1, 'gnd' and O2, 'gnd' on the terminal strip and Out1 respectively Out2 in the display. Type Passive "open collector" pulse output, outputs potential isolated to each other Pulse value Last significant digits of the display (unit/pulse), selection by corresponding Order code and setting can be read via display menu, settings changeable via software tool Current output module Function The module contains connections for 2 passive current outputs, which can be programmed individually using the software tool. The outputs are marked „#1" and „#2" with corresponding polarity „+" and „-" on the terminal strip. The module will be connected on port 1 only, but both ports are occupied by the module. Terminal voltage External supply: 10 … 30 V DC (passive output) Signal range 4 … 20 mA; 4 mA = 0 value and 20 mA = default maximum values (for #1: Power in kW and for #2: Flow with the max. values and selected unit). Defaults: For power it is the max. selectable value x 100 000 the last digit of display (e. g. 20 mA = 10 000 kW (1 digit res.) or 100 000 kW (0 digit res). For flow it is the max. selectable value x 10 000 the last digit of display (e. g. 20 mA = 1 000.0 m3/h (1 digit res.) or 10 000 m3/h (0 digit res.). Pulse output 1 • Pulse frequency 4 Hz • Pulse width 125 ms ± 10 % • Pulse duration 125 ms ± 10 % • Pulse break 125 ms -10 % Pulse output 2 • Pulse frequency 100 Hz, depending on the selected pulse length • Ratio Pulse duration/pulse break ~1:1 Pulse length 5, 10, 50, 100 ms (default: 5 ms) External voltage supply 3 … 30 V DC Current 20 mA with a residual voltage of 0.5 V 3/306 Siemens FI 01 · 2016 • Energy (default setting for 'Out1') • Volume (default setting for 'Out2') • Tariff energy 1 • Tariff energy 2 • Tariff condition 1 (limit switch) • Tariff condition 2 (limit switch) • Energy error • Volume error • Volume with specific display resolution (or with factor 0, 1, 10 or 100 thereof) • Energy with specific display resolution (or factor 0.1 thereof) © Siemens AG 2016 Flow Measurement SITRANS F US Inline SITRANS FUE950 energy calculator Load Max. 800 Upper limit Up to 20.5 mA (exceed causes the error current value) Signal on alarm Errors are indicated with 3.5 mA or 22.6 mA (programmable, default: 3.5 mA) Output values Power, flow, temperature (configuring via software tool; default: for #1: Power and for #2: Flow) M-Bus output Type The optional M-Bus plug-in module is a serial interface for communication with external devices (M-Bus Repeater) Protocol M-Bus according EN 1434-3 Connection The connection is not polarityconscious and is electrically isolated, connection of 2 x max. 2.5 mm2 wires, 300 or 2400 baud (auto baud detection), current drawn: one M-Bus load. M-Bus address: Each port has its own primary M-Bus address (Prim1 = the last two digits of the serial number; Prim2 = 0). The secondary address is unique for each calculator and is factory-set to equal the serial number. Power consumption 230 V and 24 V versions Typical current appr. 0.15 VA 3.6 V D-cell battery Typical battery lifetime 10 years under normal conditions (no addon modules, max. 40 °C ambient temperature) Supply data Internal voltage 3.6 V by the battery or plug-in power supply module Battery, 3.6 V type (option) 3.6 V lithium D-cell, battery lifetime typically 16 years with independently powered flowmeter 230 V AC module (option) Plug-in module for 230 V AC (195 ... 253 V AC), 50/60 Hz (incl. battery backup) 24 V AC module (option) Plug-in module for 24 V AC (12 ... 30 V AC) (incl. battery backup) Battery backup (option) Only with mains supply modules by internal 3.0 V lithium battery (type CR 2032) Displayed values, date and time are still updated, but the measuring functions have stopped, including the flow rate measurement. Communication via optional modules M-Bus, RS 485, RS 232 or optical interface is maintained, affecting the backup battery lifetime. RS 232 output Protocol M-Bus according EN 1434-3 Connection The module contains a 3-pole terminal strip with terminals marked 62, 63, 64 (max. 2.5 mm2); Connected cable length: max 10 m; For communication with a PC a special adapter cable is required (Article No. A5E02611774). RS 485 output Function The optional RS 485 module is a serial interface for data transmission with external devices, e.g. PC; baud rate: 2400. The module contains a 4-pole terminal strip with terminals marked D+, D-, Vcc and GND. Protocol M-Bus protocol according EN 1434-3 Connection Terminals D+ and D-; electrically isolated; 2400 baud only. An external supply of 12 V DC ± 5 V (<5 W) is needed for the module (terminals Vcc and GND). The module terminals are max. for 2.5 mm2 wires. Connected cable length: max. 10 m Accessories/Software The parameterization software based on the M-Bus is a convenient tool for handling the calculator. It runs on Windows and is used for: • Configuration of the calculator functionality, reading out different memories, printing out calculator logs (standard). • Expert programming of the device (advanced setup). • Test Lab programming of the device (full setup) Configuration of the calculator functionality, reading out different memories, printing out calculator logs. For further details please contact your local Siemens representative. A specific optical head with a permanent magnet in (IrDA adapter with bluetooth) accordance with EN 1434 can be used for programming/altering programming of readout data, configuration data, etc. The reader head can also be used to change measuring data. ■ Dimensional drawings 54.7 (2.15) The optional module RS 232 is a serial interface for data transmission with external devices, e.g. PC; baud rate: 300 or 2400. The module contains a 3-pole terminal strip with terminals marked 62 (TX), 63 (RX) and 64 (GND). For this purpose a special data cable is necessary. 150 (5.90) 99 (3.90) Type SITRANS FUE950, dimensions in mm (inch) Siemens FI 01 · 2016 3/307 3 © Siemens AG 2016 Flow Measurement SITRANS F US Inline SITRANS FUE950 energy calculator ■ Technical specifications Temperature sensor pairs: 2-wire Pt500 Pt500 2-wire temperature sensor pair (EN 1434) 3 Wall mounting m .3 ax (0. 8( 5.0 Pairing Paired to EN 1434 (10 ... 130 °C/14 ... 266 ºF) Media temperature 0...150 °C (32 ... 302 ºF) Response time T0.5 See sensor pocket specifications Medium Typically heating water Pressure rating See sensor pocket specifications Protection IP65 Pipe material AISI 304Ti/1.4303 Dimension 6 mm Sensor tube length 50 mm Cable length Up to 10 m (32.8 ft), fixed connected silicon cable, 2 connection wire terminals, terminal sleeves to DIN 46228 Pt500 4-wire temperature sensor pair (with MID and PTB K7.2 approval) 70 (2.75) Pt500 temperature sensor, EN 60751, tolerance class B, 2-wire 4-wire Pt500 4) 94 (3.7) 12 ) 11 Measuring insert 4x Ø4 ( 0.1 5) Measuring insert Pt500 temperature sensor, EN 60751, tolerance class to ISO 751 Class B; 4-wire Pairing Matched paired according to EN 1434 at 10, 75 and 140 °C (50, 167 and 284 °F) Type approval MID (DE-06-MI004-PTB011) and PTB K7.2 (PTB 22.77/09.01). Only to be mounted with related sensor pockets according to the type approvals. Media temperature 0...150 °C (32 ... 302 °F) Panel mounting, dimensions in mm (inch) Pt500 temperature sensor pairs ■ Application The temperature sensor set is designed for use with the Siemens energy calculator type SITRANS FUE950 for measurement of the energy consumption in a district heating or cooling net. Permissible temp. pair range for T • Heating 3 ... 150 K • Cooling 3 ... 85 K Temperature sensors are one of the integral components of every thermal energy meter in heating or cooling applications. They are used for determining temperature changes in fluids due to energy taken from or supplied to the loop. The temperature is thus measured by mounting temperature sensors upstream and downstream from the point where the exchange in the thermal energy of the system is. Medium Approved for heating/cooling water Protection IP65 To ensure an accurate measurement of the temperature difference according to MID (EN 1434) or PTB K7.2 the sensors are delivered as matched pairs. By selection with the corresponding Order code the Pt500 sensor pair sets can be delivered with heating approval or with approvals for combined heating/cooling applications. 3/308 Siemens FI 01 · 2016 Environment • Mechanic class M3 • Electromagnetic class E1 (MID) Pressure rating See sensor pocket specifications Material • Protective tube Stainless steel AISI 304Ti/1.4571 (or similar), diameter of protective tube: 6 mm • Connector cable Silicon cable, 4 connection wire terminals, terminal sleeves to DIN 46228 Sensor tube length 140 or 230 mm (5.51 or 9.06 inch) Cable length 5 m (16.4 ft), fixed connected © Siemens AG 2016 Flow Measurement SITRANS F US Inline SITRANS FUE950 energy calculator Sensor pockets Pt500 4-wire temperature sensor pair (with MID and PTB K7.2 approval) Stainless steel sensor pocket (for 4-wire Pt500 types only - standard) Approval Approved only together with 4-wire sensors Medium Approved for heating/cooling water; up to max. 5 m/s flow velocity Pressure rating PN 40 Length Face-to-face length 120/135 and 210/225 mm (4.72"/5.23" and 8.27"/8.86") External diameter Protective tube 8/11 mm (0.32"/0.43") Internal diameter Protective tube 6 mm (0.24") Pipe connection Thread G 1/2" (with sealing screw for sensor) Material Protective tube AISI 316Ti/1.4571 (or similar) Use • Use with related 4-wire Pt500 sensors only (according type approval) • For flow velocities up to 5 m/s • Recommended to install with welded sleeve (according to EU standard) Ø6 (2.36) Media temperature 0 ... 150 °C (32 ... 302 ºF) Pt500 4-wire temperature sensor, dimensions in mm (inch) Length L1 (mm) 92 127 168 223 L (mm) 82 117 155 210 L1 Ø 8 (0.32) G½ Media temperature 0 ... 180 °C (32 ... 356 ºF) L Approved for heating water Response time T0.5 Typically 13 s at 0.4 m/s without pasta Sensor pocket (for 2-wire Pt500 types only), stainless steel, dimensions in mm (inch) Typically 5 s at 0.4 m/s with pasta Pressure rating PN 25 Length L1 (mm) 92 127 168 223 L (mm) 117 155 210 82 3 Stainless steel sensor pocket (for 2-wire Pt500 types only) Stainless steel sensor pocket (for 2-wire Pt500 types only - some only available as spare part) Medium 5000 (1969) 140/230 (55.1/90.6) Material Stainless steel: AISI 316Ti/1.4571 Use For 2-wire Pt500 types only Stainless steel sensor pocket (for 4-wire Pt500 types only) 135/225 (5.32/8.86) Media temperature 0 ... 150 °C (32 ... 302 ºF) Approved for heating water Medium Ø8/11 (0.32/0.43) G½ Brass sensor pocket (for 2-wire Pt500 types only - some only available as spare part) Response time T0.5 Typically 9 s at 0.4 m/s without pasta 120/210 (4.72/8.27) Typically 5 s at 0.4 m/s with pasta Pressure rating PN 16 Length L1 (mm) 47 92 127 L (mm) 40 82 117 Material Brass: CuZn40Pb2 (Ms58) Use For 2-wire Pt500 types only Stainless steel sensor pocket, dimensions in mm (inch) Brass sensor pocket (for 2-wire Pt500 types only) Length L1 (mm) 47 92 127 L (mm) 40 82 117 ■ Dimensional drawings L1 Pt500 2-wire temperature sensor pair (EN 1434) G½ Ø 8 (0.32) 2, 3, 5 or 10 m ('C' at the dimensional drawing) Ø6 (0.24) Cable length L 50 (1.97) C Sensor pocket, brass (for 2-wire Pt500 types only), dimensions in mm (inch) Pt500 2-wire temperature sensor, dimensions in mm (inch) Siemens FI 01 · 2016 3/309 © Siemens AG 2016 Flow Measurement SITRANS F US Inline SITRANS FUE950 energy calculator Article No. Selection and Ordering data Energy calculator SITRANS FUE950, MID or PTB K7.2 custody transfer approved Order code 777 7 ME 3 4 8 0 - 7 7777 - 7777 Click on the Article No. for the online configuration in the PIA Life Cycle Portal. 3 Flow input setting (IN0) The pulse input value selection must be the same as the pulse output setting of the selected flowmeter. To get optimal function and performance the pulse value must be selected as low as possible according to the maximum flow rate. The following calculation formula can be used for determining the lowest pulse value at a pulse length of 5 ms: L/pulse > Qmax (m3/h)/360. For example Qmax = 300 m3/h; L/pulse > 300/360; L/pulse > 0.83; therefore the pulse value must be 1 l/pulse. Pulse input Flow limit in l/pulse Qmax in m3/h or in gal/pulse (with option L05) 1 360 2.5 900 5 1 800 10 3 600 25 9 000 50 18 000 100 36 000 250 90 000 500 180 000 1 000 360 000 *) GPM = Gallons per minute Flow limit Qmax in GPM *) (with option L05) 6 000 15 000 30 000 60 000 150 000 300 000 600 000 - Calculator application/Flowmeter installation place For heating, flowmeter in return pipe (cold pipe), typical standard For heating, flowmeter in forward pipe (hot pipe) For cooling, media water, flowmeter in forward pipe (cold pipe) For cooling, media water, flowmeter in return pipe (hot pipe) For combined cooling/heating, flowmeter in forward pipe (hot pipe as heating) (MID conformity declaration for heating) For combined cooling/heating, flowmeter in return pipe (cold pipe as heating) (MID conformity declaration for heating) Temperature sensor type Pt500 setup, no sensor pair included (standard) Pt500 setup and Pt500 sensor pair (6/140 mm), 4-wire with 5 m connection cable, 6 mm sensor diameter and 140 mm sensor length. MID approved DE-06-MI004-PTB011, PTB approved 22.77/09.01, incl. factory test report (mentioned approvals are only valid if temp. sensors are used with the applicable temperature sensor pockets). Pt500 setup and Pt500 sensor pair (6/230 mm), 4-wire with 5 m connection cable, 6 mm sensor diameter and 230 mm sensor length. MID approved DE-06-MI004-PTB011, PTB approved 22.77/09.01, incl. factory test report (mentioned approvals are only valid if temp. sensors are used with the applicable temperature sensor pockets). Pt100 setup, no sensor pair included Pt 500 setup and PT500 sensor pair (6/50 mm), 2-wire type incl. 5 m cable, 6 mm sensor diameter and 50 mm length, with MID approval (only for use with the applicable temperature sensor pockets) Pt 500 setup and PT500 sensor pair (6/50 mm), 2-wire type incl. 10 m cable, 6 mm sensor diameter and 50 mm length, with MID approval (only for use with the applicable temperature sensor pockets) Temperature sensor pocket sets: (for 6 mm sensor diameter) No pockets (standard) Brass pockets for 6 mm 2-wire sensors, length 82/92 mm, G½ inch, max. PN 16 (2 pcs.) Stainless steel pocket, 120/135 mm length for 6 mm sensor diameter, max. PN 40 and max. 5 m/s (2 pcs. for 140 mm 4-wire sensors above) Stainless steel pockets for 6 mm 2-wire sensors, length 117/127 mm, G½ inch, max. PN 25 (2 pcs.) Stainless steel pocket, 210/225 mm length for 6 mm sensor diameter, max. PN 40 and max 5 m/s (2 pcs. for 230 mm 4-wire sensors above) Stainless steel pockets for 6 mm 2-wire sensors, length 155/168 mm, G½ inch, max. PN 25 (2 pcs.) Voltage supply Battery 3.6 V DC (Litium D-cell type) (standard) Mains power module for 230 V AC supply (incl. back-up battery) Mains power module for 24 V AC supply (incl. back-up battery) No power supply module (power supply ordering separate) 3/310 Siemens FI 01 · 2016 2A 2B 2C 3A 3B 3C 4A 4B 4C 5A A B C D E F 0 3 4 5 6 7 0 2 5 6 7 8 1 2 3 4 © Siemens AG 2016 Flow Measurement SITRANS F US Inline SITRANS FUE950 energy calculator Selection and Ordering data Energy calculator SITRANS FUE950, MID or PTB K7.2 custody transfer approved Article No. Order code 777 7 ME 3 4 8 0 - 7 7777 - 7777 Option modules No module (standard) A 1 module (communication module) M-Bus module RS 232 module (M-Bus protocol) RS 485 module (M-Bus protocol) B C D 1 module (function module) Pulse output, 2x output (Out1 "Energy" and Out2 "Volume") Pulse input, 2x input (In1 and In2) Pulse out-/input combination, 2x input and 1x output E F G 3 Combination of 2 modules (communication and function module) H J K L M-Bus module and Pulse output, 2x output (Out1 "Energy" and Out2 "Volume") M-Bus module and Pulse input, 2x input (In1 and In2) M-Bus module and Pulse out/-input combination, 2x input and 1x output RS 232 module (M-Bus) and Pulse output, 2x output (Out1 "Energy" and Out2 "Volume") RS 232 module (M-Bus) and Pulse input, 2x input (In1 and In2) RS 232 module (M-Bus) and Pulse out/-input combination, 2x input and 1x output M N P RS 485 module (M-Bus) and Pulse output, 2x output (Out1 "Energy" and Out2 "Volume") RS 485 module (M-Bus) and Pulse input, 2x input (In1 and In2) RS 485 module (M-Bus) and Pulse out/-input combination, 2x input and 1x output Q R S Combination current output module, 2x passive 4 ... 20 mA (Out 1 "Power", Out 2 "Flow") (occupies both module Ports 1 and 2) Display units and resolutions MWh & kW, m3, m3/h in 2 digit resolution; Temperature: no decimal figures MWh & kW, m3, m3/h in 1 digit resolution; Temperature: no decimal figures MWh & kW, m3, m3/h in 0 digit resolution; Temperature: no decimal figures C D E GJ & kW, m3, m3/h in 2digit resolution; Temperature: no decimal figures GJ & kW, m3, m3/h in 1 digit resolution; Temperature: no decimal figures GJ & kW, m3, m3/h in 0 digit resolution; Temperature: no decimal figures H J K Gcal & kW, m3, m3/h in 2 digit resolution; Temperature: no decimal figures Gcal & kW, m3, m3/h in 1 digit resolution; Temperature: no decimal figures Gcal & kW, m3, m3/h - in 0 digit resolution; Temperature: no decimal figures M N P MBTU & MBTU/h, m3, m3/h in 2 digit resolution; Temperature: no decimal figures MBTU & MBTU/h, m3, m3/h in 1 digit resolution; Temperature: no decimal figures MBTU & MBTU/h, m3, m3/h - in 0 digit resolution; Temperature: no decimal figures Q R S Verification/Approval Without type approval mark, neutral label (standard)) With MID type approval mark (only for heating combinations, selection "A, B, E and F") With MID approval mark and first MID verfication (only for heating, selection A, B, E and F") 0 1 2 Cooling approval mark, German national cooling approval according PTB-TR-K7.2 (only for cooling and media water, selection "C and D") 7 Cooling approval mark, German national cooling approval according PTB-TR-K7.2 and first verification (only for cooling and media water, selection "C and D") 8 Further designs Please add "-Z" to Article No. and specify Order code Certificate Including factory test report (certificate) of FUE950 ALWAYS INCLUDED Cooling, setup for non water C0 2 Water/glycol setting for media type "Tyfocor LS (R)" (only with neutral label, no verification and approval) Optional settings/programming D0 2 D0 6 D0 8 D1 0 Tariff function settings (specify in clear text, up to max. 20 characters) Pulse output setting of option module (specify in clear text, up to max. 20 characters) Pulse input setting of option module (specify in clear text, up to max. 20 characters) Pulse input setting of 4 ... 20 mA option module (please specify 20 mA related type and value in clear text, up to max. 20 characters) Special display units Flow in 'GPM' and Volume in 'gal' (x100) (digits/resolution as selected above, only with 0 digit resolution) L05 Temperature in deg. F (digit resolution as selected above) L31 Siemens FI 01 · 2016 3/311 © Siemens AG 2016 Flow Measurement SITRANS F US Inline SITRANS FUE950 energy calculator ■ Flowmeter SITRANS FUE950 operating instructions, accessories and spare parts Article No. Pt500 4-wire temperature sensor pair, with MID MI004 and PTB K7.2 approvals and verification (for related 4-wire sensor pocket types only) Operating instructions Description Article No. • English A5E03424739 This device is shipped with a Quick Start guide and a CD containing further SITRANS F US literature. 3 Description All literature is available to download for free, in a range of languages, at www.siemens.com/processinstrumentation/documentation Accessories Description Article No. Infrared optical head (Bluetooth type) for data acquisition & programming of FUE950 A5E02611768 A5E02611774 Basic version of programming software tool for FUE950 free download from internet Expert version of programming software tool for FUE950 A5E03478951 Test Lab. version of re-programming software tool for FUE950 (Note: Before using this Test-Lab version an online training must be completed) A5E03461778 Spare parts Article No. Description PT500 sensor pair (6/230 mm), 4-wire with 5 m conA5E03462878 nection cable, 6 mm sensor diameter and 230 mm sensor length. MID approved DE-06-MI004-PTB011, PTB approved 22.77/09.01 (mentioned approvals are only valid if temp. sensors are used with the applicable temperature sensor pockets). FUE950 enclosure (only for 7ME348 versions) Bracket for SITRANS FUE950 wall mounting (20 pcs.) A5E02611769 Cable for data acquisition via RS 232 PC/D-sub 9F/3 wire Pt500 sensor pair (6/140 mm), 4-wire with 5 m conA5E03462872 nection cable, 6 mm sensor diameter and 140 mm sensor length. MID approved DE-06-MI004-PTB011, PTB approved 22.77/09.01 (mentioned approvals are only valid if temp. sensors are used with the applicable temperature sensor pockets). Add-on modules for FUE950 (only for 7ME348 versions) Bottom part of FUE950 enclosure (1 pc.) A5E03461508 Snap fit for FUE950 enclosure (1 pc.) A5E30461731 Pocket for Pt500 temperature sensors (for corresponding 2-wire Pt500 types only, 1pc.) Brass pocket 6 mm, G½B x 40 mm (PN 16), 1 pc. A5E02611778 Brass pocket 6 mm, G½B x 85 mm (PN 16), 1 pc. A5E02611779 Brass pocket 6 mm, G½B x 120 mm (PN 16), 1 pc. A5E02611780 Stainless steel 6 mm, G½B x 85 mm (PN 25), 1 pc. A5E02611781 Stainless steel 6 mm, G½B x 120 mm (PN 25), 1 pc. A5E02611783 Stainless steel 6 mm, G½B x 155 mm (PN 25), 1 pc. A5E02611792 Stainless steel 6 mm, G½B x 210 mm (PN 25), 1 pc. A5E02611793 Pt500 temperature sensor pair, 2-wire cable, 6 mm sensor diameter, with MID/EN-approval (for corressponding 2-wire sensor pocket types only) Pulse input module (2 inputs) A5E03461432 Cable length: Pulse output module (2 outputs) A5E03461436 2m A5E02611794 Combined pulse in-/output module (2 inputs and 1 output) A5E03461437 3m A5E02611795 5m A5E02611796 RS 232 module (M-Bus protocol) A5E03461459 10 m A5E02611798 RS 485 module (M-Bus protocol) A5E03461512 M-Bus module A5E03461516 Combined current output module, 2 x passive 4 ... 20 mA A5E03461583 Connection cable for option modules (types: Pulse, RS 232/RS 485, M-Bus, mA) (special connection cable with 2 plugs) A5E03461585 ■ Schematics Electrical connection for SITRANS FUS380/FUE380/FUE950 and MAG 5000/6000/FUE950 Power supply for FUE950 (only for 7ME348 versions) 3.6 V D-cell battery for SITRANS FUE950 A5E03461708 230 V AC supply module (incl. internal fuse T50 mA L A5E03461717 250 V and back-up battery) for SITRANS FUE950 24 V AC supply module for SITRANS FUE950, incl. back-up battery A5E03461719 56 + 57 - Pocket for temperature sensors Pt500 (for related 4-wire Pt500 type only, 1 pc.) Stainless steel pocket (1 pc.), 135 mm length for 6 mm sensor diameter, max. PN 40 and max. 5 m/s (recommended for 140 mm sensor length). A5E03462868 Stainless steel pocket (1 pc.), 225 mm length for 6 mm sensor diameter, max. PN 40 and max. 5 m/s (recommended for 230 mm sensor length). A5E03462870 3/312 Siemens FI 01 · 2016 The diagram shows the connection between SITRANS FUE950 (terminals 10 and 11) and FUS380/FUE380 and MAG 5000/6000 (terminals 56 and 57). Temperature sensors must be connected to terminals 5 (1) and 6 (2) (TH) and 7 (3) and 8 (4) (TC). Note: The right flowmeter pulse output value must be equal to the FUE950 pulse input value and must be checked via the user menu of the transmitter MAG 5000/6000 or nameplate of FUE380 or FUS380.