32310221 OE spec MTU12V4000DS1550 FC 60Hz 1 15

DIESEL GENERATOR SET
MTU 12V4000 DS1550
Standby Power: 1550 KWel
380V/60 Hz/Water Charge Air Cooling/Fuel Consumption Optimized
Optional equipment and finishing shown. Standard may vary.
Product Highlights
// Benefits
// Performance
- Low fuel consumption
- Optimized system integration ability
- High reliability
- High availability of power
- Long maintenance intervals
Assurance Certification (PAC)
- Engine-generator set tested to ISO 8528-5 for transient
response
- 85% load factor
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
// MTU
// Complete
Onsite Energy is a single-source supplier
// Support
- Global product support offered
// Standards
- Engine-generator set is designed and manufactured in
facilities certified to standards ISO 2008:9001 and
ISO 2004:14001
- Generator set complies to ISO 8528
- Generator meets NEMA MG1, BS5000, ISO, DIN EN and
IEC standards
- NFPA 110
// Power
Rating
- System rating: 650 kVA - 1700 kVA
- Accepts rated load in one step per NFPA 110
- Generator set complies to G3 according to ISO 8528-5
- Generator set exceeds load steps according to ISO 8528-5
range of accessories available
- Control panel
- Fuel system
- Fuel connections with shut-off valve mounted to base frame
- Starting/charging system
// Emissions
- Fuel consumption optimized
// Certifications
- CE certification option
2
/ // / MTU 12V4000 DS1550 / FC / 60 Hz / 380V
Application data➀
// // Engine
Manufacturer
Model
Type
Arrangement
Displacement: l
Bore: mm Stroke: mm Compression ratio
Rated speed: rpm
Engine governor
Max power: kWm Air cleaner
// MTU
12V4000G43
4-cycle
12V
57.2
170
210
16.4
1800
ADEC (ECU 7)
1736
Dry
Fuel System
Maximum fuel lift: m Total fuel flow: l/min
// 5
16
Fuel Consumption
➁
At 100% of power rating: At 75% of power rating: At 50% of power rating:
l/hr
420.4
312.2
221.7
g/kwh
201
199
212
Liquid Capacity (Lubrication)
Total oil system capacity: l
Engine jacket water capacity: l
Intercooler coolant capacity: l
260
160
40
// Combustion Air Requirements
Combustion air volume: m3/s
Max. air intake restriction: mbar
2.3
50
// Cooling/Radiator System
Coolant flow rate (HT circuit): m3/h
Coolant flow rate (LT circuit): m3/h
Heat rejection to coolant: kW
Heat radiated to charge air cooling: kW
Heat radiated to ambient: kW
67
35
640
410
75
// Exhaust System
Exhaust gas temp. (after turbocharger): °C
Exhaust gas volume: m3/s
Maximum allowable back pressure: mbar
Minimum allowable back pressure: mbar
➀ All data refers only to the engine and is based on ISO standard conditions (25°C and 100m above sea level).
➁ Values referenced are in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml.
All fuel consumption values refer to rated engine power.
430
5.4
85
30
3
/ // / MTU 12V4000 DS1550 / FC / 60 Hz / 380V
Standard and Optional Features
// System
Ratings (kW/kVA)
Voltage: V
Phases
Frequency: Hz
Power output: kWel
Power output: kVA*
Rated AMPS
Generator model
MTU 12V4000 DS1550
Standby Power
380
3
60
1550
1938
2944
Marathon 744RSL7091
* cos phi = 0,8
// Engine
■ 4-Cycle
■ Standard single stage air filter
■ Oil drain extension & shut-off valve
// ■ Fuel consumption optimized engine
■ No load to full load regulation
■ ±0.25% voltage regulation no load to
full load
■ Brushless alternator with brushless
pilot exciter
■ 4 pole, rotating field
■ Sustained short circuit current of up
to 300% of the rated current for up
to 10 seconds
■ Marathon low voltage generator
Generator
■ NEMA MG1, BS5000, ISO, DIN EN and
IEC standards
■ Self-ventilated
■ Superior voltage waveform
■ Solid state, volts-per-Hertz regulator
// ■ Closed crankcase ventilation
■ Governor-electronic isochronous
■ Common rail fuel injection
Cooling System
■ Jacket water pump
■ Thermostat(s)
■ Water charge air cooling
 Jacket water heater
■ Represents standard features
 Represents optional features
4
/ // / MTU 12V4000 DS1550 / FC / 60 Hz / 380V
Standard and Optional Features, continuation
// Control Panel
■ Pre-wired control cabinet for easy
application of customized controller
(V1+)
 Island operation (V2)
 Automatic mains failure operation
with ATS (V3a)
 Automatic mains failure operation
incl. control of generator and mains
breaker (V3b)
 Island parallel operation of multiple
gensets (V4)
Automatic mains failure operation
with short (< 10s) mains parallel
overlap synchronization (V5)
Mains parallel operation of a single
genset (V6)
Mains parallel operation of multiple
gensets (V7)
//  Battery rack & cables
 Battery charger
Mounting System
■Welded base frame
//  Switchable fuel filter with
water separator
 Separate fuel cooler
Starting/Charging System
■ 24V starter
 Starter batteries
//  Different expansion modules
 Remote annunciator
 Daytank control
 Generator winding temperature
monitoring
 Generator bearing temperature
monitoring
 Differential protection with
multi-function protection relay
 Modbus RTU-TCP gateway
Fuel System
■ Flexible fuel connectors mounted to
base frame
 Fuel filter with water separator
//  Basler controller
 Deif controller
■Complete system metering
■ Digital metering
■ Engine parameters
■ Generator protection functions
■ Engine protection
■ SAE J1939 engine ECU
communications
■ Parametrization software
■ Multilingual capability
■ Multiple programmable contact inputs
■ Multiple contact outputs
■ Event recording
■ IP 54 front panel rating with
integrated gasket
■ Resilient engine and generator
mounting
Exhaust System
 Exhaust bellows with connection
flange
 Y-connection-pipe
■ Represents standard features
 Represents optional features
■ Modular base frame design
5
/ // / MTU 12V4000 DS1550 / FC / 60 Hz / 380V
Weights and dimensions
Drawing above for illustration purposes only, based an standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.
System
Open Power Unit (OPU)
Dimensions (L x W x H)
4583 x 1836 x 2330 mm
Weight (dry/less tank)
10877 kg
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific engine-generator set.
Sound data
// Consult your local MTU Onsite Energy distributor for sound data.
Emissions data
// Consult your local MTU Onsite Energy distributor for emissions data.
Rating Definitions and conditions
Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for
the duration of a power outage. No overload capability for this rating. Ratings are in accordance with ISO 8528-1, ISO-3046-1,
BS 5514 and AS 2789. Average Load Factor: ≤ 85%. Operating hours/year: max. 500.
// Deration factor:
Altitude: Consult your local MTU Onsite Energy Power Generation distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy Power Generation distributor for temperature derations.
Rated power is available up to 40°C and 400m above sea level.