FUE950 energy calculator catalog sheet

© Siemens AG 2016
Flow Measurement
SITRANS F US Inline
SITRANS FUE950 energy calculator
■ Overview
■ Application
The SITRANS FUE950 is able to handle 3 kinds of applications,
means energy calculation in:
• District heating applications
• Chilled water applications
• Combined cooling/heating applications
Energy metering in heating, hot water applications
(code "A" and "B")
3
s
INFOCAL 5
SITRANS FUE950 is a universal thermal energy calculator, which
meets the requirements EN 1434 and has the MID and PTB K7.2
approval for energy metering with the media water.
SITRANS FUE950 has been developed for the SITRANS FUS380/
FUE380 and alternatively MAG 5000/6000 or FST020. SITRANS
FUE950 is modular in construction and can by order be fitted with
optional modules depending on the application. The FUE950 supports none of the SITRANS FX, FC products and only some of the
FUS clamp-on products.
Heat
Energy metering in cooling, chilled water applications
(code "C" and "D")
s
INFOCAL 5
■ Benefits
Basic functions
• Prepared for heating, cooling measurement
• Approval for MID for heat metering and PTB K7.2 for cooling
• High-accuracy thermal energy metering, meets EN1434 requirements
• Measured temperature range -20 … +190 °C (-4 … +374 °F)
• Instantaneous values for energy/volume flow
• Battery or mains powered
• Battery version with battery lifetime of typically up to 10 years
• Optical data interface
• Real date and time
• Auto-detection of 2-wire or 4-wire temperature sensors
Additional functions
• Individual tariff functions
• Advanced functions for cooling/heating applications or the
combination
• Memory for 24 periods (months, weeks, days)
• Data logger function
• Expandable functionality with 2 optional plug and play add-on
modules
• Communication over M-Bus, RS 485 or RS 232
Add-on modules
• Plug-in module with 2 extra pulse inputs
• Plug-in module with 2 pulse outputs
• Plug-in module with combination of input and output pulses
• Plug-in module for M-Bus communication
• Plug-in module for RS 232 or RS 485 communication
• Plug-in module with 2 passive current outputs (4 ... 20 mA)
3/302
Siemens FI 01 · 2016
V2
V1
Cooling
Energy metering in combined cooling/heating applications
(code "E" and "F")
s
INFOCAL 5
Cooling
7+
7&
Heat
© Siemens AG 2016
Flow Measurement
SITRANS F US Inline
SITRANS FUE950 energy calculator
Data logger memory (LOG)
■ Design
SITRANS FUE950 has an easy-read 8-digit LCD display with associated pictograms for the various functions. As the display has
been made for several applications, some figures/symbols not
used for normal district heating applications will be shown.
SITRANS FUE950 has a push button for simple operation and
provides user-friendly control via the various display menu
loops. The display will always be configured for the application
chosen, and for the selected display settings.
The integrator has an IP54 plastic housing and is designed for
wall or panel mounting. The housing comes with prepared rubber gaskets cable entries for fast and easy installation.
The LOG of the calculator is stored every 24 hours with all cumulative values in the EEPROM. The storage frequency can be selected from various storage intervals (5, 6, 10, 12, 15, 20, 30, 60
minutes or the default setting of 24 hours). The data which are
stored in the LOG could be read out using a software tool and
can be used for evaluations.
Extract of possible LOG settings
Storage
interval
Values
Number of
Recording
data records period
5 minutes
• Error status
• Overload time temperature
• Overload time flow
rate
• Forward temperature
• Return temperature
• Date and time
• Energy
• Tariff energy 1
• Tariff energy 2
• Tariff definition 1
• Tariff definition 2
• Volume
• Error day counter
440
36.6 hours
440
110 hours
440
18.3 days
440
440 days
15 minutes
Operation menu loop structure
1 hour
The FUE950 display has six menu loops and the menus are numbered in the display from 1 to 6. Some display menus consist of
two values (to maximum seven) that are shown alternately at 4second intervals.
24 hours
(default setting)
The main menu loop no. 1 with the current data, e.g. for energy,
volume, flow rate and temperature, is preprogrammed as default
setting.
In the combined heating/cooling configuration the menu loop no.
5 (tariff menu loop) will be activated additionally.
Display and output pulses
Units: MWh, GJ, Gcal, MBtu, m3, gal, m3/h, GPM, °C, °F and kW;
all decimal points are statically (the unit "gal" is shown with factor
x 100).
The display unit and the last fractional digit are typical used for
the pulse outputs.
■ Function
Technical principle
Calculation of energy is based on the following formula:
Energy = Volume x (THot - TCold) x Kfactor (Ti)
Volume: Volume [m3] of a given amount of volume pulses
THot: Measured temperature in the hot line
TCold: Measured temperature in the cold line
Kfactor (Ti): Thermal coefficient of media enthalpy and heat
content
The energy calculation is made by a counter and depends on
temperature difference, pulse input frequency and legal requirements.
The calculator always carries out at least one energy calculation
every 2 seconds. If the connected flowmeter has not sent
enough pulses the energy calculation and flow indication is also
based on the 8 seconds value.
Data memory
The FUE950 has a history memory of 24 periods (months,
weeks, days). The following values are stored monthly, weekly or
daily in the EEPROM on the programmed day of 1…31 (via software tool).
• Date/Time
• Volume
• Energy
• Error day counter
• Tariff energy 1
• Maximum monthly flow rate
• Tariff energy 2
• Maximum monthly power
• Tariff definition 1
• Date of maximum monthly flow rate
• Tariff definition 2
• Date of maximum monthly power
• Pulse counter input 1
• Pulse counter input 2
Maximal Values
The integrator creates max. values for power and flow rate
based on consumption time, which are stored in the EEPROM.
The integration intervals are adjustable to 6, 15, 30 or 60 minutes
and 24h. Default setting is 60 minutes.
Tariff/Accounting date function
The calculator includes two independent memories in which the
accumulated energy at two programmable tariff dates are
stored.
• Last accounting date
• Last but one accounting date
Values stored
• Energy
• Volume
• Tariff counter 1
• Tariff counter 2
• Pulse counter 1
• Pulse counter 2
• Date
The integrator offers two optional tariff memories for monitoring
plant load states. Here it concerns threshold value tariffs. Extensive tariff conditions make it possible to adapt the calculator individually to the required customer-specific applications.
Both tariffs are separately configurable and independent from
each other. Energy or time can be measured alternatively per
tariff register dependent on the tariff mode adjusted in each
case.
With the "time triggered tariff function" the switch-on time and the
switch-off time are adjustable independent from each other for
each day of the week in steps of 15 minutes.
• Operation hours
Siemens FI 01 · 2016
3/303
3
© Siemens AG 2016
Flow Measurement
SITRANS F US Inline
SITRANS FUE950 energy calculator
The following tariff limit types of the tariff function are possible:
(This example applies to the display at 1 fractional digits after
comma)
3
Pulse input module
Type Description
Limit
Limit
resolution
dT
Temperature difference
1 ... 190 °C
1 °C
Two pulse inputs are available. The pulse value and the unit is
configurable for energy, water, gas or electrical meter by parameterization software. Data are separate cumulated in different
registers and are also stored on the two accounting day's (Tariff
registers).
-dT
Negative temperature difference
1 ... 190 °C
1 °C
Combined Pulse Input/Output module
TR
Return temperature (low)
1 ... 190 °C
1 °C
TV
Forward temperature (high)
1 ... 190 °C
1 °C
P
Power
10 ... 2 500 kW 10 kW
Two pulse inputs combined with one pulse output are available
on one module. The pulse inputs are configurable with value and
the unit by parameterization software.
Q
Flow
1 ... 255 m3/h
FE
"Theoretically forward energy" with
return temperature of 0 °C
Z
"Time triggered" counting energy
E
"External" counting energy
1 m3/h
Error handling and memory
Events such as changes and faults are stored in a non-volatile
memory with a capacity of up to 127 entries. The following
events are recorded:
• Checksum error
• Temperature measurement error
• Error hours
• Start and end of test mode
If SITRANS FUE950 records an error, this will be automatically indicated by a "alarm symbol" on the display.
To protect the reading data, all the relevant data are saved in a
non-volatile memory (EEPROM). This memory saves the measured values, device parameters and types of error at regular intervals.
The following events are recorded:
• Temperature sensor error
• Swapped hot and cold temperature sensors
• Battery low warning
• Power supply failure
• Optical communication warning
• RAM checksum error
Outputs/Inputs/Communication
Communication interfaces:
SITRANS FUE950 is fitted with an optical infra-red send/receive
port in accordance with EN1434/IEC 61107, protocol standard,
EN 1434/EN 60870-3 (M-Bus protocol).
A specific optical head with a permanent magnet (IrDA-adapter)
in accordance with EN 1434 can be used for readout data or
communication with the parameterization software.
2 ports for optionally plug-in modules
The calculator features 2 ports for the plug-in modules.
One slot is for the function modules and the other for the communication modules.
Communication modules
The following communication modules are available as options:
RS 232 module, RS 485 module and M-Bus module. The RS 232
and RS 485 communication modules are serial interfaces and
permit data exchange with the calculator. For this purpose a
special data cable is necessary.
The M-Bus module is a serial interface for communication with
external devices (M-Bus Master/Centre). According to the
M-Bus structure a number of calculators can be connected to a
control centre.
3/304
Siemens FI 01 · 2016
The pulse output is also programmable using the parameterization software.
Pulse output
The calculator provides levels for two optional external pulse
outputs, which can be freely programmed using the parameterization software tool.
Default setting is one pulse which occurs per change in the least
significant digit in the display with the unit and resolution selected by the device ordering.
Possible pulse output values
• Energy (default setting)
• Volume (default setting)
• Tariff energy 1
• Tariff energy 2
• Tariff condition 1, limit switch
• Tariff condition 2, limit switch
• Energy error
• Volume error
• Volume with specific resolution (0.1, 1.0, 10 or 100)
• Energy with specific resolution (0.1, 1.0, 10 or 100)
Combined current output module
Optional module with 2 passive 4 ... 20 mA outputs.
Possible output values:
• Power (default setting for output #1)
• Flow (default setting for output #2)
• Hot, cold or difference temperature
The settings can be configured by parameterization software.
The current output module occupies both ports, means no other
plug-in module will possible to plug in.
Module combinations
The calculator has a group of extension modules for communication and another group of extension modules for additional
functionality. These modules are available first selected within
the calculator, or for retrofitting in the field.
One single function module as well as one single communication
module out of following modules is selectable.
Function modules:
• Pulse input module, 2 inputs
• Pulse output module, 2 outputs
• Combined pulse module 2 inputs, 1 output
• Combined current output module, 2 x passive 4 ... 20 mA
(occupies both ports)
Communication modules:
• M-Bus (M-Bus protocol according EN 1434-3)
• RS 232 (M-Bus protocol according EN 1434-3)
• RS 485 (M-Bus protocol according EN 1434-3)
© Siemens AG 2016
Flow Measurement
SITRANS F US Inline
SITRANS FUE950 energy calculator
■ Integration
User interface (always included)
SITRANS FUE950 is a multi-purpose energy calculator for media
water which meets the requirements of EN 1434. Further, the energy calculator has been specially developed to process volume
pulses from SITRANS FUS380/FUE380 or alternatively
MAG 5000/6000 or FST020 transmitter.
Display
8-digit LCD display with associated pictograms/symbols
Units
MWh, GJ, Gcal, MBtu, m3, m3/h,
GPM, gal, °C, °F, kW, MBtu/h
(gal is shown with factor x 100)
Totalizer value range
99 999 999 or 9 999 999.9 (0 and
1 digit after comma). Display digits: Flow in 6 digits; Volume,
power and energy in 8 digits
Values
Power, energy, volume, flow rate,
temperatures
Push button
Single push button for the menu
controlling
Optical interface
IrDA interface
ZVEI optical interface with M-Bus
protocol as per EN 1434, connection via separate IrDA-adapter
baud rate: 300 or 2400
■ Technical specifications
Approval
MID approved in accordance with
energy meter EN 1434 and PTB
K7.2 (German national cooling
approval)
Approved temperature range
• Heating
0 ... 180 ºC (32 ... 356 °F)
• Cooling
0 ... 105 °C (32 ... 221 °F)
Absolute temperature range
-20 ... +190 °C (-4 ... -374 °F)
Rated operation conditions
Differential temperature
3 ... 177 K (starting at 0.1 K)
Enclosure
• Cooling
3 ... 102 K
Material
Measuring accuracy
Meets requirements of EN 1434
Typically max.  (0.5 + 3K/) [%]
of measured value
• Housing
C Lexan 141R (or similar); colors:
light gray (top part) and black
(bottom part)
• Pipe/wall fitting
PA 6.6 GF25 (or similar)
Volume: 1 s, temperature: 4 s
• Other plastic parts
ABS Cycolac GPM500 (or similar)
• Mains versions
Volume: 1/8 s, temperature: 2 s
• Gaskets
Neoprene and rubber cable
bushings: EPDM 50
Flow range
Depends on pulse input value
(IN0), see "Selection and Ordering data".
• Rubber cable bushings
EPDM 50
• Heating
Measuring rates
• Battery type D-cell
Power range value
Depends on pulse input value as
follows:
Pulse input
value
(l/P or gal/P)
Max power [kW]
1
2.5
5
10
25
50
100
250 *)
500 *)
1 000 *)
15 000
15 000
15 000
150 000
150 000
150 000
1 500 000
1 500 000
1 500 000
15 000 000
Temperature
• Ambient
5 ... 55 °C (41 … 131 °F)
• Storage
-25 ... +70 °C (-13 … +158 °F)
Relative ambient humidity < 93 %
Environment class
*) not available for gal/pulse
• Mechanic class
M1/M2
• Electromagnetic class
E1/E2 (MID) or C (DIN EN 1434)
Temperature input
(always included)
Function
The temperature sensors must be
connected to terminals 1-5 and
6-2 (TH) and 3-7 and 8-4 (TC)
depending on cable type (2-wire
or 4-wire).
Temperature range
Absolute measuring range
-20 ... 190 °C (-4 … 374 °F) for TH
and TC
Temperature difference
Start 0.1 K, min. 3 K, max. 177 K
Measurement cut-off
0.125 K
16-bit digital resolution AD converter
Display resolution
TH and TC: 0.1 K , T: 0.1 K
Sensor types
Pt100 or Pt500 as 2-wire or 4wire; Standard is Pt500.
Sensor cable length: up to 10 m
(according EN 1434 and MIDtype approval).
Sensor connection
4-wire or 2-wire; auto detection of
connection version
Max. error
Typical accuracy of FUE950
2.0
1.5
EN 1434
1.0
0.5
0
-0.5
Flow input (IN0)
(always included)
-1.0
Function
-1.5
-2.0
IP54 in accordance with IEC 529
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
∆Θ
Used as standard for flow input of
the external flowmeter. The input
is marked as 10 (+ Flow Pulse),
11 (- Gnd) on the terminal strip.
Note: The pulse input value selection must be the same as the
pulse output setting of the flowmeter.
Siemens FI 01 · 2016
3/305
3
© Siemens AG 2016
Flow Measurement
SITRANS F US Inline
SITRANS FUE950 energy calculator
3
Pulse value
1 ... 1 000 l/pulse or 1 ... 100
gal/pulse, selection by corresponding Order code. Will be
shown at the device label
Pulse frequency
 100 Hz (200 Hz)
Pulse ON-time
 3 ms
Pulse OFF-time
 2 ms
Type
Active pulse input
Terminal voltage
3.6 V DC (supplied internally by
FUE950)
Flowmeter installation place
The flowmeter installation place
can be in the hot line or cold line
("forward or return pipe") selected
by corresponding Order code.
The "installation place" will be
shown at the device display and
nameplate
Connected cable
Max. 10 m (shielded cables are
highly recommended)
Possible pulse output selection
Pulse input
Function
Add-on module for two additional
counters. The pulse input 1 is
marked as I1, 'gnd' and the input
2 as I2, 'gnd' on the terminal strip
and indicated in the display as
separate registers IN1 and IN2
and can also be transferred via
the communication modules.
Type
Passive "open collector" pulse
inputs, outputs not potential isolated to each other, data are separate cumulated in different
registers and are also stored on
the two accounting day's.
Pulse value
Pulse value and the unit are configurable for energy, water, gas or
electrical meter by a software tool
Default: Pulse input 0.1 m3 or
1 gal (if unit 'gal' is ordered with
the Z-option "L05")
Pulse frequency
 8 Hz
Pulse length
 10 ms
External voltage supply
3 V DC (supplied internally by
FUE950)
Current
based on Ri = 2.2 M
Cable length
< 10 m connection limit
Ports for option modules
Type
The calculator features 2 ports for
optional plug-in modules.
Function modules (Port 1 or 2)
• Pulse input module, 2 inputs
(In1, In2)
• Pulse output module, 2 outputs
(Out1, Out2)
• Combination module of 2 inputs
(In1, In2) and 1 output (Out1)
Current output module (Port 1)
2 passive 4 ... 20 mA (#1, #2)
(occupies both port 1 and 2)
Communication modules
(Port 1 or 2)
M-Bus, RS 232 or RS 485 (M-Bus
protocol, according EN 1434-3)
Pulse output
Function
The module contains connections
for 2 pulse outputs, which can be
programmed as desired using a
software tool. The pulse outputs
are marked as standard as O1,
'gnd' and O2, 'gnd' on the terminal strip and Out1 respectively
Out2 in the display.
Type
Passive "open collector" pulse
output, outputs potential isolated
to each other
Pulse value
Last significant digits of the display (unit/pulse), selection by corresponding Order code and
setting can be read via display
menu, settings changeable via
software tool
Current output module
Function
The module contains connections
for 2 passive current outputs,
which can be programmed individually using the software tool.
The outputs are marked „#1" and
„#2" with corresponding polarity
„+" and „-" on the terminal strip.
The module will be connected on
port 1 only, but both ports are
occupied by the module.
Terminal voltage
External supply: 10 … 30 V DC
(passive output)
Signal range
4 … 20 mA; 4 mA = 0 value and
20 mA = default maximum values
(for #1: Power in kW and for #2:
Flow with the max. values and
selected unit).
Defaults:
For power it is the max. selectable
value x 100 000 the last digit of
display (e. g. 20 mA = 10 000 kW
(1 digit res.) or 100 000 kW
(0 digit res).
For flow it is the max. selectable
value x 10 000 the last digit of
display (e. g. 20 mA = 1 000.0
m3/h (1 digit res.) or 10 000 m3/h
(0 digit res.).
Pulse output 1
• Pulse frequency
 4 Hz
• Pulse width
125 ms ± 10 %
• Pulse duration
125 ms ± 10 %
• Pulse break
125 ms -10 %
Pulse output 2
• Pulse frequency
 100 Hz, depending on the
selected pulse length
• Ratio
Pulse duration/pulse break ~1:1
Pulse length
5, 10, 50, 100 ms (default: 5 ms)
External voltage supply
3 … 30 V DC
Current
 20 mA with a residual voltage of
 0.5 V
3/306
Siemens FI 01 · 2016
• Energy
(default setting for 'Out1')
• Volume
(default setting for 'Out2')
• Tariff energy 1
• Tariff energy 2
• Tariff condition 1 (limit switch)
• Tariff condition 2 (limit switch)
• Energy error
• Volume error
• Volume with specific display resolution (or with factor 0, 1, 10 or
100 thereof)
• Energy with specific display
resolution (or factor 0.1 thereof)
© Siemens AG 2016
Flow Measurement
SITRANS F US Inline
SITRANS FUE950 energy calculator
Load
Max. 800 
Upper limit
Up to 20.5 mA (exceed causes
the error current value)
Signal on alarm
Errors are indicated with 3.5 mA
or 22.6 mA (programmable,
default: 3.5 mA)
Output values
Power, flow, temperature (configuring via software tool; default: for
#1: Power and for #2: Flow)
M-Bus output
Type
The optional M-Bus plug-in module is a serial interface for communication with external devices
(M-Bus Repeater)
Protocol
M-Bus according EN 1434-3
Connection
The connection is not polarityconscious and is electrically isolated, connection of 2 x max.
2.5 mm2 wires, 300 or 2400 baud
(auto baud detection), current
drawn: one M-Bus load.
M-Bus address:
Each port has its own primary
M-Bus address (Prim1 = the last
two digits of the serial number;
Prim2 = 0). The secondary
address is unique for each calculator and is factory-set to equal
the serial number.
Power consumption
230 V and 24 V versions
Typical current appr. 0.15 VA
3.6 V D-cell battery
Typical battery lifetime 10 years
under normal conditions (no addon modules, max. 40 °C ambient
temperature)
Supply data
Internal voltage 3.6 V by the battery or plug-in power supply module
Battery, 3.6 V type (option)
3.6 V lithium D-cell, battery lifetime
typically 16 years with independently powered flowmeter
230 V AC module (option)
Plug-in module for 230 V AC
(195 ... 253 V AC), 50/60 Hz (incl.
battery backup)
24 V AC module (option)
Plug-in module for 24 V AC
(12 ... 30 V AC) (incl. battery
backup)
Battery backup (option)
Only with mains supply modules
by internal 3.0 V lithium battery
(type CR 2032)
Displayed values, date and time
are still updated, but the measuring functions have stopped,
including the flow rate measurement. Communication via optional
modules M-Bus, RS 485, RS 232
or optical interface is maintained,
affecting the backup battery lifetime.
RS 232 output
Protocol
M-Bus according EN 1434-3
Connection
The module contains a 3-pole terminal strip with terminals marked
62, 63, 64 (max. 2.5 mm2); Connected cable length: max 10 m;
For communication with a PC a
special adapter cable is required
(Article No. A5E02611774).
RS 485 output
Function
The optional RS 485 module is a
serial interface for data transmission with external devices, e.g.
PC; baud rate: 2400. The module
contains a 4-pole terminal strip
with terminals marked D+, D-,
Vcc and GND.
Protocol
M-Bus protocol according
EN 1434-3
Connection
Terminals D+ and D-; electrically
isolated; 2400 baud only.
An external supply of 12 V DC
± 5 V (<5 W) is needed for the
module (terminals Vcc and GND).
The module terminals are max. for
2.5 mm2 wires. Connected cable
length: max. 10 m
Accessories/Software
The parameterization software based on the M-Bus is a convenient tool for handling the calculator. It runs on Windows and is
used for:
• Configuration of the calculator functionality, reading out different memories, printing out calculator logs (standard).
• Expert programming of the device (advanced setup).
• Test Lab programming of the device (full setup)
Configuration of the calculator functionality, reading out different
memories, printing out calculator logs. For further details please
contact your local Siemens representative.
A specific optical head with a permanent magnet in
(IrDA adapter with bluetooth) accordance with EN 1434 can be
used for programming/altering programming of readout data,
configuration data, etc. The reader head can also be used to
change measuring data.
■ Dimensional drawings
54.7 (2.15)
The optional module RS 232 is a
serial interface for data transmission with external devices, e.g.
PC; baud rate: 300 or 2400. The
module contains a 3-pole terminal
strip with terminals marked 62
(TX), 63 (RX) and 64 (GND). For
this purpose a special data cable
is necessary.
150 (5.90)
99 (3.90)
Type
SITRANS FUE950, dimensions in mm (inch)
Siemens FI 01 · 2016
3/307
3
© Siemens AG 2016
Flow Measurement
SITRANS F US Inline
SITRANS FUE950 energy calculator
■ Technical specifications
Temperature sensor pairs:
2-wire Pt500
Pt500 2-wire temperature sensor pair (EN 1434)
3
Wall mounting
m
.3
ax
(0.
8(
5.0
Pairing
Paired to EN 1434
(10 ... 130 °C/14 ... 266 ºF)
Media temperature
0...150 °C (32 ... 302 ºF)
Response time T0.5
See sensor pocket specifications
Medium
Typically heating water
Pressure rating
See sensor pocket specifications
Protection
IP65
Pipe material
AISI 304Ti/1.4303
Dimension
 6 mm
Sensor tube length
50 mm
Cable length
Up to 10 m (32.8 ft), fixed connected silicon cable, 2 connection wire terminals, terminal
sleeves to DIN 46228
Pt500 4-wire temperature sensor pair (with MID and PTB K7.2
approval)
70
(2.75)
Pt500 temperature sensor,
EN 60751, tolerance class B,
2-wire
4-wire Pt500
4)
94
(3.7)
12
)
11
Measuring insert
4x
Ø4
(
0.1
5)
Measuring insert
Pt500 temperature sensor,
EN 60751, tolerance class to
ISO 751 Class B; 4-wire
Pairing
Matched paired according to
EN 1434 at 10, 75 and 140 °C
(50, 167 and 284 °F)
Type approval
MID (DE-06-MI004-PTB011) and
PTB K7.2 (PTB 22.77/09.01).
Only to be mounted with related
sensor pockets according to the
type approvals.
Media temperature
0...150 °C (32 ... 302 °F)
Panel mounting, dimensions in mm (inch)
Pt500 temperature sensor pairs
■ Application
The temperature sensor set is designed for use with the
Siemens energy calculator type SITRANS FUE950 for measurement of the energy consumption in a district heating or cooling
net.
Permissible temp. pair range for T
• Heating
3 ... 150 K
• Cooling
3 ... 85 K
Temperature sensors are one of the integral components of every thermal energy meter in heating or cooling applications.
They are used for determining temperature changes in fluids
due to energy taken from or supplied to the loop. The temperature is thus measured by mounting temperature sensors upstream and downstream from the point where the exchange in
the thermal energy of the system is.
Medium
Approved for heating/cooling
water
Protection
IP65
To ensure an accurate measurement of the temperature difference according to MID (EN 1434) or PTB K7.2 the sensors are
delivered as matched pairs.
By selection with the corresponding Order code the Pt500 sensor pair sets can be delivered with heating approval or with approvals for combined heating/cooling applications.
3/308
Siemens FI 01 · 2016
Environment
• Mechanic class
M3
• Electromagnetic class
E1 (MID)
Pressure rating
See sensor pocket specifications
Material
• Protective tube
Stainless steel AISI 304Ti/1.4571
(or similar), diameter of protective tube: 6 mm
• Connector cable
Silicon cable, 4 connection wire
terminals, terminal sleeves to
DIN 46228
Sensor tube length
140 or 230 mm
(5.51 or 9.06 inch)
Cable length
5 m (16.4 ft), fixed connected
© Siemens AG 2016
Flow Measurement
SITRANS F US Inline
SITRANS FUE950 energy calculator
Sensor pockets
Pt500 4-wire temperature sensor pair (with MID and PTB K7.2 approval)
Stainless steel sensor pocket (for 4-wire Pt500 types only - standard)
Approval
Approved only together with 4-wire sensors
Medium
Approved for heating/cooling water; up to max.
5 m/s flow velocity
Pressure rating
PN 40
Length
Face-to-face length 120/135 and 210/225 mm
(4.72"/5.23" and 8.27"/8.86")
External diameter
Protective tube 8/11 mm (0.32"/0.43")
Internal diameter
Protective tube 6 mm (0.24")
Pipe connection
Thread G 1/2" (with sealing screw for sensor)
Material
Protective tube AISI 316Ti/1.4571 (or similar)
Use
• Use with related 4-wire Pt500 sensors only
(according type approval)
• For flow velocities up to 5 m/s
• Recommended to install with welded sleeve
(according to EU standard)
Ø6
(2.36)
Media temperature 0 ... 150 °C (32 ... 302 ºF)
Pt500 4-wire temperature sensor, dimensions in mm (inch)
Length
L1 (mm)
92
127
168
223
L (mm)
82
117
155
210
L1
Ø 8 (0.32)
G½
Media temperature 0 ... 180 °C (32 ... 356 ºF)
L
Approved for heating water
Response time T0.5 Typically 13 s at 0.4 m/s without pasta
Sensor pocket (for 2-wire Pt500 types only), stainless steel, dimensions
in mm (inch)
Typically 5 s at 0.4 m/s with pasta
Pressure rating
PN 25
Length
L1 (mm) 92
127
168
223
L (mm)
117
155
210
82
3
Stainless steel sensor pocket (for 2-wire Pt500 types only)
Stainless steel sensor pocket (for 2-wire Pt500 types only - some
only available as spare part)
Medium
5000 (1969)
140/230 (55.1/90.6)
Material
Stainless steel: AISI 316Ti/1.4571
Use
For 2-wire Pt500 types only
Stainless steel sensor pocket (for 4-wire Pt500 types only)
135/225
(5.32/8.86)
Media temperature 0 ... 150 °C (32 ... 302 ºF)
Approved for heating water
Medium
Ø8/11
(0.32/0.43)
G½
Brass sensor pocket (for 2-wire Pt500 types only - some only available as spare part)
Response time T0.5 Typically 9 s at 0.4 m/s without pasta
120/210
(4.72/8.27)
Typically 5 s at 0.4 m/s with pasta
Pressure rating
PN 16
Length
L1 (mm)
47
92
127
L (mm)
40
82
117
Material
Brass: CuZn40Pb2 (Ms58)
Use
For 2-wire Pt500 types only
Stainless steel sensor pocket, dimensions in mm (inch)
Brass sensor pocket (for 2-wire Pt500 types only)
Length
L1 (mm)
47
92
127
L (mm)
40
82
117
■ Dimensional drawings
L1
Pt500 2-wire temperature sensor pair (EN 1434)
G½
Ø 8 (0.32)
2, 3, 5 or 10 m ('C' at the dimensional drawing)
Ø6
(0.24)
Cable length
L
50 (1.97)
C
Sensor pocket, brass (for 2-wire Pt500 types only), dimensions in mm
(inch)
Pt500 2-wire temperature sensor, dimensions in mm (inch)
Siemens FI 01 · 2016
3/309
© Siemens AG 2016
Flow Measurement
SITRANS F US Inline
SITRANS FUE950 energy calculator
Article No.
Selection and Ordering data
Energy calculator SITRANS FUE950, MID or PTB K7.2 custody transfer approved
Order code
777
7 ME 3 4 8 0 - 7 7777 - 7777
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
3
Flow input setting (IN0)
The pulse input value selection must be the same as the pulse output setting of the selected flowmeter.
To get optimal function and performance the pulse value must be selected as low as possible according
to the maximum flow rate.
The following calculation formula can be used for determining the lowest pulse value at a pulse length of
5 ms: L/pulse > Qmax (m3/h)/360.
For example Qmax = 300 m3/h; L/pulse > 300/360; L/pulse > 0.83; therefore the pulse value must be
1 l/pulse.
Pulse input
Flow limit
in l/pulse
Qmax in m3/h
or in gal/pulse
(with option
L05)
1
360
2.5
900
5
1 800
10
3 600
25
9 000
50
18 000
100
36 000
250
90 000
500
180 000
1 000
360 000
*) GPM = Gallons per minute
Flow limit Qmax
in GPM *)
(with option L05)
6 000
15 000
30 000
60 000
150 000
300 000
600 000
-
Calculator application/Flowmeter installation place
For heating, flowmeter in return pipe (cold pipe), typical standard
For heating, flowmeter in forward pipe (hot pipe)
For cooling, media water, flowmeter in forward pipe (cold pipe)
For cooling, media water, flowmeter in return pipe (hot pipe)
For combined cooling/heating, flowmeter in forward pipe (hot pipe as heating)
(MID conformity declaration for heating)
For combined cooling/heating, flowmeter in return pipe (cold pipe as heating)
(MID conformity declaration for heating)
Temperature sensor type
Pt500 setup, no sensor pair included (standard)
Pt500 setup and Pt500 sensor pair (6/140 mm), 4-wire with 5 m connection cable, 6 mm sensor diameter
and 140 mm sensor length. MID approved DE-06-MI004-PTB011, PTB approved 22.77/09.01, incl. factory
test report (mentioned approvals are only valid if temp. sensors are used with the applicable temperature
sensor pockets).
Pt500 setup and Pt500 sensor pair (6/230 mm), 4-wire with 5 m connection cable, 6 mm sensor diameter
and 230 mm sensor length. MID approved DE-06-MI004-PTB011, PTB approved 22.77/09.01, incl. factory
test report (mentioned approvals are only valid if temp. sensors are used with the applicable temperature
sensor pockets).
Pt100 setup, no sensor pair included
Pt 500 setup and PT500 sensor pair (6/50 mm), 2-wire type incl. 5 m cable, 6 mm sensor diameter and
50 mm length, with MID approval (only for use with the applicable temperature sensor pockets)
Pt 500 setup and PT500 sensor pair (6/50 mm), 2-wire type incl. 10 m cable, 6 mm sensor diameter and
50 mm length, with MID approval (only for use with the applicable temperature sensor pockets)
Temperature sensor pocket sets: (for 6 mm sensor diameter)
No pockets (standard)
Brass pockets for 6 mm 2-wire sensors, length 82/92 mm, G½ inch, max. PN 16 (2 pcs.)
Stainless steel pocket, 120/135 mm length for 6 mm sensor diameter, max. PN 40 and max. 5 m/s
(2 pcs. for 140 mm 4-wire sensors above)
Stainless steel pockets for 6 mm 2-wire sensors, length 117/127 mm, G½ inch, max. PN 25 (2 pcs.)
Stainless steel pocket, 210/225 mm length for 6 mm sensor diameter, max. PN 40 and max 5 m/s
(2 pcs. for 230 mm 4-wire sensors above)
Stainless steel pockets for 6 mm 2-wire sensors, length 155/168 mm, G½ inch, max. PN 25 (2 pcs.)
Voltage supply
Battery 3.6 V DC (Litium D-cell type) (standard)
Mains power module for 230 V AC supply (incl. back-up battery)
Mains power module for 24 V AC supply (incl. back-up battery)
No power supply module (power supply ordering separate)
3/310
Siemens FI 01 · 2016
2A
2B
2C
3A
3B
3C
4A
4B
4C
5A
A
B
C
D
E
F
0
3
4
5
6
7
0
2
5
6
7
8
1
2
3
4
© Siemens AG 2016
Flow Measurement
SITRANS F US Inline
SITRANS FUE950 energy calculator
Selection and Ordering data
Energy calculator SITRANS FUE950, MID or PTB K7.2 custody transfer approved
Article No.
Order code
777
7 ME 3 4 8 0 - 7 7777 - 7777
Option modules
No module (standard)
A
1 module (communication module)
M-Bus module
RS 232 module (M-Bus protocol)
RS 485 module (M-Bus protocol)
B
C
D
1 module (function module)
Pulse output, 2x output (Out1 "Energy" and Out2 "Volume")
Pulse input, 2x input (In1 and In2)
Pulse out-/input combination, 2x input and 1x output
E
F
G
3
Combination of 2 modules (communication and function module)
H
J
K
L
M-Bus module and Pulse output, 2x output (Out1 "Energy" and Out2 "Volume")
M-Bus module and Pulse input, 2x input (In1 and In2)
M-Bus module and Pulse out/-input combination, 2x input and 1x output
RS 232 module (M-Bus) and Pulse output, 2x output (Out1 "Energy" and Out2 "Volume")
RS 232 module (M-Bus) and Pulse input, 2x input (In1 and In2)
RS 232 module (M-Bus) and Pulse out/-input combination, 2x input and 1x output
M
N
P
RS 485 module (M-Bus) and Pulse output, 2x output (Out1 "Energy" and Out2 "Volume")
RS 485 module (M-Bus) and Pulse input, 2x input (In1 and In2)
RS 485 module (M-Bus) and Pulse out/-input combination, 2x input and 1x output
Q
R
S
Combination current output module, 2x passive 4 ... 20 mA (Out 1 "Power", Out 2 "Flow")
(occupies both module Ports 1 and 2)
Display units and resolutions
MWh & kW, m3, m3/h in 2 digit resolution; Temperature: no decimal figures
MWh & kW, m3, m3/h in 1 digit resolution; Temperature: no decimal figures
MWh & kW, m3, m3/h in 0 digit resolution; Temperature: no decimal figures
C
D
E
GJ & kW, m3, m3/h in 2digit resolution; Temperature: no decimal figures
GJ & kW, m3, m3/h in 1 digit resolution; Temperature: no decimal figures
GJ & kW, m3, m3/h in 0 digit resolution; Temperature: no decimal figures
H
J
K
Gcal & kW, m3, m3/h in 2 digit resolution; Temperature: no decimal figures
Gcal & kW, m3, m3/h in 1 digit resolution; Temperature: no decimal figures
Gcal & kW, m3, m3/h - in 0 digit resolution; Temperature: no decimal figures
M
N
P
MBTU & MBTU/h, m3, m3/h in 2 digit resolution; Temperature: no decimal figures
MBTU & MBTU/h, m3, m3/h in 1 digit resolution; Temperature: no decimal figures
MBTU & MBTU/h, m3, m3/h - in 0 digit resolution; Temperature: no decimal figures
Q
R
S
Verification/Approval
Without type approval mark, neutral label (standard))
With MID type approval mark (only for heating combinations, selection "A, B, E and F")
With MID approval mark and first MID verfication (only for heating, selection A, B, E and F")
0
1
2
Cooling approval mark, German national cooling approval according PTB-TR-K7.2 (only for cooling and
media water, selection "C and D")
7
Cooling approval mark, German national cooling approval according PTB-TR-K7.2 and first verification
(only for cooling and media water, selection "C and D")
8
Further designs
Please add "-Z" to Article No. and specify Order code
Certificate
Including factory test report (certificate) of FUE950
ALWAYS INCLUDED
Cooling, setup for non water
C0 2
Water/glycol setting for media type "Tyfocor LS (R)" (only with neutral label, no verification and approval)
Optional settings/programming
D0 2
D0 6
D0 8
D1 0
Tariff function settings (specify in clear text, up to max. 20 characters)
Pulse output setting of option module (specify in clear text, up to max. 20 characters)
Pulse input setting of option module (specify in clear text, up to max. 20 characters)
Pulse input setting of 4 ... 20 mA option module (please specify 20 mA related type and value in clear text,
up to max. 20 characters)
Special display units
Flow in 'GPM' and Volume in 'gal' (x100) (digits/resolution as selected above, only with 0 digit resolution)
L05
Temperature in deg. F (digit resolution as selected above)
L31
Siemens FI 01 · 2016
3/311
© Siemens AG 2016
Flow Measurement
SITRANS F US Inline
SITRANS FUE950 energy calculator
■ Flowmeter SITRANS FUE950 operating instructions,
accessories and spare parts
Article No.
Pt500 4-wire temperature sensor pair, with MID
MI004 and PTB K7.2 approvals and verification (for
related 4-wire sensor pocket types only)
Operating instructions
Description
Article No.
• English
A5E03424739
This device is shipped with a Quick Start guide and a CD containing further SITRANS F US literature.
3
Description
All literature is available to download for free, in a range of languages, at
www.siemens.com/processinstrumentation/documentation
Accessories
Description
Article No.
Infrared optical head (Bluetooth type) for data
acquisition & programming of FUE950
A5E02611768
A5E02611774
Basic version of programming software tool for FUE950 free download
from internet
Expert version of programming software tool for
FUE950
A5E03478951
Test Lab. version of re-programming software tool for
FUE950 (Note: Before using this Test-Lab version an
online training must be completed)
A5E03461778
Spare parts
Article No.
Description
PT500 sensor pair (6/230 mm), 4-wire with 5 m conA5E03462878
nection cable, 6 mm sensor diameter and 230 mm
sensor length. MID approved DE-06-MI004-PTB011,
PTB approved 22.77/09.01 (mentioned approvals are
only valid if temp. sensors are used with the applicable temperature sensor pockets).
FUE950 enclosure (only for 7ME348 versions)
Bracket for SITRANS FUE950 wall mounting (20 pcs.) A5E02611769
Cable for data acquisition via RS 232 PC/D-sub
9F/3 wire
Pt500 sensor pair (6/140 mm), 4-wire with 5 m conA5E03462872
nection cable, 6 mm sensor diameter and 140 mm
sensor length. MID approved DE-06-MI004-PTB011,
PTB approved 22.77/09.01 (mentioned approvals are
only valid if temp. sensors are used with the applicable temperature sensor pockets).
Add-on modules for FUE950 (only for 7ME348 versions)
Bottom part of FUE950 enclosure (1 pc.)
A5E03461508
Snap fit for FUE950 enclosure (1 pc.)
A5E30461731
Pocket for Pt500 temperature sensors (for corresponding 2-wire Pt500 types only, 1pc.)
Brass pocket 6 mm, G½B x 40 mm (PN 16), 1 pc.
A5E02611778
Brass pocket 6 mm, G½B x 85 mm (PN 16), 1 pc.
A5E02611779
Brass pocket 6 mm, G½B x 120 mm (PN 16), 1 pc.
A5E02611780
Stainless steel 6 mm, G½B x 85 mm (PN 25), 1 pc.
A5E02611781
Stainless steel 6 mm, G½B x 120 mm (PN 25), 1 pc.
A5E02611783
Stainless steel 6 mm, G½B x 155 mm (PN 25), 1 pc.
A5E02611792
Stainless steel 6 mm, G½B x 210 mm (PN 25), 1 pc.
A5E02611793
Pt500 temperature sensor pair, 2-wire cable, 6 mm
sensor diameter, with MID/EN-approval (for corressponding 2-wire sensor pocket types only)
Pulse input module (2 inputs)
A5E03461432
Cable length:
Pulse output module (2 outputs)
A5E03461436
2m
A5E02611794
Combined pulse in-/output module (2 inputs and
1 output)
A5E03461437
3m
A5E02611795
5m
A5E02611796
RS 232 module (M-Bus protocol)
A5E03461459
10 m
A5E02611798
RS 485 module (M-Bus protocol)
A5E03461512
M-Bus module
A5E03461516
Combined current output module, 2 x passive
4 ... 20 mA
A5E03461583
Connection cable for option modules (types: Pulse,
RS 232/RS 485, M-Bus, mA) (special connection
cable with 2 plugs)
A5E03461585
■ Schematics
Electrical connection for SITRANS FUS380/FUE380/FUE950
and MAG 5000/6000/FUE950
Power supply for FUE950 (only for 7ME348 versions)
3.6 V D-cell battery for SITRANS FUE950
A5E03461708
230 V AC supply module (incl. internal fuse T50 mA L A5E03461717
250 V and back-up battery) for SITRANS FUE950
24 V AC supply module for SITRANS FUE950, incl.
back-up battery
A5E03461719
56 +
57 -
Pocket for temperature sensors Pt500 (for related
4-wire Pt500 type only, 1 pc.)
Stainless steel pocket (1 pc.), 135 mm length for
6 mm sensor diameter, max. PN 40 and max. 5 m/s
(recommended for 140 mm sensor length).
A5E03462868
Stainless steel pocket (1 pc.), 225 mm length for
6 mm sensor diameter, max. PN 40 and max. 5 m/s
(recommended for 230 mm sensor length).
A5E03462870
3/312
Siemens FI 01 · 2016
The diagram shows the connection between SITRANS FUE950 (terminals
10 and 11) and FUS380/FUE380 and MAG 5000/6000 (terminals 56 and
57). Temperature sensors must be connected to terminals 5 (1) and
6 (2) (TH) and 7 (3) and 8 (4) (TC).
Note:
The right flowmeter pulse output value must be equal to the
FUE950 pulse input value and must be checked via the user
menu of the transmitter MAG 5000/6000 or nameplate of FUE380
or FUS380.