Spec Sheet MTU 6R0185 GS200 (200 kW Standby)

GAS GENERATOR SET
MTU 6R0185 GS200
200 kWe /60 Hz /Standby
208 - 600V
Reference MTU 6R0185 GS200 (175 kWe) for Prime Rating Technical Data
SYSTEM RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
Natural Gas
Ratings: Amps
Natural Gas
Ratings: kW/kVA
LP Gas
Ratings: Amps
LP Gas
Ratings: kW/kVA
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
240V**
1
1
60
240V**
1
1
60
208V**
3
0.8
60
240V**
3
0.8
60
480V**
3
0.8
60
600V**
3
0.8
60
750
750
694
601
300
240
180/180
180/180
200/250
200/250
200/250
200/250
541
541
451
390
195
156
130/130
130/130
130/162
130/162
130/162
130/162
425
433CSL6216
130 °C/40 °C
370
432PSL6228
130 °C/40 °C
608
432CSL6210
130 °C/40 °C
608
432CSL6210
130 °C/40 °C
809
432CSL6210
130 °C/40 °C
720
432PSL6246
130 °C/40 °C
12 LEAD ZIG-ZAG
4 LEAD
12 LEAD LOW WYE
12 LEAD HI DELTA
12 LEAD HI WYE
4 LEAD WYE
* Consult the factory for alternate configuration.
** UL 2200 Offered
CERTIFICATIONS AND STANDARDS
// Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
// UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified
// Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
// Power Rating
- Accepts Rated Load in One Step Per NFPA 110
2
/ // /
MTU 6R0185 GS200 (200 kWe) - Standby
STANDARD FEATURES*
// // // // // // // // MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
11.1 L Turbo Engine Charge Air Cooling
- 11.1 Liter Displacement
- 4-Cycle
3-Way Catalyst
Optional Fuel System: NG and LP Vapor Dual Fuel
Engine-generator resilient mounted
Complete Range of Accessories
Generator
- Brushless, Rotating Field Generator
- 2/3 Pitch Windings
- 300% Short Circuit Capability with Optional PMG
// Digital Control Panel(s)
- UL Recognized, CSA Certified, NFPA 110
- Complete System Metering
- LCD Display
// Cooling System
- Integral Set-Mounted
- Engine Driven Fan
// STANDARD EQUIPMENT*
// Engine
Air Cleaner
Oil Pump
Oil Drain Extension & S/O Valve
Full Flow Oil Filter
Jacket Water Pump
Thermostats
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 24V
Governor – Electronic Isochronous
Base - Formed Steel
SAE Flywheel & Bell Housing
Charging Alternator - 24V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
// Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Self Ventilated and Drip-proof
Superior Voltage Waveform
Solid State, Volts-per-hertz Regulator
±1% Voltage Regulation No load to full load
Brushless Alternator with Brushless Pilot Exciter
4 pole, Rotating Field
130 °C Maximum Standby Temperature Rise
1 Bearing, Sealed
Flexible Coupling
Full Amortisseur Windings
125% Rotor Balancing
3-phase Voltage Sensing
100% of Rated Load - One Step
5% Maximum Total Harmonic Distortion
// Digital Control Panel(s)
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
SAE J1939 Engine ECU Communications
Windows®-Based Software
Multilingual Capability
Remote Communications to RDP-110 Remote Annunciator
Programmable Input and Output Contacts
UL Recognized, CSA Certified, CE Approved
Event Recording
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Compatible
* Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional configurations.
3
/ // /
MTU 6R0185 GS200 (200 kWe) - Standby
APPLICATION DATA
// Engine
Manufacturer
Model
Type
Arrangement
Displacement: L (in3)
Bore: cm (in)
Stroke: cm (in)
Compression Ratio
Rated RPM
Engine Governor
Maximum Power (NG): kWm (bhp)
Maximum Power (LP): kWm (bhp)
Speed Regulation
Air Cleaner
// // Doosan
11.1L CAC
4-Cycle
6-Inline
11.1 (673)
12.3 (4.84)
15.5 (6.1)
10.5:1
1,800
Bosch
225 (302)
155 (208)
±0.5%
Dry
At 100% of Power Rating: m3/hr (ft3/hr)
At 75% of Power Rating: m3/hr (ft3/hr)
At 50% of Power Rating: m3/hr (ft3/hr)
// LPG
19.9 (704)
17 (600)
11.5 (404)
Cooling - Radiator System
NG and LPG
50 (122)*
Ambient Capacity of Radiator: °C (°F)
Maximum Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: kPa (in. H20)
Water Pump Capacity: L/min (gpm)
Heat Rejection to Coolant: kW (BTUM)
Heat Radiated to Ambient: kW (BTUM)
Fan Power: kW (hp)
0.12 (0.5)
310 (82)
194.6 (11,071)
40.4 (2,295)
10.4 (13.9)
28.5 (8)
25 (5.5)
149 (32.8)
* Installation of enclosures reduces the ambient capacity of the cooling
system by 1 °C (1.8 °F). Gravity exhaust louvers reduce ambient
capacity of the cooling system by an additional 3 °C (5.5 °F).
// Air Requirements
Electrical
Electric Volts DC
Cold Cranking Amps Under -17.8 °C (0 °F)
// NG
59.9 (2,115)
46.7 (1,648)
32.8 (1,157)
Liquid Capacity (Lubrication)
Total Oil System: L (gal)
Engine Jacket Water Capacity: L (gal)
System Coolant Capacity: L (gal)
// Fuel Consumption (NG-1000 BTU/ft3 / LP-2500 BTU/ft3)
24
1,050
Fuel Inlet
Fuel Supply Connection Size
Fuel Supply Pressure: mm H20 (in. H20)
2” NPT
178–279 (7–11)
NG and LPG
11.7 (400)
Aspirating: *m3/min (SCFM)
Air Flow Required for Rad.
Cooled Unit: **m3/min (SCFM)
Remote Cooled Applications;
Air Flow Required for Dissipation
of Radiated Gen-set Heat for a
Max of 25 °F Rise: *m3/min (SCFM)
631 (22,300)
237 (8,365)
* Air density = 1.184 kg/m (0.0739 lbm/ft )
** At 0.25 kPa (1 in. H20) static pressure and 52 °C (125 °F) at radiator
3
// 3
Exhaust System
Gas Temp. (Stack): °C (°F)
Gas Volume at Stack
Temp: m3/min (CFM)
Maximum Allowable
Back Pressure: kPa (in. H20)
NG and LPG
694 (1,281)
38.8 (1,371)
2.5 (10.25)
4
/ // /
MTU 6R0185 GS200 (200 kWe) - Standby
WEIGHTS AND DIMENSIONS
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.
System
Open Power Unit (OPU)
Dimensions (L x W x H)
3,607 x 1,591 x 2,026 mm (142 x 62.6 x 79.75 in)
Weight (dry)
3,096 kg (6,258 lb)
SOUND DATA
Unit Type
Level 0: Open Power Unit dB(A)
Standby Full Load (NG)
86.3
Standby Full Load (LP)
86.1
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.
EMISSIONS DATA
Fuel Type
Natural Gas
Liquid Propane
THC + NOx
2.25
0.08
RATING DEFINITIONS AND CONDITIONS
CO
0.26
0.25
All units are in g/hp-hr and are EPA weighted cycle values.
Emission levels of the engine may vary with ambient
temperature, barometric pressure, humidity, fuel type and
quality, installation parameters, measuring instrumentation, etc.
The data was obtained in compliance with US EPA regulations.
C/F = Consult Factory/MTU Onsite Energy Distributor
N/A = Not Available
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
Ambient capability factor at 984 ft (300 m). Consult your
local MTU Onsite Energy Power Generation Distributor for
other altitudes.
// Standby ratings apply to installations served by a reliable
utility source. The standby rating is applicable to varying
loads for the duration of a power outage. No overload
capability for this rating. Ratings are in accordance with
ISO 3046-1, BS 5514, and AS 2789. Average load
factor: ≤ 85%.
// Deration Factor:
Production tolerances in engines and installed components
can account for power variations of ±5%. Altitude,
temperature and excessive exhaust and intake restrictions
should be applied to power calculations. Consult your
local MTU Onsite Energy Power Generation Distributor for
derations.
// © MTU Onsite Energy. Subject to alteration due to technological advances. OE 23 470 (72 3E) 2015-03
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.