UL Report for Contactors 3RT102.pdf

File E31519
Project 96ME20939
September 10, 1996
REPORT
on
MOTOR CONTROLLERS, MAGNETIC
Siemens AG
Amberg, Fed. Rep. Germany
Copyright © 1996 Underwriters Laboratories Inc.
Underwriters Laboratories Inc. authorizes the above-named company to reproduce
this Report provided it is reproduced in its entirety.
File E31519
Vol. 11
Sec. 1
and Report
Page 1
Issued: 1996-09-10
Revised: 2006-01-13
DESCRIPTION
PRODUCT COVERED:
USL, CNL
24, 25, 26 or
P, Q, R, S, V
3, 4, 5, 6 or
numbers.
- Type No 3RT10, 3RT11, 3RT13, 3RT15 or 3RT16 followed by 23,
27 followed by -1 or -3, followed by A, B, C, D, E, F, H, J, K,
or X followed by a character and a number followed by 0, 1, 2,
8, may be followed by -0LA2, -0GA0 or any suffix letters and/or
GENERAL:
These devices are open types 3 or 4 pole contactors for use in industrial
applications. Type 3RT1.23 is identical to 3RT1.24 except for the ratings.
Type 3RT1124 devices additionally have been evaluated to IEC 60947-6,
weld-free.
ENGINEERING CONSIDERATIONS (NOT FOR UL REPRESENTATIVE USE):
CNL - Indicates Investigated to Canadian National Standard(s) C22.2 No.
14-M95
Note: CNL = Canadian National Standards - Listed.
USL = United States Standards - Listed.
RATINGS:
Horsepower 3RT1023
Voltage
115 V
200/208
230/240
460/480
575/600
V
V
V
V
1-ph
3-ph
FLA
1/3 hp
1 hp
1 hp
-
2
3
5
7
7.2
9.2
9.6
7.6
9.0
hp
hp
hp
1/2 hp
LRA
A
A
A
A
A
-57.5 A
73 A
61 A
73.2 A
Horsepower 3RT1024
Voltage
115 V
200/208
230/240
460/480
575/600
V
V
V
V
1-ph
3-ph
FLA
LRA
1 hp
2 hp
2 hp
---
-3 hp
3 hp
7 1/2 hp
10 hp
16 A
13.8 A
12 A
11 A
11 A
-84 A
73 A
91.5 A
90 A
*File E31519
Vol. 11
and Report
Sec. 1
Page 2
Issued:
Revised:
1996-09-10
2003-03-06
Horsepower 3RT1025
Voltage
115 V
200/208
230/240
460/480
575/600
V
V
V
V
1-ph
3-ph
FLA
LRA
1 hp
2 hp
3 hp
---
-5 hp
5 hp
10 hp
15 hp
16 A
17.5 A
17 A
14 A
17 A
-140
122
113
135
A
A
A
A
Horsepower 3RT1026
Voltage
115 V
200/208
230/240
460/480
575/600
V
V
V
V
1-ph
3-ph
FLA
LRA
2 hp
3 hp
3 hp
---
-7 1/2 hp
7 1/2 hp
15 hp
20 hp
24 A
25.3 A
22 A
21 A
22 A
-210.5A
183 A
169 A
180 A
Horsepower 3RT1023 or 3RT1024 (Elevator Control)
Voltage
*120 V
*230/240 V
460/480 V
575/600 V
1-ph
2-ph
3-ph
FLA
LRA
1/3 hp
1 hp
3 hp
3 hp
3 hp
7.5 hp
7.5 hp
3 hp
6 hp
7-1/2 hp
9.6 A
9.6 A
9 A
73 A
73 A
73.2 A
Horsepower 3RT1025 or 3RT1026 (Elevator Control)
Voltage
*120 V
230/240 V
460/480 V
575/600 V
1-ph
2-ph
3-ph
FLA
LRA
¾
2
5
3
5 hp
10 hp
10 hp
5 hp
10 hp
10 hp
15.2 A
14 A
11 A
122 A
113 A
90 A
hp
hp
hp
hp
Horsepower 3RT1124 (Weld-Free according to IEC 60947-6 Standard)
Voltage
200/208 V
230/240 V
460/480 V
3-ph
FLA
LRA
3 hp
3 hp
7-1/2 hp
11 A
9.6 A
11 A
84 A
73 A
91.5 A
Horsepower 3RT1325, 3RT1326 or 3RT1526 (4 NO or 2 NO + 2 NC Main Contacts)
Voltage
200/208 V
230/240 V
460/480 V
3-ph
FLA
LRA
5 hp
7-1/2 hp
15 hp
17.5 A
22 A
21 A
140 A
183 A
169 A
File E31519
Vol. 11
Sec. 1
and Report
*Page 3
Issued:
Revised:
9-10-96
1-2-02
Capacitive Switching 3RT1626
Voltage
200/208
230/240
460/480
575/600
V
V
V
V
1-ph
3-ph
4.5 kVar
5 kVar
10.5 kVar
13 kVar
8 kVar
9 kVar
18 kVar
22.8 kVar
Current
22
22
22
22
A
A
A
A
Capacitive Switching 3RT1627
Voltage
200/208
230/240
460/480
575/600
V
V
V
V
Main contacts:
1-ph
3-ph
7 kVar
8 kVar
16 kVar
20 kVar
12.5 kVar
14 kVar
28.5 kVar
35 kVar
Current
36
36
36
36
A
A
A
A
General Purpose Rating
- type 3RT102., 600 V AC, 35 A
Auxiliary contacts: 1-, 2- or 4-pole auxiliary contacts type 3RH1921 are top
or side mounted, for ratings refer to File E44653 Vol. 11,
Sec. 2 or Vol. 12 Sec. 3. The auxiliary contact blocks
are available as factory assembled (removable or not
removable design) or available as separate devices for
individual arrangements.
Coil Ratings:
24 through 600 V ac
12 through 250 V dc
Definite Purpose:
Electric Heating,
- type 3RT1023 35
- type 3RT1024 35
- type 3RT1025 35
- type 3RT1026 35
AC Resistance:
- type 3RT1325 600 V, 40 A
- type 3RT1326 600 V, 40 A
- type 3RT1526 600 V, 40 A
600 V, 250,000 c.
A
A
A
A
File E31519
Vol. 11
Sec. 1
and Report
Page 4
Issued: 1996-09-10
Revised: 2006-01-13
Short Circuit Ratings:
Type No.
Fuse
3RT1023
3RT1024
3RT1025/3RT1325
3RT1026
3RT1326/3RT1526
3RT1124
3RT1626
3RT1627
1
2
Note:
Note:
max 70 A
max 70 A
max 70 A
max 100 A
max 100 A
max 40 A
max 80 A
Max 125 A
Circuit Breaker
Bkr I2
Bkr TM1
max 60 A
max 60 A
max 60 A
max 100 A
max 100 A
-
max
max
max
max
max
10
10
30
40
40
-
Short
Circuit
A
A
A
A
A
5
5
5
5
5
5
5
5
Voltage
kA
kA
kA
kA
kA
kA
kA
kA
600
600
600
600
600
480
600
600
V
V
V
V
V
V
V
V
UL Listed inverse time circuit breakers
UL Recognized instantaneous trip circuit breakers manufactured by
Siemens, Type ED63A...
High Capacity Short Circuit Ratings:
Type No.
3RT1023
3RT1024
3RT1025
3RT1026
3
Fuse Rating
Size
Volt
Short
[A]
[V]
[kA]
-
480
600
480
600
480
600
480
600
-
CB Rating (Bkr TM)
Size
Volt.
Short
[A]
[V]
[kA]
30
30
40
40
50
50
70
70
480
600
480
600
480
600
480
600
65
25
65
25
65
25
65
25
3RV102 / Size SO3
Size
Volt
Short
[A]
[V]
[kA]
8
8
10
10
16
12.5
22
12.5
480
600
480
600
480
600
480
600
Note:
For Siemens UL Listed Combination Motor Controller Type 3RV102
(Size SO) covered in File E156943.
Models:
3RT1026 may be marked “May Replace NEMA Size 1 Contactors”.
*
65
25
65
25
65
25
65
25
File E31519
Vol. 11
Sec. 1
and Report
Page 4A
Issued: 1996-09-10
Revised: 2006-01-13
Short Circuit Rating for Contactor, Fuse, Overload Relay combination according
To UL 60947-4-1, for type “2” co-ordination.
Contactor
Overload
Relay
Fuse
Class
LPJ
[A]
Voltage
for High
Fault
Current
High Fault
Current [kA]
according to
UL60947-4-1
Standard Fault
Current [kA]
according to
UL60947-4-1 at
600V
3RT1024
3RT1025
3RT1025
3RT1026
3RT1026
3RT1026
3RT1026
3RT1026
3RU1126-1K
3RU1126-4A
3RU1126-4B
3RU1126-4C
3RU1126-4C
3RU1126-4D
3RU1126-4D
3RU1126-4D
20
25
30
40
40
30
50
50
600
600
600
480
600
600
480
600
100
100
100
100
65
100
100
65
5
5
5
5
5
5
5
5