View the TE Sensor Solutions for HVACR brochure here.

TE SENSOR SOLUTIONS
FOR HVACR
SENSOR SOLUTIONS /// HVACR
TE SENSOR SOLUTIONS
FOR HVACR
TE Connectivity (TE) is a global technology leader, providing connectivity and sensor solutions essential
in today’s increasingly connected world. With the acquisition of Measurement Specialties (MEAS), a global
designer and manufacturer of sensors and sensor-based systems, TE is one of the largest sensor companies
in the world. Our broad portfolio of sensor technologies is designed for a wide range of applications. We
collaborate with engineers to help transform concepts into creations—redefining what’s possible using
intelligent, efficient and high-performing TE products and solutions proven in harsh environments.
SENSOR SOLUTIONS
• PRESSURE
• TEMPERATURE
• HUMIDITY
• POSITION
• VIBRATION
• FLOW
• MASS AIR FLOW
• ULTRASONIC
INNOVATION
QUALITY STATEMENTS
• ISO 13485
• ISO 14001
• ISO 9001
• Measuring Instruments
Directive 2004/22/EC annex D
• TS 16949
• UL/CSA
SENSOR SOLUTIONS /// HVACR
HVACR APPLICATION SOLUTIONS
Alternative Energy and Solar
Commercial Chillers
Container Storage
• Room air temperature
• Flue temperature for efficiency
• Outside air temperature
to modulate damper
• Water inlet and outlet for
solar water heaters
• Solar refrigerators
• Inlet and outlet refrigerant
temperature
• Suction line temperature
• Room and outside air temperature
• Compressor high side and
low side pressure
• Room humidity
• Variable volume valve position
• Sump water level sensors
• Evaporator inlet and outlet
water temperature
• Compressor gas temperature
• Condenser inlet and outlet
water temperature
• Compressor motor temperature
• Container air temperature
• Outside air temperature
• Evaporator line pressure
• Condenser line pressure
• Container humidity
• Defrost control—humidity
or temperature
• Anti-sweat heater control—humidity
Boiler Controls
• Inlet and outlet water temperature
• Level sensing
• Outside air temperature
for reset control
• Heat and cooling rate for boiler mass
• Boiler lead and lag
timing temperature
Building and Energy
Management
• Room air temperature
for thermostats
• Duct air temperature
• Duct air pressure
• Room air humidity
• Outside air temperature
• Mass air flow sensors
Commercial
Cooking Equipment
• Non-contact temperature
sensors for flame detection
• Temperature sensors for monitoring
• Vibration sensors for fan motors
Compressors and Motors
•
•
•
•
Motor winding temperature
Compressor discharge
Compressor suction temperature
Compressor high side and
low side pressure
• Compressor oil pressure
• Compressor staging—pressure
• Vibration and acoustic sensors
for machine health monitoring
Electronic Expansion Valves
• Expansion valve pressure
• Expansion valve temperature
Forced Air Furnaces
•
•
•
•
Inlet and outlet air temperature
Room and outside air temperature
Room humidity
Air inlet and outlet pressure
PAGE 3
HVACR APPLICATION SOLUTIONS
Heat Pumps
• Cabinet entering and
leaving air temperature
• Compressor high
side and low side pressure
• Compressor discharge, compressor
suction temperature
• Entering and leaving hot
water temperature
• Load entering and leaving
water temperature
• Source entering and leaving
water temperature
• Water coil and air coil temperature
Humidifiers and
Dehumidifiers
• Room air humidity
• Water temperature for
humidification
HVACR Diagnostic
Equipment
• Digital manifold pressure
• Temperature for superheat
monitoring
Ice Machines
• Bin level sensor temperature
• Discharge water temperature
• Water inlet temperature
SENSOR SOLUTIONS /// HVACR
Packaged Terminal Air
Conditioner (PTAC)
and Small A/C
•
•
•
•
Coil temperature
Defrost termination temperature
Room temperature
Room humidity
Pool Heater and Equipment
•
•
•
•
Flue temperature
Inlet and outlet water temperature
Outside air temperature
Pressure sensor for clogged
filter monitoring
Refrigerators
• Dewpoint measurement
for anti-sweat control
• Compartment humidity
for food conservation
• Humidity monitoring
for defrost control
• Zone air temperature
Refrigeration Controls
• Compressor head pressure
• Compressor high side and
low side pressure
• Defrost termination temperature
• Inlet and outlet refrigerant
temperature
• Suction line temperature
Underfloor Heating
and Ice Melting
• Floor temperature monitoring
• Liquid temperature
• Room air temperature
VAV Systems and
Air Handlers
•
•
•
•
Damper position
Differential pressure
Fan pressure optimization
Inlet and outlet air temperature
Water Heater
Refrigerated Beverage
Dispensing
• Cabinet air temperature
• Condenser inlet and
outlet temperature
• Compressor discharge, compressor
suction temperature
• Compressor high side and
low side pressure
• Water flow sensor
• Water inlet and outlet temperature
Zone Controls
• Air temperature
• Damper position
• Duct temperature
TE SENSOR SOLUTIONS FOR HVACR
PRESSURE SENSORS
Transducers and Transmitters
M7100, U7100
M5200, U5200, D5100
Package
Automotive grade, stainless steel hermetic
pressure ports and integral electrical connector
Industrial stainless steel housing with a large selection of threaded
fittings, electrical connectors, cable options and customized housings
Type
Gage, no vent gage (M7100)
Gage, sealed gage, absolute (U7100)
Gage (M5200) Gage, sealed gage, absolute(U5200),
Differential wet-wet (D5100)
Pressure Range
0 - 10 thru 0 - 689 bar / 0 - 150 thru 0 - 10K psi (M7100)
0 - 1 thru 0 - 10 bar / 0 - 15 thru 0 - 150 psi (U7100)
0 - 3 bar thru 0 - 2K bar / 0 - 50 psi thru 0 - 30K psi (M5200)
0 - 0.14 bar thru 0 - 700 bar / 0 - 2 psi thru 0 - 10K psi (U5200)
0 - 0.07 bar thru 0 - 34 bar / 0 - 1 psi thru 0 - 500 psi (D5100)
Output/Span
0.5 - 4.5 VDC [Ratiometric output], 1 - 5 VDC [Regulated] (M7100)
0.5 - 4.5 VDC [Ratiometric output] (U7100)
0.5 - 4.5 VDC, 1 - 5 VDC, 0 - 5 VDC, 0 - 10 VDC, 4 - 20 mA
Unique Features
• 1% total error band (-20°C to 85°C)
• Solid state reliability
• Survives high vibration and immersion
• Microfused technology (M7100)
• UltraStable technology (U7100)
• Copper tube for HVACR (M7100)
• Microfused technology (M5200)
• UltraStable technology (U5200, D5100)
• High performance at a low cost
• Solid state reliability
• 1% total error band (-20°C to 85°C all possible
errors combined) (M5200, D5100)
• 0.75% total error band (-20°C to 85°C all
possible errors combined) (U5200)
• Line pressure max. 1000 psi (D5100)
Accuracy
±0.25% FSO
±0.25% FSO (M5200, D5100), ±0.1% FSO (U5200)
Operating Temp.
-40°C to 125°C
-40°C to 125°C
Dimensions (mm)
26.7 x 26.7 x 50.0
M5200: 22.23 x 22.23 x 80.77 /
U5200: 22.23 x 22.23 x 98.04 / D5100: 25.4 x 58.4 x 72.0
Typical Apps
HVACR refrigeration controls, compressors,
hydraulic, energy and water management
HVACR controls, energy and water management, pumps, compressors,
pneumatic equipment, filter blockage, pressurized tank level
Agency Approvals
CE [EMC], UL 508
CE [EMC] (M5200, D5100), CE [EMC], UL 508 (U5200)
Board Mountable
Digital Output
Board Mountable
Amplified Output
Combination Module
Digital Output
MS4515DO, MS4525DO
MS4515, MS4525
MS8607
Unique Features
• 14-bit digital sensor
• Pressure and temperature measurement
• Single supply of 3.3 or 5.0 VDC
• Top, side barbed or manifold O-ring port
• J lead or thru hole pins
• Ratiometric analog output sensor
• Single supply of either 3.3 or 5.0 VDC
• Top, side barbed or manifold O-ring port
• J lead or thru hole pins
• Optional gel coat
Options
Linearity/Absolute
Accuracy
Output / Span
Gel coat, low power
±0.25% / ±1% TEB
Gel coat
0.25% Non-linearity / 1% TEB
• QFN package pressure, temperature
and humidity sensor
• High resolution module: 0.016
mbar, 0.04% RH, 0.01°C
• Supply voltage: 1.5 to 3.6 V
• Integrated pressure, humidity and temperature
• Fully factory calibrated
—
±2 mbar / ±0.03 psi, ±3.0% RH at 25°C, ±1.0°C
14-bit digital word SPI or I2C protocol
10% to 90% or 5% to 95% of supply
Digital 24-bit I2C
Type
Gage, differential (MS4515)
Gage, absolute, differential,
compound (MS4525)
0 - 2, 4, 5, 10, 20, 30” H2O (MS4515)
0 - 0.07, 0.14, 0.35, 1, 2, 3, 10 bar /
0 - 1, 2, 5, 15, 30, 50, 150 psi (MS4525)
0.69 bar / 10 psi (MS4515)
3X range (MS4525)
Absolute
Operating Temp.
Gage, differential (MS4515DO)
Gage, absolute, differential,
compound (MS4525DO)
0 - 2, 4, 5, 10, 20, 30" H2O (MS4515DO)
0 - 0.07, 0.14, 0.35, 1, 2, 3, 10 bar /
0 - 1, 2, 5, 15, 30, 50, 150 psi (MS4525DO)
0.69 bar / 10 psi (MS4515DO)
3X range (MS4525DO)
-25°C to 125°C
-25°C to 105°C
-40°C to 85°C
Dimensions (mm)
12.5 x 9.9
12.5 x 9.9
5x3x1
Typical Apps
Air flow measurements, process
control, leak detection
Air flow measurements, process
control, leak detection
Energy management systems, thermostats,
humidifiers, dehumidifiers, home automation
Pressure Range
Overpressure
10 – 2K mbar, 0 – 100% RH, -40°C to 85°C
6 bar / 87 psi
PAGE 5
TE SENSOR SOLUTIONS FOR HVACR
PRESSURE SENSORS
Media Isolated Modules
Digital Output
85BSD, 86BSD
89BSD
Package
• 13 mm diaphragm diameter with weldable
or process fittings (85BSD)
• 16 mm diaphragm diameter with O-ring mount (86BSD)
• 9 mm diaphragm diameter
• Threaded/weldable
• Pressure and temperature read-out
• Low power: 1 μA (Standby < 0.15 μA)
Accuracy
±0.25% span
±0.3% span
Output/Span
Digital 14-bit I2C or SPI
Digital 24-bit I2C
Total Error Band
±1.0% FSO
±3.0% FSO Max
Type
Gage, absolute
Absolute, sealed gage
Pressure Range
0 - 0.35, 1, 2, 3, 7, 10, 14, 20 bar /
0 - 5, 15, 30, 50, 100, 150, 200, 300 psi (85BSD)
0 - 0.07, 0.14, 0.35, 1, 2, 3, 7, 10, 14, 20 bar /
0 - 1, 2, 5, 15, 30, 50, 100, 150, 200, 300 psi (86BSD)
0 - 6, 12, 18, 28, 30 bar /
0 - 87, 174, 261, 406, 435 psi
Overpressure
2X
2X
Operating Temp.
-40°C to 125°C
-40°C to 85°C
Dimensions (mm)
Ø 15.9 x 7.9 (85BSD), Ø 15.9 x 9.3 (86BSD)
Ø 9.0 x 7.5
Typical Apps
Level controls, tank level measurement, corrosive fluids and gas
measurement systems, sealed systems, submersible depth monitoring
Level controls, tank level measurement, corrosive
fluids and gas measurement systems, sealed systems,
manifold pressure measurement, dive computers
Media Isolated Modules
Analog Output
Transducers and Transmitters
Industrial
U86B
MSP100
Package
Mountable with O-ring seal
Small housing with O-ring and proprietary ‘snap-in’ feature that lowers
the total installed cost and customized housings for OEM applications
Type
Sealed gage, absolute
Gage
Pressure Range
0 - 5, 10, 12, 13 bar /
0 - 50, 100, 150, 200 psi
0 - 7 bar thru 0 - 34 bar /
0 - 100 psi thru 0 - 500 psi
Output/Span
0.5 - 4.5 VDC (Ratiometric output)
100 mV typical
Unique Features
• Amplified
• Microfused technology
• Low cost stainless steel isolated transducer
• No threads needed for pressure connect
• Highly customized for OEM application
• Solid state reliability
Accuracy
±0.5% span
±0.5% FSO
Operating Temp.
-7°C to 105°C
0°C to 55°C
Dimensions (mm)
Ø 15.82 x 13.6
Socket spacing: 31.75
12.7 x 24.38 x 20.32
Typical Apps
Liquid level, liquid pressure
Beverage dispensing systems, automation,
HVACR controls, energy and water
management, pumps, compressors, pneumatic equipment
SENSOR SOLUTIONS /// HVACR
TE SENSOR SOLUTIONS FOR HVACR
TEMPERATURE SENSORS
Sensor Assemblies
Push-in Sensors
Screw-in Sensors
Refrigeration Molded Sensors
Package
Brass, copper or stainless
steel closed-end tube
Brass, copper or stainless steel housing
with integrated connector
PVC or TPE
Type
Epoxy potted element, miniature design
Epoxy potted element, rigid sheath
Overmolded
Sensor Range
• NTC
• RTD: Pt, Ni
• Thermocouple: Type J, K, T, E
• NTC
• RTD: Pt, Ni, Cu
• Thermocouple: Type J, K, T, E
• NTC
• RTD: Pt
Unique Features
• High moisture resistant
• Available with mounting tabs or clips
• Moisture resistant
• Different threads types
• Connectors available
• High moisture resistant
Accuracy
• NTC: Custom tolerances available
• Pt RTD: Class AA, A, B
according to IEC60751
• NTC: Custom tolerances available
• Pt RTD: Class AA, A, B
according to IEC60751
• NTC: Custom tolerances available
• Pt RTD: Class AA, A, B
according to IEC60751
Operating Temp.
Varies: -50°C to 250°C
Varies: -50°C to 250°C
-40°C to 125°C
Dimensions (mm)
Case specific dimensions
Custom lengths, diameters and
threads available
8 x 30, 6.5 x 25, 6 x 50, 6 x 5 x 15
Typical Apps
Boiler, liquid, evaporator, HVACR,
industrial processes control, district
heating/cooling, gear boxes
Boiler, liquid, industrial processes control,
district heating/cooling, immersion
Industrial processes control
Sensor Assemblies
Boiler Sensors
Air Temperature Sensors
Pipe Mount Sensors
Package
Brass housing
Flange mount, snap-in, ring terminal
Copper or stainless steel housing
Type
• Screw
• Epoxy potted element with rigid sheath
or with snap-in ring and overmold
• Overmolded
• Epoxy potted
Sensor Range
• NTC
• RTD: Pt, Ni, Cu
• NTC
• RTD: Pt
• NTC
Unique Features
• Integrated connector
• Moisture resistant
• Different threads types
• Connectors available
• Easy mounting features
• Moisture resistant designs
• Fast response time
• Excellent thermal tracking
• Fast response time
• Moisture resistant construction
Accuracy
• NTC: Custom tolerances available
• Pt RTD: Class AA, A, B
according to IEC60751
• NTC: Custom tolerances available
• Pt RTD: Class A, B or custom
• NTC: Custom tolerances available
Operating Temp.
Varies: -50°C to 250°C
-40°C to 105°C or higher
-40°C to 125°C
Dimensions (mm)
Custom lengths, diameters
and threads available
Varies by design
Custom configurations available
Typical Apps
Boiler control, liquid, industrial processes
control, district heating and cooling, immersion
Cabinet air, leaving air, duct air, VAV air,
inlet/outlet air, room air, outside air
Industrial process, boiler control,
refrigeration, food service, energy
management, test equipment
PAGE 7
TE SENSOR SOLUTIONS FOR HVACR
TEMPERATURE SENSORS
Sensor Assemblies
Handy Box Sensors
Motor Temperature Sensors
Package
Duct mount or metal housing with PVC sun shield
with or without weatherproof box
Epoxy case or plastic tube with PTFE extension leads
Type
Fully potted subassembly
Epoxy potted element
Sensor Range
• NTC
• RTD: Pt
• NTC
• RTD: Pt, Ni-Fe (Other options also avaialbe on request)
Unique Features
• Easy mounting features
• Moisture resistant designs
• Fast response time
• Excellent thermal tracking
• Very rugged design
• Epoxy case design provides rigidity and electrical isolation
• Withstand varnish and bake operations with hermetic motors
• PTFE insulated lead wires for extended temp range
Accuracy
• NTC: Custom tolerances available
• Pt RTD: Class A, B or custom
• NTC: Custom tolerances available
• Pt RTD: Class A, B or custom
Operating Temp.
-40°C to 105°C
High temp. models also available
-40°C to 175°C
High temp. models also available
Dimensions (mm)
Varies by design
Varies by design
Typical Apps
Residential and commercial building controls,
energy management systems
Hermetic motor winding, general purpose motor winding
Sensing Elements—NTC, RTD
Radial Leaded Thermistors
Axial Thermistors
Package
Radial, beads
DO-35
Wired component
Type
• NTC
• Epoxy or glass coated
• NTC
• Glass coated
• RTD thin film platinum deposited on
ceramic substrate, glass coated
• Tube outline available
• Connection via radial leads
Resistance Range
100 to 1M
5k to 100k
100, 1000 (Other values on request)
Unique Features
• Interchangeable
• Moisture resistant
• Stability
• UL/CSA certified models available
• Tight tolerance (±1%)
• Max stability using high density (HD) chip
• Hermetically sealed
• Tinned and nickel plated leads
• Long term stability
• Interchangeability
• Small dimensions
• Short response time
• High electrical insulation
Accuracy
0.25% to 20%
±1% to ±3%
Class T (F0.1), A (F0.15), B (F0.3)
according to DIN EN 60751
Operating Temp.
-55°C to 280°C
-40°C to 300°C
-50°C to 600°C (Standard)
Down to -200 °C or up to 1000 °C (On request)
Dimensions (mm)
0.4 to 4.9
2.0 x 4.0 body
2.0 x 2.3 x 1.1 (Standard)
1.2 x 4.0 x 1.1 (Standard)
Other dimensions (On request)
Typical Apps
Environmental temperature, general purpose
sensing element for HVACR applications
Refrigeration including cabinet sensing and
evaporator coil, fire detection units, air-conditioning
systems, PCB temp sensing, general purpose
sensing element for HVACR applications
General purpose sensing element
for HVACR applications (Element
selection will depend upon many
factors including accuracy, temperature
range and mounting configuration)
SENSOR SOLUTIONS /// HVACR
Platinum Thin Film Sensors
TE SENSOR SOLUTIONS FOR HVACR
TEMPERATURE SENSORS
Sensing Elements—Digital Output
Thermopiles
TSYS Series
TSEV
Single or multi pixel series
Package
QFN16, TDFN8
OEM-module
Type
I2C, SPI, PWM, SDM
(Convertible to analog voltage)
Single pixel or multi pixel thermopile module
Temp. Range
—
Object temperature range 0°C to 300°C
(Other temperature ranges available upon request)
Unique Features
• Low power
• Small size
• Calibrated and ready to use
• 16 bit resolution
• Calibrated, interfaces: I2C, SPI
• Different field of views: 5° at 50%, 10° at
50%, 90° at 50%, others on request
Accuracy
Up to ±0.1°C at -5°C to 50°C
Depends on temperature range,
typical 1% full scale, max. accuracy 0.1°C
Operating Temp.
-40°C to 125°C
Ambient temperature range: 0°C to 85°C
Dimensions (mm)
QFN16: 4 x 4 x 0.85
TDFN8: 2.5 x 2.5 x 0.75
35 x 25 x 13 to 31
Typical Apps
Industrial control, replacement of precision RTDs,
thermistors and NTCs, heating and cooling systems
Contactless temperature measurement on moving parts,
heated rolls, microwave oven, air conditioner
HUMIDITY SENSORS
HTU2X Series
HTU3535PVBM/Wire
HS1101LF
HTG351xCH
HTF3000LF
Package
DFN type
Cost effective small
size mini-module
Through hole with side
opening plastic cap
Cost effective small
size mini-module
PCB for board to board
Type
Digital RH and temperature
Analog or digital voltage
RH and NTC temperature
Capacitive humidity
Analog voltage RH and
NTC temperature
Frequency output for RH,
direct NTC for temperature
Operating Range
0 to 100% RH
0 to 100% RH
0 to 100% RH
0 to 100% RH
0 to 100% RH
Operating Temp
-40°C to 125°C
-40°C to 110°C
-60°C to 140°C
-40°C to 110°C
-40°C to 85°C
Unique Features
• Low power consumption
• Fast response time
• I2C interface or PWM
interface or SDM
interface
• PTFE filter (Optional)
• Electronics fully
protected (5 V)
• Multiple connector
choices
• Based on HTU21
• Very robust and
recognized component
capable of withstanding
most of the applications
in the humidity world in
very cost effective ways
• Electronics fully
protected with potting
material (3.3 V or 5 V)
• Multiple connector
choices
• Voltage supply
from 3 to 8 VDC
• Through hole or SMD
• T and R available
Calibration
±3% RH at 25°C
(10 to 95% RH)
±0.3°C at 25°C
±3% RH at 55% RH;
±0.25°C at 25°C
180 pF, ±3 pF at 55% RH
±3% RH at 55% RH;
±0.25°C at 25°C
±3% RH at 55% RH
±0.25°C at 25°C
Dimensions (mm)
3.0 x 3.0 x 1.0
27 x 11.9 x YY (Depending
on the connector, from
6 to 10.8 mm length)
10 x 10 x 19
27 x 11.9 x 6.7
12.5 x 18.5 x 11.2
Typical Apps
Building automation
systems, thermostats,
humidifiers, dehumidifiers
Building automation
systems, thermostats,
humidifiers, dehumidifiers
Building automation
systems, thermostats,
humidifiers, dehumidifiers
Building automation
systems, thermostats,
humidifiers, dehumidifiers
Building automation
systems, thermostats,
humidifiers, dehumidifiers
PAGE 9
TE SENSOR SOLUTIONS FOR HVACR
POSITION SENSORS
KMA36
PCI-650 Series
RVIT-Z
Type
• TSSOP
• Magnetic rotary position
sensor, angle sensor
• Stainless steel
• Linear position transducer, absolute
• PCB for OEM volumes
• Angular position transducer,
inductive, absolute
Linearity
—
±1%
±0.5%
Excitation
—
12 to 28 VDC
DC Voltage
Range
360° angle
11, 40, 70, 85, 100mm
Up to ±75°
Unique Features
• Low cost MR encoder for rotational
and incremental measurements
• ATEX certification
• Vibration and shock resistant
• 100 bar operation
• Compatible with refrigerants
(Incl. ammonia) and compressor oils
• Absolute position
Output
Voltage 0 - 5 V, I2C, customer specific
4 to 20mA
DC voltage, DC current, digital
Resolution
Typ. 0.1°
Infinite
Infinite
Accuracy
Typ. 0.3°
—
—
Operating Temp
-25°C to 85°C
-40°C to 120°C
-25°C to 85°C
Dimensions (mm)
TSSOP20: 6.5 x 6.4 x 1.2
—
Custom
Typical Apps
Knobs, small robotics, angular and linear
position, flap location, louver control
Refrigerant compressor capacity control
valves, refrigerant compressor oil systems
Viscometers, valve position,
robotics, HVACR vane position
VIBRATION SENSORS
DC and Piezoelectric Accelerometers
808/808M1
810M1
MiniSense 100
LDTC Family
8011/
8021-AR/AP
8032-01
4020/4030
Package
TO-8
Board level
Piezo film elements with
or without mass and pins
Stainless steel
Stainless steel
Molded plastic
Type
Adhesive
(Stud mount option)
SMD
Cantilever beam with
vertical or horizontal pins
Stud/through
hole mount
Stud mount
Screw mount
F.S. Range (g)
±10, 50 (808)
±4, 20 (808M1)
±25, 100
±10 (Typical)
±5 to ±50
±50 to ±500
±2
Unique Features
• Hermetically sealed
• Case grounded
design
• Bandwidth to 8 kHz
• Small size, low cost
• Dynamic response
• 6 kHz bandwidth
• Very low cost
• High sensitivity (1 V/g)
• Ultra-low power
(Self generating)
• Industrial
accelerometer
• Case isolated,
internal shielding
• ±50, 20, 10,
5 g ranges
• Industrial
accelerometer
• Case isolated,
internal shielding
• Low cost
• Molded strain relief
• Low cost
• Biaxial, with
triaxial option
• DC response
• Rugged
construction
Accuracy
±1.0% Non-linearity
±2.0% Non-linearity
±20.0% (typical)
±1.0% Non-linearity
±1.0% Non-linearity
±1.0% Non-linearity
Operating Temp
-50°C to 100°C
-40°C to 70°C
-40°C to 85°C
-55°C to 100°C
-40°C to 85°C
Dimensions (mm)
Ø 15.2 x 16.6
12.70 x 15.24
19.05 x 6.35 x 6.35
22.23 x 48.26
14.3 x 45.3
71.2 x 40.0 x 15.2
Typical Apps
Machine monitoring,
data loggers,
embedded
applications
Data logging,
impact detection
Wake-up switch, load
imbalance, impact
sensing
Industrial
applications, machine
monitoring
Industrial applications,
machine monitoring
Structural monitoring
SENSOR SOLUTIONS /// HVACR
-40°C to 125°C
TE SENSOR SOLUTIONS FOR HVACR
FLOW SENSORS
ULTRASONIC SENSORS
Standard Contact Point Level
FS-01
Package
Noryl
Type
Flow switch
Max Pressure
10 Bar at 20°C
Operating Temp
-30°C to 85°C
Unique Features
LL-01
Type
Gap
Unique Features
• SPST reed switch
• Normally open, close on flow
• All 316L SS
• Integral electronics
• Miniature threads
• Single machined
• No adjustment for viscosity, density
Input
6 - 24 VDC
Dimensions (mm)
106 x 32 x 32
Output
1/2A contact
Typical Apps
For direction of liquid and gas flow, mains water
control, power shower, central heating systems,
circulation pump protection, cooling systems
Pressure
250 psi
Temperature
100°C
Actuation point
0.25"
Process
Connection
1/4" NPT or 1/2" NPT
Cable
12"
Approvals
CE
Typical Apps
Histology processors, compressors, chillers,
coolant reservoirs
MASS AIR FLOW SENSORS
LMM-H03
LMM-H04
Package
Hybrid
Hybrid
Type
Hot film anemometer component
Hot film anemometer component
Range
Bi-directional
Uni-directional
Operating Temp
-40°C to 125°C
-40°C to 125°C
Unique Features
• High sensitivity at low
heater temperatures
• Fast response time
• True air temperature sensor
• High sensitivity at low
heater temperatures
• Fast response time
• True air temperature sensor
Calibration /
Accuracy
Dependent on electronics
Dependent on electronics
Dimensions (mm)
23 x 10.15 x 1.1
24 x 10.15 x 1.1
Typical Apps
Industrial gas flow
Industrial gas flow
PAGE 11
Alternative Energy and Solar
Boiler Controls
Building and Energy Management
Cold Beverage Dispensing
Commercial Chillers
•
•
Commercial Cooking Equipment
Compressors and Motors
Container Storage
Electronic Expansion Valves
Forced Air Furnaces
Heat Pumps
•
•
•
•
•
Humidifiers and Dehumidifiers
HVACR Diagnostic Equipment
Ice Machines
PTAC and Small A/C
Pool Heater and Equipment
•
•
•
•
Refrigerators
Refrigerated Beverage Control
Refrigeration Controls
•
•
Underfloor Heating and Ice Melting
VAV Systems and Air Handlers
•
Water Heater
Zone Controls
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Ultrasonic
Mass Air Flow
Flow
Vibration
Position
Humidity
Temperature
Pressure
PRODUCT AND
APPLICATION MATRIX
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
te.com/hvacrsensorsolutions
© 2015 TE Connectivity. All Rights Reserved.
Microfused, UltraStable, Measurement Specialties, TE Connectivity, TE, and the TE connectivity (logo) are
•
•
TE SENSOR SOLUTIONS
For More Information Contact
TE Connectivity
trademarks of the TE Connectivity Ltd. family of companies. Other logos, product and company names mentioned
herein may be trademarks of their respective owners.
te.com/sensorsolutions-contact
While TE has made every reasonable effort to ensure the accuracy of the information in this brochure, TE does
not guarantee that it is error-free, nor does TE make any other representation, warranty or guarantee that the
information is accurate, correct, reliable or current. TE reserves the right to make any adjustments to the information
contained herein at any time without notice. TE expressly disclaims all implied warranties regarding the information
contained herein, including, but not limited to, any implied warranties of merchantability or fitness for a particular
purpose. The dimensions in this brochure are for reference purposes only and are subject to change without notice.
Specifications are subject to change without notice. Consult TE for the latest dimensions and design specifications.
SS-TS-HV100 09/2015
SENSOR SOLUTIONS /// HVACR
www.te.com
www.meas-spec.com