3237631 OE spec MTU20V4000DS3200 3D FC 50Hz 1 15

DIESEL GENERATOR SET
MTU 20V4000 DS3200
380V – 11 kV/50 Hz/Standby Power/Fuel Consumption Optimized
MTU 20V4000G63L/Water Charge Air Cooling
Optional equipment and finishing shown. Standard may vary.
Product Highlights
// Benefits
// Performance
- Low fuel consumtion
- Optimized system integration ability
- High reliability
- High availability of power
- Long maintenance intervals
Assurance Certification (PAC)
- Engine-generator set tested to ISO 8528-5 for transient
response
- 85% load factor
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
// MTU
// Complete
Onsite Energy is a single-source supplier
// Support
- Global product support offered
// Standards
- Engine-generator set is designed and manufactured in
facilities certified to standards ISO 2008:9001 and
ISO 2004:14001
- Generator set complies to ISO 8528
- Generator meets NEMA MG1, BS5000, ISO, DIN EN and
IEC standards
- NFPA 110
// Power
Rating
- System ratings: 3100 kVA - 3400 kVA
- Accepts rated load in one step per NFPA 110
- Generator set complies to G3 according to ISO 8528-5
- Generator set exceeds load steps according to ISO 8528-5
range of accessories available
- Control panel
- Circuit breaker/power distribution
- Fuel system
- Fuel connections with shut-off valve mounted to base frame
- Starting/charging system
- Exhaust system
- Mechanical and electrical driven radiators
- Medium voltage alternators
// Emissions
- Fuel consumption optimized
// Certifications
- CE certification option
2
/ // / MTU 20V4000 DS3200 / 50 Hz / 380V - 11kV
Application data➀
// Manufacturer
Model
Type
Arrangement
Displacement: l
Bore: mm Stroke: mm Compression ratio
Rated speed: rpm
Engine governor
Max power: kWm Air cleaner
// // Engine
MTU
20V4000G63L
4-cycle
20V
95.4
170
210
16.4
1500
ADEC (ECU 7)
2850
Dry
Fuel System
Maximum fuel lift: m Total fuel flow: l/min
// 5
27
Total oil system capacity: l
Engine jacket water capacity: l
Intercooler coolant capacity: l
390
205
50
// Combustion Air Requirements
Combustion air volume: m3/s
Max. air intake restriction: mbar
3.3
50
// Cooling/Radiator System
Coolant flow rate (HT circuit): m3/h
Coolant flow rate (LT circuit): m3/h
Heat rejection to coolant: kW
Heat radiated to charge air cooling: kW
Heat radiated to ambient: kW
Fan power for mech. radiator (40°C): kWm
80
32.5
1050
500
105
70
// Fuel Consumption➁
At 100% of power rating: At 75% of power rating: At 50% of power rating:
Liquid Capacity (Lubrication)
l/hr
666.1
489.3
338.2
g/kwh
194
190
197
Exhaust System
Exhaust gas temp. (after turbocharger): °C
Exhaust gas volume: m3/s
Maximum allowable back pressure: mbar
Minimum allowable back pressure: mbar
➀ All data refers only to the engine and is based on ISO standard conditions (25°C and 100m above sea level).
➁ Values referenced are in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml.
All fuel consumption values refer to rated engine power.
560
8.8
85
30
3
/ // / MTU 20V4000 DS3200 / 50 Hz / 380V - 11kV
Standard and Optional Features
// System Ratings (kW/kVA)
Generator model
Voltage
Fuel consumption optimized 40°C/400m
without radiator
with mechanical radiator
with electr. driven radiator
kWel
kVA*
AMPS
kWel
kVA*
AMPS
kWel
kVA*
AMPS
Marathon 1030FDL7094 380 V
2640
3300
5014
2640
3300
5014
2520
3150
4786
(Low voltage
400 V
2600
3250
4691
2560
3200
4619
2520
3150
4547
marathon standard)
415 V
2560
3200
4452
2560
3200
4452
2480
3100
4313
n.a.
380 V
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
(Low voltage
400 V
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
marathon oversized)
415 V
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
380 V
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
(Low voltage marathon
400 V
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
engine output optimized) 415 V
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
Leroy Somer LSA 54 M75
380 V
c/f
c/f
c/f
c/f
c/f
c/f
c/f
c/f
c/f
(Low voltage
400 V
2720
3400
4907
2640
3300
4763
2640
3300
4763
Leroy Somer)
415 V
2720
3400
4730
2640
3300
4591
2640
3300
4591
Marathon 1030FDH7102 11 kV
2720
3400
178
2680
3350
176
2640
3300
173
(Medium volt. marathon)
Leroy Somer LSA 54 XL85 11 kV
2720
3400
178
2680
3350
176
2640
3300
173
(Medium volt. Leroy Somer)
* cos phi = 0,8
// Engine
■ 4-Cycle
■ Standard single stage air filter
■ Oil drain extension & shut-off valve
■ Closed crankcase ventilation
■ Governor-electronic isochronous
■ Common rail fuel injection
■ Fuel consumption optimized engine
■ NEMA MG1, BS5000, ISO, DIN EN and
IEC standards
■ Self-ventilated
■ Superior voltage waveform
■ Solid state, volts-per-Hertz regulator
■ No load to full load regulation
■ ±0,25% voltage regulation no load to
full load
■ Brushless alternator with brushless
pilot exciter
■ 4 pole, rotating field
■ Sustained short circuit current of up
to 250% of the rated current for up
to 10 seconds (marathon generator)
 Sustained short circuit current of up
to 300% of the rated current for up to
10 seconds (Leroy Somer generator)
■ Marathon low voltage generator
 Leroy Somer generator
 Oversized generator
 Medium voltage generator
■ Represents standard features
 Represents optional features
// Generator
4
/ // / MTU 20V4000 DS3200 / 50 Hz / 380V - 11kV
Standard and Optional Features, continuation
// Cooling System
■ Jacket water pump
■ Thermostat(s)
■ Water charge air cooling
// Control Panel
■ Pre-wired control cabinet for easy
application of customized controller
(V1+)
 Island operation (V2)
 Automatic mains failure operation
with ATS (V3a)
 Automatic mains failure operation
incl. control of generator and mains
breaker (V3b)
 Island parallel operation of multiple
gensets (V4)
Automatic mains failure operation
with short (< 10s) mains parallel
overlap synchronization (V5)
Mains parallel operation of a single
genset (V6)
Mains parallel operation of multiple
gensets (V7)
// Basler controller
Deif controller
■Complete system metering
■ Digital metering
■ Engine parameters
■ Generator Protection Functions
■ Engine protection
■ SAE J1939 engine ECU
communications
■ Parametrization software
■ Multilingual capability
■ Multiple programmable contact inputs
■ Multiple contact outputs
■ Event recording
■ IP 54 front panel rating with
integrated gasket
 Different expansion modules
 Remote annunciator
 Daytank control
 Generator winding temperature
monitoring
 Generator bearing temperature
monitoring
 Differential protection with
multi-finction protection relay
 Modbus RTU-TCP gateway
 Manual-actuated circuit breaker
 Electrical-actuated circuit breaker
 Stand-alone solution in seperate
switch box
Circuit Breaker/Power Distribution
 3-pole circuit breaker
 4-pole circuit breaker
//  Mechanical radiator
 Electrical driven front-end cooler
 Jacket water heater
Fuel System
■ Flexible fuel connectors mounted to
base frame
 Fuel filter with water separator
 Switchable fuel filter with
water separator
 Seperate fuel cooler
 Fuel cooler integrated into cooling
equipment
■ Represents standard features
 Represents optional features
5
/ // / MTU 20V4000 DS3200 / 50 Hz / 380V - 11kV
Standard and Optional Features, continuation
// Starting/Charging System
■ 24V starter
 Starter batteries
// Mounting System
■ Welded base frame
//  Battery rack & cables
 Battery charger
■ Resilient engine and generator
mounting
Exhaust System
 Exhaust bellows with connection
flange
 Exhaust silencer with 10 dB(A) sound
attenuation
 Exhaust silencer with 30 dB(A) sound
attenuation
 Exhaust silencer with 40 dB(A) sound
attenuation
 Y-connection-pipe
■ Represents standard features
 Represents optional features
■ Modular base frame design
SCHWERPUNKT in Bezug auf den Koordinatenrahmen AS_KO_STD der Baugruppe 20V_1040:
X
5,710mm
6 / // / MTU 20V4000 DS3200 / 50 Hz / 380V - 11kV
Y
218,210mm
Z
139,800mm
L=
B=
H=
6654,9910 (ohne Kühler)
1810,0000
2332.0000 (mit Standard Luftfiltern)
MASSE
= 19.614,491
Kg
Weights
and dimensions
See website for unit specific template drawings.
__________________________________________________
Drawing above for illustration purposes only, based an standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design.
System
Dimensions (L x W x H)
Weight (dry/less tank)
Powersind
Unit berechnet
(OPU)
6315
x 1810
x 2332
mm
19955 kgSchaltschrank)
*Alle Open
Massen
und
ohne
Anbaukomponenten
(ausgenommen
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific engine-generator set.
Sound data
// Consult your local MTU Onsite Energy distributor for sound data.
Emissions data
// Consult your local MTU Onsite Energy distributor for emissions data.
Rating Definitions and conditions
Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for
the duration of a power outage. No overload capability for this rating. Ratings are in accordance with ISO 8528-1, ISO-3046-1,
BS 5514 and AS 2789. Average Load Factor: ≤ 85%. Operating hours/year: max. 500.
// Deration factor:
Altitude: Consult your local MTU Onsite Energy Power Generation distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy Power Generation distributor for temperature derations.
Rated power is available up to 40°C and 400m above sea level.
Materials and specifications subject to change without notice.
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
Subject to change. | 3237631 | Edition 01/15 | ENC 2015-10.
//