LITTELFUSE SPFJ200

POWR-GARD® Fuse Datasheet
SPFJ SERIES FUSE
1000 VDC • 125 - 450A
Specifications
Voltage Ratings:
Interrupting Rating:
1000 VDC
AC: 200 kAIC;
DC: 125-200 A: 20 kAIC
250-400 A: 10 kAIC
450 A: 20 kAIC
Amperage:
125, 160, 200, 250, 300, 350, 400, 450
Approvals:
UL 2579 Listed
UL 248-8, Class J
C UL (Approval on Class J fuse–no PV standard)
VDE certifications to IEC 60269-6 in progress
Material:Body-Melamine
End Bells-Copper Alloy
Environmental:
RoHS Compliant
Country of Origin:Mexico
Description
The SPFJ series is the smallest 1000VDC 125-450A
photovoltaic fuse available in the market. The SPFJ series
is manufactured in Class J case sizes that allows for both
fuseholder and busbar mounting configuration. The SPFJ
meets both UL and IEC requirements.
Features/Benefits
Applications
•
•
•
•
•
• Inverters
• Re-combiner boxes
Meets both UL and IEC photovoltaic standards
Small footprint reduces panel size
Full-range PV time-current characteristic
Flexibility of fuseholder or busbar mounting
Higher amperage solar fuses in standard sizes
Recommended Fuseholder
LFJ 1000VDC Solar Series
• UL Listed Class J branch and feeder circuit rated
Dimensions in mm (inches)
F
E
G
A
D
B
C
DIMENSIONS IN INCHES (MM)
Amperage
A
B
C
D
E
F
G
125-200
3 (76.2)
4 11/32 (110.19)
5 21/32 (144.02)
1 1/2 (38.1)
1 1/8 (28.6)
9/32 (7.1)
3/16 (4.8)
250-400
3 3/8 (85.7)
5 1/4 (133.35)
7 1/8 (181.0)
2 (50.8)
1 5/8 (41.3)
13/32 (10.3)
1/4 (6.4)
450
3 3/4 (95.3)
5.98 (151.99)
8 (203.2)
2 1/2 (63.5)
2 (50.8)
17/32 (13.5)
3/8 (9.5)
Look for this logo to indicate products that are used in solar applications. Visit our website
www.littelfuse.com/solar for the latest updates on approvals, certifications, codes and standards.
www.littelfuse.com
1
© JUNE 2011 Littelfuse POWR-GARD Products
POWR-GARD® Fuse Datasheet
SPFJ SERIES FUSE
Ordering Information
PART
Number
ORDERING
number
AMPERAGE
SPFJ 125
SPFJ125.X
125
SPFJ 160
SPFJ160.X
SPFJ 200
Agency Approvals
UPC
UL
VDE*
CE
ROHS
CCC*
C UL°
07945894924
l
l
l
l
l
l
160
07945894925
l
l
l
l
l
l
SPFJ200.X
200
07945894926
l
l
l
l
l
l
SPFJ 250
SPFJ250.X
250
07945894927
l
l
l
l
l
l
SPFJ 300
SPFJ300.X
300
07945894928
l
l
l
l
l
l
SPFJ 350
SPFJ350.X
350
07945894929
l
l
l
l
l
l
SPFJ 400
SPFJ400.X
400
07945894930
l
l
l
l
l
l
SPFJ 450
SPFJ450.X
450
07945894931
l
l
l
l
l
l
Electrical Specifications
VOLTAGE RATING
Interrupting Rating
TOTAL CLEARING
I2T (A2SEC) 100 kA
(600Vac)
TOTAL CLEARING
I2T (A2SEC) 10 kA
(1000Vdc)
TOTAL CLEARING
I2T (A2SEC) 20 kA
(1000Vdc)
24750
17391
23529
60100
38771
47465
108000
66151
79642
85900
55897
N/A
143000
91129
N/A
232000
170863
N/A
ORDERING
Number
AMPERAGE
Rating
AC
DC
AC
DC
SPFJ125.X
125
600
1000
200 kA
20 kA
SPFJ160.X
160
600
1000
200 kA
20 kA
SPFJ200.X
200
600
1000
200 kA
20 kA
SPFJ250.X
250
600
1000
200 kA
10 kA
SPFJ300.X
300
600
1000
200 kA
10 kA
SPFJ350.X
350
600
1000
200 kA
10 kA
SPFJ400.X
400
600
1000
200 kA
10 kA
400500
287094
N/A
SPFJ450.X
450
600
1000
200 kA
20 kA
565333
401687
400916
ORDERING
Number
AMPERAGE
Rating
Nom Cold
Resistance
(Ohm)
MELTING
I 2T (10kA dc)
(1000Vdc)
MELTING
I 2 T (20kA dc)
(1000Vdc)
Watts Loss
at 100% Rated
Current (W)
WATTS LOSS
AT 80% RATED
CURRENT (W)
WATTS LOSS
AT 70% RATED
CURRENT (W)
9.04
SPFJ125.X
125
0.964
6863
5824
23.00
12.60
SPFJ160.X
160
0.613
19053
19368
22.77
12.67
9.15
SPFJ200.X
200
0.460
34053
32502
27.40
15.09
10.87
SPFJ250.X
250
0.485
31022
N/A
49.17
26.20
20.59
SPFJ300.X
300
0.367
59201
N/A
52.90
28.32
20.02
SPFJ350.X
350
0.285
109799
N/A
54.48
29.31
20.99
SPFJ400.X
400
0.236
198654
N/A
58.40
31.47
22.21
SPFJ450.X
450
0.187
317627
201877
50.55
28.68
20.79
* In Progress
° C UL Approval on Class J fuse (no CSA PV standard exists)
www.littelfuse.com
2
© JUNE 2011 Littelfuse POWR-GARD Products
POWR-GARD® Fuse Datasheet
SPFJ SERIES FUSE
Electrical Specification – Agency Requirements
Opening Time (Minutes)
ORDERING
NUMBER.
AMPERAGE
SPFJ125.X
125
SPFJ160.X
160
SPFJ200.X
200
SPFJ250.X
250
SPFJ300.X
300
SPFJ350.X
350
SPFJ400.X
400
SPFJ450.X
450
100% of Amp Rating 113% of Amp Rating 135% of Amp Rating 145% of Amp Rating 200% of Amp Rating
per UL
per IEC
per UL
per IEC
per UL
120 Min
120 Max
10 Max
Temperature
Stabilization
180 Min
120 Max
180 Max
12 Max
240 Min
240 Max
14 Max
PERCENT OF UPRATING
Temperature Rerating Curve
60
40
20
0
20
40
60
-60˚ C
-76˚ F
-40˚ C
-40˚ F
-20˚ C
-4˚ F
0˚ C
-32˚ F
20˚ C
68˚ F
40˚ C
104˚ F
60˚ C
140˚ F
80˚ C
176˚ F
100˚ C
212˚ F
120˚ C
248˚ F
PERCENT OF DOWNRATING
0
140˚ C
284˚ F
AMBIENT TEMPERATURE
www.littelfuse.com
3
© JUNE 2011 Littelfuse POWR-GARD Products
POWR-GARD® Fuse Datasheet
SPFJ SERIES FUSE
Recommended Torque Values For Buss Bar Mounting
RECOMMENDED TORQUE VALUES FOR BUSS BAR MOUNTING FUSE
ORDERING NUMBER
FUSE TORQUE–METRIC (STANDARD)
HARDWARE size–Metric (Standard)*
SPFJ125.X
7.3 N•m (65 in-lb)
6mm (1/4 -20)
SPFJ160.X
7.3 N•m (65 in-lb)
6mm (1/4 -20)
SPFJ200.X
7.3 N•m (65 in-lb)
6mm (1/4 -20)
SPFJ250.X
19.2 N•m (170 in-lb)
10mm ( 3/ 8 -16)
SPFJ300.X
19.2 N•m (170 in-lb)
10mm ( 3/ 8 -16)
SPFJ350.X
19.2 N•m (170 in-lb)
10mm ( 3/ 8 -16)
SPFJ400.X
19.2 N•m (170 in-lb)
10mm ( 3/ 8 -16)
SPFJ450.X
19.2 N•m (170 in-lb)
12mm (7/16 -14)
* Recommended minimum hardware grade 2 or class 5.8
For fuseholder information, drawings and specifications visit www.littelfuse.com/solar
www.littelfuse.com
4
© JUNE 2011 Littelfuse POWR-GARD Products
POWR-GARD® Fuse Datasheet
SPFJ SERIES FUSE
TIME CURRENT CURVE
Time Current Curve
100000
90000
80000
70000
60000
50000
40000
30000
20000
10000
9000
8000
7000
6000
5000
4000
3000
2000
1000
900
800
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
1000
900
800
700
600
500
1000
900
800
700
600
500
400
400
450A
300
300
400A
200
200
350A
300A
100
90
80
70
60
50
250A
200A
40
TIME IN SECONDS
100
90
80
70
60
50
30
160A
20
125A
40
30
20
10
9
8
7
6
5
10
9
8
7
6
5
4
4
3
3
2
2
1
0.9
0.8
0.7
0.6
0.5
1
0.9
0.8
0.7
0.6
0.5
0.4
0.4
0.3
0.3
0.2
0.2
0.1
0.09
0.08
0.07
0.06
0.05
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.04
0.03
0.03
0.02
0.02
0.01
0.01
100000
90000
80000
70000
60000
50000
40000
30000
5
20000
www.littelfuse.com
TIME CONSTANT/ POWER FACTOR:
10000
9000
8000
7000
6000
5000
BASIS FOR DATA:
1000 Vdc
4000
TEST VOLTAGE:
3000
2000
1000
900
800
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
CURRENT IN AMPERES
FUSE CATALOG NUMBER
SPFJ 125A-450A
© JUNE 2011 Littelfuse POWR-GARD Products
DRAWN BY:
NCS
POWR-GARD® Fuse Datasheet
SPFJ SERIES FUSE
PEAK LET-THRU CHARACTERISTIC CURVES
1000000
100000
450A
400A
350A
PEAK LET- THRU IN AMPERES
300A
250A
200A
200A
160A
160A
125A
125A
10000
1000
100
100
1000
10000
100000
1000000
AVAILABLE FAULT CURRENT
SYMMETRICAL R.M.S. AMPERES
Tested at 600 Vac
www.littelfuse.com
6
© JUNE 2011 Littelfuse POWR-GARD Products