New Product Liquid Leakage Sensor Amplifiers K7L Series Reliable Sensitive Liquid Sensors for Stable Detection of Liquid Chemicals with Low Conductivity and Water Leakage • New models available that are compatible with PushIn Plus Terminal Block Sockets. • UL listed when used with Push-In Plus Terminal Block Sockets. • Sensor disconnection detection (K7L-AT50D@/ -UD@). • Models for long-distance wiring to 400 m. • Ribbon Electrode Bands and Point Sensors available. K7L-AT50@ K7L-U@ K7L-@@B For the most recent information on models that have been certified for safety standards, refer to your OMRON website. Model Number Legend K7L-@@@@ @ @ (1) (2) (3) (1) (2) Symbol AT50 U Meaning Standard wiring distance Blank Long wiring distance Wiring distance (3) Symbol D Disconnection detection Not supported. Standard usage • Wiring cable: 50 m max. • Sensing Bands: 10 m max. Supported. Not supported. Long distance use • Total Length of Wiring Cable and Sensing Bands: 400 m max. Supported. Meaning No sensor disconnection detection Sensor disconnection detection Socket terminals (*1) Symbol Meaning Blank For Screw Terminal Block Socket B For Push-In Plus Terminal Block Socket Standards Model Screw Terminal Block P2RF-08/-08-E Push-In Plus Terminal Block P2RF-08-PU K7L-AT50 (*2) Screw Terminal Block P2RF-08/-08-E Push-In Plus Terminal Block P2RF-08-PU K7L-AT50D (*2) Screw Terminal Block P2RF-08/-08-E Push-In Plus Terminal Block P2RF-08-PU K7L-AT50DB K7L-U (*2) Screw Terminal Block P2RF-08/-08-E Push-In Plus Terminal Block P2RF-08-PU K7L-AT50B K7L-UB K7L-UD (*2) K7L-UDB *1. The applicable models of the K7L depend on the model of the Socket. If the correct Socket is not used, the K7L nameplate will be upside down. *2. The UL listing applies only when the Sensor is used in combination with a Push-In Socket (P2RF-08-PU). By itself, the K7L is UL recognized. 1 Liquid Leakage Sensor Amplifier/Liquid Leakage Sensor Amplifier with Disconnection Detection Function K7L-AT50@/AT50D@ Reliable Detection of a Wide Variety of Liquids Ranging from Water to Liquid Chemicals with Low Conductivity. Four Sensing Ranges Available. • New models available that are compatible with PushIn Plus Terminal Block Sockets. • UL listed when used with Push-In Plus Terminal Block Sockets. *1 *1. The UL listing applies only when the Sensor is used in • Provides stable detection of liquids with impedance as combination with a Push-In Plus Terminal Block Socket high as 50 MΩ using inter-electrode resistance detection. (P2RF-08-PU). Detection of IPA and pure water possible. By itself, the K7L is UL recognized. *2. For the K7L-AT50D. • Higher noise immunity with a noise canceller circuit *3. UL/CSA UL 508 connected to a 3-conductor cable. CAN/CSA C22.2 No.14 • Prevents electrode corrosion with an AC detection method. CE: EMI EN 55011 EMS EN 61000-6-2 • The power supply circuit and detection circuit are isolated, allowing several Amplifiers to be installed in the same place. • After a disconnection is detected, operating status is held to eliminate instability due to contact of the disconnected part. *2 • Series includes an Explosion-proof Barrier (Sold Separately) to enable usage in hazard atmospheres. • CE Marking and UL/CSA certification. *3 Refer to Safety Precautions on page 10. Features Sensing Bands boast high degree of chemical resistance. The K7L can be used in a wide range of applications, from semiconductor production installations to food-processing equipment. Inter-electrode Resistance Detection Noise Canceller Function (Patent Pending) Stable detection of liquids with impedances of up to 50 MΩ and common water. Four sensing ranges are available, ensuring detection suited to the application. The K7L incorporates a noise canceller circuit that uses a 3-conductor cable, ensuring a high level of noise immunity. Fresh water, pure water, distilled water, plating liquids, chemical liquids, IPA (isopropyl alcohol) AC Detection Method The K7L internally oscillates AC signals provided to the Sensing Band, protecting the Sensing Band from electric corrosion and ensuring safe operation. Oscillator Detector Current 2 Connecting cable K7L-AT50@/AT50D@ Multi-channel Applications Isolation between the power supply circuits and sensing circuits allows multiple channels to be installed in the same location. Detection of Condensation and Liquid Leakage at Semiconductor Production Installations Detection is also possible for condensation inside cleaning devices and liquid leaked to the surroundings. Sensing Band with Excellent Chemical Resistance SUS316 and polyethylene are used for the Sensing Band's core and sheath to ensure high resistance to both acidic and alkaline liquids. Detection of Liquid Leakage at Pipe Joints for Liquid Chemical Tanks Liquid leakage at a pipe joint can be detected by wrapping the Sensing Band around the joint. Liquid Leakage Detection for Measuring Baths in CMP Devices Liquid leaked to drain pans can be detected to prevent damage to devices and cleaning irregularities for wafers. Detection of Cleaning Fluid Level for Plating Devices The level of pure water is detected inside plating baths. High sensitivity allows high-accuracy control to prevent cleaning irregularities. Note: Be sure to ground the baths if two or more K7L Sensors are used in the same tank in an explosion-prevention area. Model Number Legend K7L-AT50 @ @ (1) (2) (1) (2) Symbol Blank D Meaning No sensor disconnection detection Sensor disconnection detection Symbol Blank B Meaning Ivory, Screw Terminal Block Socket Black, Push-In Plus Terminal Block Socket Note: If you want a Push-In Plus Terminal Block Socket, use the K7L-AT50@B. (The terminal arrangement of a Push-In Plus Terminal Block Socket is upside down in comparison with a Screw Terminal Block Socket.) 3 K7L-AT50@/AT50D@ Ordering Information Product name Model K7L-AT50 Liquid Leakage Sensor Amplifier *1 Amplifier K7L-AT50B K7L-AT50D Liquid Leakage Sensor Amplifier with Disconnection Detection Function *1 K7L-AT50DB F03-15 F03-16PE Sensing Band F03-16PT Sensors F03-16SF F03-16SFC F03-16PS Point Sensor (for K7L-AT50/AT50B) F03-16PS-F F03-25 F03-26PES Sensing Band Stickers Mounting Brackets and Stickers F03-26PEN F03-26PTN Socket *2 (for K7L-AT50/AT50D) Socket *2 (for K7L-AT50B/AT50DB) Point Sensor Mounting Brackets F03-26PS Round terminals can be used. P2RF-08 Round terminals cannot be used. P2RF-08-E Push-In Plus Terminal P2RF-08-PU Terminal Blocks F03-20 *1. Accessories are provided. Check the accessories listed in the specifications for details. *2. The applicable models of the K7L depend on the model of the Socket. If the correct Socket is not used, the K7L nameplate will be upside down. Characteristics Ambient temperature Operating: –10 to +55°C Ambient humidity Operating: 45% to 85% Insulation resistance 10 MΩ at 100 VDC between case and current-carrying parts Dielectric strength 1,000 VAC at 50/60 Hz for 1 min between case and current-carrying parts Power consumption 1 W max. Response time Operate: 800 ms max. Release: 800 ms max. When turning ON power: 2 s max. Weight Approx. 14 g Specifications Rated power supply voltage 12 to 24 VDC (Allowable voltage fluctuation range: 10 to 30 VDC) 0 Ω to 50 MΩ, variable Range 0: 0 to 250 kΩ. Range 2: 0 to 5 kΩ. Operate resistance Range 1: 0 to 600 kΩ Range 3: 0 to 50 kΩ Note: The range is set using the DIP switch on the side of the Sensor Amplifier. (Refer to DIP Switch Settings.) Set the corresponding pin of the DIP switch in the up position. (For range 0, set all 3 pins in the down position.) The adjuster (ADJUST) on the top of the Sensor Amplifier sets the resistance value for detection within the set range. It is factory-set to the upper limit. (Normally, the K7L can be used with the adjuster at this setting.) With any range, resistance values can be set from 0 Ω. Disconnection detection function * Detection signal: 10 VDC max., 200 ms Detection time: 10 s max. Recovery: Operation is recovered by resetting the power supply. Release resistance 105% min. of operate resistance NPN open-collector transistor output with 100 mA at 30 VDC max. for both liquid leakage detection and disconnection detection. Max. 30 VDC, 100mA Output configuration Note: If the rightmost pin of the DIP switch on the side of the Sensor Amplifier is set to the down position, the output turns ON when liquid is detected; if it is set to the up position, the output turns OFF when liquid is detected. Connecting cable: 50 m max. Sensing Band length: 10 m max. Wiring distance Accessories * For the K7L-AT50D. 4 Note: These values are possible on condition that a completely insulated 3-conductor VCT cable with a thickness of 0.75 mm2 and a dielectric strength of 600 V is used together with a Liquid Sensing Band specified by OMRON. (A 0.2-mm2 cable can also be used.) Terminal Block Screwdriver for ADJUST Terminator K7L-AT50/AT50B 1 1 --- K7L-AT50D/AT50DB 1 1 1 K7L-AT50D-S 1 1 --- K7L-AT50@/AT50D@ Nomenclature and DIP Switch Settings K7L-AT50/AT50D PW OMRON Corporation K7L-AT50 SENSOR RANGE MODE Power indicator (green) (Lit when power is supplied.) LIQUID LEAKAGE SENSOR Output indicator (red) (Lit when output is ON.) MODE(OUTPUT) NC NO Resistance adjuster OUT SENSOR RANGE ADJUST K7L-AT50B/AT50DB Output indicator (red) (Lit when output is ON.) Resistance adjuster Power indicator (green) (Lit when power is supplied.) Setting Sensing Range DIP switch Range number Sensing range DIP switch Output mode Range 0 0 to 250 kΩ Output OFF when liquid leakage/ Disconnection* detected Range 1 0 to 600 kΩ Output ON when liquid leakage/ Disconnection* detected Range 2 0 to 5 MΩ Range 3 0 to 50 MΩ * Disconnection detection is supported only by the K7L-AT50D/ AT50DB. Countermeasures Against Noise Noise Canceller Function for Highly Sensitive Impedance Detection Connected with 3-conductor Cable that Offsets Inductive Noise (Patent Pending) The K7L Liquid Leakage Sensor Amplifier detects liquids with impedance as high as 50 MΩ and connects to the Sensing Band through a cable that can be extended up to 50 meters. Countermeasures against external noise are especially important for the Sensing Band and connecting cable because they pick up external noise like an antenna. The K7L incorporates the noise canceller function described below. A VCT cable with three conductors (lines) is used. Line 1 is connected to the Sensing Band and line 2 is left open. Lines 1 and 2 are almost in the same position and thus will experience the same noise level. The K7L obtains the difference between these signals. This means that the noise signals in lines 1 and 2 are offset against each other and a reading for the signal, without inductive noise, can be made. K7L Signal transmission circuit Signal transmission line Sensing Band 4 2 3 Line 1 Line 2 Subtraction circuit Connecting cable Resistance measurement circuit 5 K7L-AT50@/AT50D@ Connections External Connections K7L-AT50/AT50B K7L-AT50/AT50B 5 4 6 Level input 1 3 7 Level input 2 2 8 4 3 2 OUT- 100 mA at 30 VDC max. Signal transmission 2 3 4 F03-20 Terminal Block OUT+ Open-collector output Connecting cable (0.2 mm2 min.) Sensing Band * Use a class 2 power supply for the DC power supply if UL/CSA or CE Marking compliance is required. 1 Note: Always use a 3-conductor cable for wiring and connect to terminals 2, 3, and 4 on the Unit. Connect the Sensing Band between terminals 2 and 4 or terminals 3 and 4. 12 to 24 VDC * Connection Examples Connection as an NPN Output 6 5 Load Connection as an PNP (Equivalent) Output 6 Load + 5 + Load power supply Load power supply K7L-AT50D/AT50DB Open-collector output (Bottom view) 100 mA at 30 VDC max. K7L-AT50D/AT50DB COM- Signal transmission 4 6 Level input 1 3 7 Level input 2 2 8 Connecting cable (0.2 mm2 min.) Sensing Band * Use a class 2 power supply for the DC power supply if UL/CSA or CE Marking compliance is required. 1 + F03-20T Terminator 2-4 (4-2) Common BURN OUT+ 5 4 3 2 Disconnection detection output OUT+ 2 3 4 F03-20 Terminal Block Liquid leakage detection output - Note: Always use a 3-conductor cable for wiring and connect to terminals 2, 3, and 4 on the Unit. Connect the Sensing Band between terminals 2 and 4 or terminals 3 and 4. 12 to 24 VDC * Stripping and Connecting Terminals 1. Cut into the Sensing Band approximately 4 to 6 cm in from the end as shown in the diagram below. 2. Strip away approximately the last 9 mm of the sheath to expose the core (SUS line). 3. To connect to the Terminal Block, push down the top of the terminal with a screwdriver* and insert the core from the side. More Sensing Bands can be connected simply by wiring in an arch shape. 4 to 6 cm 9 mm Insert Exposed part of core F03-20 Terminal Block Note: When you are finished working, sufficiently confirm that there is an electrical connection. * You can use a commercially available screwdriver, but we recommend either 1) a 210-350/01 Screwdriver or 2) a 209-132 Operating Tool from Wago. Information: //www.wago.com 6 K7L-AT50@/AT50D@ Functions Disconnection detection function (K7L-AT50D/AT50DB only) Operation While Monitoring for Liquid Leakage • Short-wave signals (2.5 VAC, 3.75 Hz) for liquid leakage detection are output from terminal 4 of the K7L. • When there is no liquid leakage, the liquid leakage detection signals that are output are interrupted by the Terminator and the core of the Sensing Band will form an open loop. Signals interrupted by Terminator. K7L 8 3 7 2 K7L 3 7 2 K7L 8 1 Operation at Disconnection Detection • If there is a disconnection, the signals will be interrupted at the place where the disconnection occurred, and will not return to the K7L. • If the signals do not return when the K7L is in disconnection monitoring mode, it will determine that a disconnection has occurred. The output indicator will flash, and the disconnection output will turn ON/OFF depending on the position of the DIP switch (right). Signals are interrupted where the disconnection occurred. 4 5 1 6 3 7 2 4 3 2 8 4 3 2 4 6 4 5 6 2 3 4 • When liquid leakage occurs within the sensing range, the liquid leakage detection signals output from terminal 4 are input to terminal 2 through the leaked liquid. • The voltage of the input signals will vary with the resistance of the leaked liquid. This voltage is compared with the detection level set at the K7L. • If the K7L determines from the comparison results that there is liquid leakage, the liquid leakage output will turn ON or OFF. (The output can be set to NO or NC operation.) The output indicator will turn ON and OFF together with the output. The indicator lights when the output turns ON. 4 3 2 Operation at Liquid Leakage Detection 5 Disconnection detection signals are not interrupted by the Terminator and return to the K7L. 10 VDC max., 200 ms 1 2 3 4 2 • Output of disconnection detection signals starts within 2 s of power being supplied to the K7L and is repeated at 7-s intervals. • Disconnection signals are DC signals of 10 V max. that are output for approximately 200 ms. During this time, the K7L is in disconnection monitoring mode, i.e. it monitors for disconnections only and the liquid leakage detection signals are stopped. • If there is no disconnection, the disconnection detection signals (10 VDC) that are output pass through the Terminator and return to the K7L. The K7L takes this as normal, i.e., there is no disconnection. 2 3 4 3 7 4 3 2 4 5 6 2 3 4 2.5 VAC (3.75 Hz) Operation While Monitoring for Disconnection K7L 8 1 Note: 1. Disconnection detection is only performed between terminals 2 and 4. Therefore, be sure to connect the Sensing Band between terminals 2 and 4. 2. The K7L will switch from liquid leakage detection to disconnection detection if either of the following conditions occur while liquid leakage is detected. 2-1. Disconnection occurs between the K7L and the place where liquid is leaked. 2-2. While liquid leakage is detected, disconnection occurs between the place where liquid is leaked and the Terminator (F03-20T) and, subsequently, the leaked liquid is removed (e.g., wiped up or dried). 3. During disconnection detection, liquid leakage will not be detected. Once disconnection has been detected, reset the power supply to stop disconnection detection. 7 K7L-AT50@/AT50D@ Dimensions (Unit: mm) Terminal Block * F03-20 Liquid Leakage Sensor Amplifier K7L-AT50/AT50D 29.1 3 5.8 3 23.1 17.5 5×3=15 2.5 25 3.2 12.8 5.8 17 3.2 46 3.5 Mounting Hole Dimensions 28.8 Two, M3 23±0.2 Liquid Leakage Sensor K7L-AT50B/AT50DB Terminator * F03-20T 24.1 3 18.1 Mounting Hole Dimensions 3 Two, M3 25 3.2 3.2 12.8 18±0.2 46 5.8 12.5 5.8 28.8 17 3.5 3.5 * The Terminal Block is made of nylon 66. Mount the Terminal Block in locations not subject to liquid chemicals using M3 screws. 8 K7L-AT50@/AT50D@ Track-mounted Sockets * P2RF-08-E Track-mounted Sockets * P2RF-08 (Round terminals can be used.) 7 35.5 71.5 max. 31.5 2 Terminal 4 dia. Arrangement 9.5 (TOP VIEW) 2 73 max. Terminal Arrangement (TOP VIEW) 1.5 48 max. M3 screws 2 3 dia. (21) (22) 3.5 dia. hole 39.5 6 3 5 4 85.5 max. 6 3 7 2 5 4 (11) (12) (24) (14) 35.5 Eight, M3.5 x 8 7 2 8 1 19.5 4 19.5 max. 30 max. 11.5 4 16 54 max. 8 (A1) (A2) 1 61 max. 84 max. (Including height of DIN track) Figures in parentheses indicate DIN standard numbers. Note: Secure the Sockets with M3 screws at a torque of 0.78 to 1.18 N⋅m. Note: Secure the Sockets with M3 screws at a torque of 0.78 to 1.18 N⋅m. * The applicable models of the K7L depend on the model of the Socket. If * The applicable models of the K7L depend on the model of the Socket. If the correct Socket is not used, the K7L nameplate will be upside down. the correct Socket is not used, the K7L nameplate will be upside down. Track-mounted Sockets P2RF-08-PU Terminal Arrangement/ Internal Connection Diagram (TOP VIEW) 56.5 max. 56.3 52.4 A2 (1) 28.1 27.6 A1 (8) (3) 90 max. 35.5 27.25 3.9 27.6 36.3 45 52.1 83 max. (3) 15.5 max. 12 (2) 14 (4) 22 (7) 24 (5) 11 (3) 21 (6) Note: The numbers in parentheses are traditionally used terminal numbers. Note: The applicable models of the K7L depend on the model of the Socket. If the correct Socket is not used, the K7L nameplate will be upside down. Liquid Leakage Point Sensor F03-16PS F03-16PS-F 8 10 Bottom View 2 Electrode Overall length 2,000 mm Sheath: Fluoroplastic, 0.66 dia. 32 dia. 5.5 dia. Conductor cross section: 0.079 mm2 2.6-dia. vinyl-insulated round cable with 2 conductors Point Sensor Mounting Bracket F03-26PS R5 10 19.2 1 24 8.85 1 3 R3 22.5 6 dia. 12 Glued surface * * Use a commercially available bonding agent for PVC. Do not use adhesive tape for securing. 9 K7L-AT50@/AT50D@ Mounting Methods Stud Screw Mounting Special Bracket Mounting 1. Securing the Sensor with a Nut 2. Securing the Sensor with a Wing Nut * * Use a commercially available bonding agent for PVC. Safety Precautions Warning Indications Application Precautions Indicates a potentially hazardous situation which, if not avoided, will result in minor or moderate injury, or may result in serious injury or death. Additionally there may be significant property damage. You must allow sufficient leeway in ratings and performance, and provide proper fail-safe or other safety measures when using these products in any of the following applications. Be sure also to consult with your OMRON representative before actually attempting any of these applications. Precautions for Safe Use Supplementary comments on what to do or avoid doing, to use the product safely. Precautions for Correct Use Supplementary comments on what to do or avoid doing, to prevent failure to operate, malfunction, or undesirable effects on product performance. 1. Applications under conditions or environments not specified in user documentation 2. Applications for nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, or safety equipment 3. Applications that may have a serious influence on lives and property and thus require particularly attention to safety WARNING Meaning of Product Safety Symbols Used for general prohibitions for which is no specific symbol. WARNING This product is not designed or rated for ensuring safety of persons either directly or indirectly. Do not use it for such purposes. Precautions for Safe Use Observe the following points to ensure safe operation. 1. Be sure to use a power supply voltage within the specified range. 2. Do not use the product in locations subject to flammable gases or combustible objects. 3. Insert the connection points into Sockets until the connection is locked securely. 4. Do not short-circuit loads connected to output terminals. 5. Be sure to connect the power supply with the correct polarity. Precautions for Correct Use Do not use the Encoder under ambient conditions that exceed the ratings. Installation Attach to a panel of thickness 1 to 5 mm. Do not install in the following locations. 1. Locations subject to shock or vibration 2. Locations where the temperature or humidity lies outside the specified range, or where condensation is likely to occur (To detect liquids with high impedances, do not use in locations with high humidity.) 3. Locations subject to dust 4. Locations subject to corrosive gases (particularly sulfide and ammonia gases) 5. Outdoors or locations subject to direct sunlight 6. Near devices that generate strong high-frequency noise (e.g., highfrequency welding devices etc.) 10 K7L-AT50@/AT50D@ Liquid Leakage Sensor Amplifier K7L Q&A Some questions that are frequently asked about the K7L are given below. Use this information when selecting a model. Q A Can one K7L Amplifier be used for detection in more than one place? Yes. By using Terminal Blocks to connect Sensing Bands in parallel, detection can be performed in more than place with only one K7L Amplifier. Q A K7L-AT50 Possible wiring distance for wiring cable. Can a different terminal block (e.g. a commercially available terminal block or a terminal block constructed by the user) be used instead of the one provided? Yes. When using another terminal block, however, be sure to check that all the terminals are mutually isolated, and that there is no danger of ground faults in connecting cables or Sensing Bands. Possible wiring distance for Sensing Band. 50 m max. 10 m max. K7L-AT50 Note: For explosion-proof areas, use F03-20 Liquid Leakage Sensor, which has been certified for intrinsic safety and explosionproof capability. Q Terminal Blocks Note: 1. When wiring, be sure not to exceed the maximum possible wiring distances for both the connecting cable and the Sensing Band. Exceeding these distances may lead to faulty operation. Connect one Sensing Band to each Terminal Block. 2. Not applicable to K7L-AT50D. A Can the K7L Amplifier detect pure water? Yes. Even pure water, which has a resistance exceeding 10 MΩ⋅cm, can nearly always be detected if the K7L is used at its maximum sensitivity. This is because impurities are mixed with the water when it is leaked and the resistance drops. K7L-U Impurities in the air 400 m max. Terminal Blocks Impurities on the drain pan K7L-U Q A Note: 1. When wiring, be sure not to exceed the maximum possible wiring distances for both the connecting cable and the Sensing Band. Exceeding these distances may lead to faulty operation. Connect one Sensing Band to each Terminal Block. 2. Not applicable to K7L-UD. Q A Pure water Detection possible if sensing range 3 (0 to 50 MΩ) is selected using the DIP switch. Can the K7L Amplifier detect oil? In most cases, no. If, however, it contains impurities such as metal powder, as is the case with cutting oil and used engine oil, detection may be possible (actual instances of detection have been observed). The user should confirm whether the required kind of detection is possible before application. Can the K7L Amplifier be used as a replacement for the 61F-GPN-V50 Water Leakage Detector? Yes. Because the surge withstand capability is different, however, do not use in locations where it will be exposed to impulses and surges, such as outdoor roofs or in pump panels. Also, items such as the power supply voltage and the connection sockets are different. Check these items before application. 11 Liquid Leakage Sensor Amplifiers for Long-distance Wiring K7L-U@/-UD@ Ultra-miniature Liquid Leakage Sensor Amplifier Enables Longest Liquid Leakage Monitoring Distance in Industry • New models available that are compatible with Push-In Plus Terminal Block Sockets. • UL listed when used with Push-In Plus Terminal Block Sockets. *1 • Stable detection of liquids with impedance as high as 1 MΩ using inter-electrode resistance detection. Detection of *1. The UL listing applies only when the Sensor is used in combination with a Push-In Socket (P2RF-08-PU). chemical liquids and pure water is possible. By itself, the K7L is UL recognized. • Higher noise immunity with a noise canceller circuit *2. For the K7L-UD. *3. UL: UL 508 connected to a 3-conductor cable. CAN/CSA C22.2 No.14 • Prevents electrode corrosion with an AC detection method. CE: EMI EN 55011 EMS EN 61000-6-2 • The power supply circuit and detection circuit are isolated, allowing several Amplifiers to be installed in the same place. • After a disconnection is detected, operating status is held to eliminate instability due to contact of the disconnected part. *2 • CE Marking and UL/CSA certification. *3 Refer to Safety Precautions on page 19. Features A total distance of 400 m is achieved for cable and Sensing Band to minimize leakage damage. Greatly expands the detection area. Detects broken wires. Broken wire signal Detects broken wires all the way from the main unit to the tip of the Sensing Band. This enhances reliability in long-distance wiring applications. A total distance of 400 m for the cable and Sensing Band extends the wiring distance by approximately 7 times compared with our previous models. Cable Industry's longest Breaks in wiring 4 3 2 3 2-4 (4-2) 2 Sensing Band 3 2 4 3 2 4 4 Terminal Block Sensing Band Total length of cable and Sensing Band is 400 m max. * According to an OMRON survey Helps to downsize gang-mounted panels. Terminal Block Terminator Cable Features a Noise Canceller (Patented) The extremely compact size, with a width of only 16 mm, helps to save panel size when mounting several Units together. A noise canceling circuit employing a three-conductor cable enables stable liquid leakage detection with excellent noise resistance. Connecting cable Only 192 mm for 12 Units Application Examples Floor or Ceiling of Semiconductor or Flat Panel Display Factory K7L-U(D) 12 Floor below Chemical Purification Tank K7L-U(D) K7L-U@/-UD@ Model Number Legend K7L-U @ @ (1) (2) (1) (2) Symbol Meaning Symbol Blank No sensor disconnection detection Blank D Sensor disconnection detection B Meaning Ivory, Screw Terminal Block Socket Black, Push-In Plus Terminal Block Socket Note: If you want a Push-In Plus Terminal Block Socket, use the K7L-U@B. (The terminal arrangement of a Push-In Plus Terminal Block Socket is upside down in comparison with a Screw Terminal Block Socket.) Ordering Information Characteristics Product name Liquid Leakage Sensor Amplifier *1 Amplifier Model K7L-U Liquid Leakage Sensor Amplifier *1 K7L-UB Liquid Leakage Sensor Amplifier with Disconnection Detection Function *1 K7L-UD Liquid Leakage Sensor Amplifier with Disconnection Detection Function *1 K7L-UDB F03-15 F03-16PE Sensing Band Sensors F03-16PT F03-16SF F03-16SFC Point Sensor (for K7L-U/UB) F03-16PS F03-16PS-F Ambient temperature Ambient humidity Operating: 45% to 85% Insulation resistance 10 MΩ at 100 VDC between case and current-carrying parts Dielectric strength 1,000 VAC at 50/60 Hz for 1 min between case and current-carrying parts Power consumption 1 W max. Response time Operate:800 ms max. Release:800 ms max. Startup time after power ON: 2 s max. Weight Approx. 14 g Ratings Rated power 12 to 24 VDC supply voltage (Allowable voltage fluctuation range: 10 to 30 VDC) 0 to 1 MΩ variable Operate resistance F03-25 Mounting Brackets and Stickers Track-mounted Socket *2 (for K7L-U/UD) Track-mounted Socket *2 (for K7L-UB/UDB) Terminal Blocks Sensing Band Stickers Operating: –10 to 55°C F03-26PES Note: The adjuster (ADJUST) on the top of the Sensor Amplifier sets the resistance for detection within the setting range. It is factory-set to the upper limit. (Normally, the K7L can be used with the adjuster at this setting.) F03-26PTN Disconnecti on detection function * Detection signal: 10 VDC max., 200 ms Detection time: 10 s max. Recovery: Operation is recovered by resetting the power supply. Point Sensor Mounting Brackets F03-26PS Release resistance 105% min. of operate resistance Round terminals can be used. P2RF-08 Round terminals cannot be used. P2RF-08-E Push-In Plus Terminal P2RF-08-PU F03-26PEN F03-20 *1. Accessories are available. Check the ratings for details. *2. The applicable models of the K7L depend on the model of the Socket. If the correct Socket is not used, the K7L nameplate will be upside down. NPN open-collector transistor output with 100 mA at 30 VDC max. for both liquid leakage detection and disconnection detection. Note: If the rightmost pin of the DIP switch on the side of the Output Sensor Amplifier is set to the down position, the output configuration turns ON when liquid is detected; if it is set to the up position, the output turns OFF when liquid is detected. Vibration resistance 10 to 150 Hz, 0.1-mm single amplitude with 15-m/s2 acceleration for 8 minutes 10 times each in X, Y, and Z directions Shock resistance 150 m/s2 3 times each in six directions on 3 axes Wiring cable Sensing Band Wiring distance } Product Name Accessories Total: 400 m max. Note: These values are possible on the condition that a completely insulated 3-conductor VCT cable with a thickness of 0.75 mm2 and a dielectric strength of 600 V is used together with the Liquid Sensing Band specified by OMRON. (A 0.2-mm2 cable can also be used.) Model Terminal Block Screwdriver for ADJUST Terminator F03-20 --- F03-20T K7L-U/UB 1 1 --- K7L-UD/ UDB 1 1 1 * For the K7L-UD. 13 K7L-U@/-UD@ Nomenclature and DIP Switch Settings K7L-U/UD Power indicator (green) (Lit when power is supplied.) Output indicator (red) (Lit when output is ON.) Resistance adjuster Sensing Range Settings DIP switch Output Output is OFF when liquid leakage or disconnection is detected. * K7L-UB/UDB Output is ON when liquid leakage or disconnection is detected. * Resistance adjuster * Disconnection detection is supported only by the K7L-UD/UDB. Output indicator (red) (Lit when output is ON.) Power indicator (green) (Lit when power is supplied.) Noise Countermeasures (Common) Noise Canceller Function for Highly Sensitive Impedance Detection Connected with 3-conductor Cable that Offsets Inductive Noise (Patent Pending) The K7L-U/UB Liquid Leakage Sensor Amplifier detects liquids with impedance as high as 1 MW and connects to the Sensing Band through a cable that can be extended up to 400 meters. Countermeasures against external noise are especially important for the Sensing Band and connecting cable because they pick up external noise like an antenna. The K7L incorporates the noise canceller function described below. A VCT cable with three conductors (lines) is used as shown in the diagram. Line 1 is connected to the Sensing Band and line 2 is left open. Lines 1 and 2 are almost in the same position and thus will experience the same noise level. The K7L detects the difference between these signals (including noise). This means that the noise signals in lines 1 and 2 are offset against each other and a reading for the signal, without inductive noise, can be made. K7L Sensing Band Signal transmission circuit Signal transmission line Line 1 Line 2 Connecting cable 4 2 3 Subtraction circuit Resistance measurement circuit 14 K7L-U@/-UD@ Connections K7L-U/UB K7L-U/UB Signal transmission 4 OUT- 100 mA at 30 VDC max. 6 Level input 1 3 7 Level input 2 2 8 Connecting cable (0.2 mm2 min.) 4 3 2 5 2 3 4 F03-20 Terminal Block OUT+ Open-collector output Sensing Band Example: F03-16PE * A Class 2 power supply must be used for the DC power supply to comply with UL standards. Note: Always use a 3-conductor cable for wiring and connect to terminals 2, 3, and 4 on the Unit. Connect the Sensing Band between terminals 2 and 4 or terminals 3 and 4. 1 12 to 24 VDC * Output Circuit Examples The NPN open-collector output of the K7L-U/UB is isolated from the internal circuits by a photocoupler, so you can use either an NPN opencollector output or a PNP (equivalent) output. NPN Output PNP (Equivalent) Output 6 5 Load Load power supply 6 5 Load Load power supply K7L-UD/UDB K7L-UD/UDB Terminal Block F03-20 5 Disconnection BURN OUT+ detection output COMCommon 6 Level input 1 3 7 Level input 2 2 8 4 1 Commercially available connecting cable (0.2 mm2 min.) Terminator F03-20T 2-4 (4-2) OUT+ Signal transmission 4 3 2 Liquid leakage detection output (Bottom View) 2 3 4 Open-collector output 30 VDC max. 100 mA Sensing Band Example: F03-16PE * A Class 2 power supply must be used for the DC power supply to comply with UL standards. Note: Always use a 3-conductor cable for wiring and connect to terminals 2, 3, and 4 on the Unit. Connect the Sensing Band between terminals 2 and 4 or terminals 3 and 4. 12 to 24 VDC * 15 K7L-U@/-UD@ Disconnection Detection Function (K7L-UD/UDB) Operation While Monitoring for Liquid Leakage Operation While Monitoring for Disconnection • Short-wave signals (2.5 VAC, 3.75 Hz) for liquid leakage detection are output from terminal 4 of the K7L. • When there is no liquid leakage, the liquid leakage detection signals that are output are interrupted by the Terminator and the core of the Sensing Band will form an open loop. 2.5 VAC (3.75 Hz) 2 2 3 4 3 7 Signals interrupted by Terminator. 4 3 2 4 5 6 • Output of disconnection detection signals starts within 2 s after power is supplied to the K7L and is repeated at approximately 7-s intervals. • Disconnection signals are DC signals of 10 V max. that are output for approximately 200 ms. During this time, the K7L is in disconnection monitoring mode, i.e. it monitors for disconnections only and the liquid leakage detection signals are stopped. • If there is no disconnection, the disconnection detection signals (10 VDC) that are output pass through the Terminator and return to the K7L. The K7L takes this as normal, i.e., there is no disconnection. K7L 2 6 3 7 2 K7L 8 1 Operation at Disconnection Detection 2 3 4 3 7 4 3 2 4 6 4 5 • When liquid leakage occurs within the sensing range, the liquid leakage detection signals output from terminal 4 are input to terminal 2 through the leaked liquid. • The voltage of the input signals will vary with the resistance of the leaked liquid. This voltage is compared with the detection level set at the K7L. • As a result of the comparison, if the K7L determines that liquid leakage has occurred, the K7L's output LED will light, and the liquid detection output will either turn ON or OFF. 4 3 2 Operation at Liquid Leakage Detection 5 Disconnection detection signals are not interrupted by the Terminator and return to the K7L. 10 VDC max., 200 ms 1 2 3 4 8 • If there is a disconnection, the signals will be interrupted at the place where the disconnection occurred, and will not return to the K7L. • If the signals do not return, it will determine that a disconnection has occurred. The output indicator will flash, and the disconnection output will turn ON/OFF. Signals are interrupted where the disconnection occurred. 1 4 5 6 3 7 2 4 3 2 8 2 3 4 K7L K7L 8 1 Note: 1. Disconnection detection is only performed between terminals 2 and 4. Therefore, be sure to connect the Sensing Band between terminals 2 and 4. 2. The K7L will switch from liquid leakage detection to disconnection detection if either of the following conditions occur while liquid leakage is detected. 2-1. Disconnection occurs between the K7L and the place where liquid is leaked. 2-2. While liquid leakage is detected, disconnection occurs between the place where liquid is leaked and the Terminator (F03-20T) and, subsequently, the leaked liquid is removed (e.g., wiped up or dried). 3. During disconnection detection, liquid leakage will not be detected. Once disconnection has been detected, reset the power supply to stop disconnection detection. Surges Use in conjunction with a 61F-03B/04B Surge Suppressor Unit in environments exposed to surges. Install the Surge Suppressor Unit near the K7L. The surge suppression may not be sufficient if the Surge Suppressor Unit is installed near the Sensing Band. 3 7 2 4 3 2 6 2 3 4 Induced lightening 4 5 61F-03B Electrode connection terminals 3 5 9 1 7 11 61F-04B Electrode connection terminals 3 4 8 9 1 6 7 11 K7L 8 1 61F-03B When using shield wire Ground Note: For details on Surge Suppressor Units, refer to your OMRON website. 16 Ground K7L-U@/-UD@ Dimensions (Unit: mm) Terminal Block * F03-20 Liquid Leakage Sensor Amplifier K7L-U/-UD 12.8 46 29.1 3 2 3 2 25 3.2 2 3 5.8 17.5 2.5 5×3=15 4 28.8 5.8 3 23.1 3 4 17 3.2 4 3.5 Terminator * F03-20T Liquid Leakage Sensor Amplifier K7L-UB/-UDB 24.1 3 3 18.1 Mounting Hole Dimensions 2-4 (4-2) 12.8 46 Two, M3 25 3.2 3.2 18±0.2 28.8 Track-mounted Sockets * P2RF-08 (Round terminals can be used.) 7 Track-mounted Sockets * P2RF-08-E 2 73 max. Eight, M3.5 × 8 35.5 71.5 max. 19.5 (21) 39.5 85.5 max. 6 3 7 2 5 4 (11) (12) (24) (14) 35.5 7 2 8 1 4 54 max. Note: The applicable models of the K7L depend on the model of the Socket. If the correct Socket is not used, the K7L nameplate will be upside down. 11.5 16 8 (A1) 61 max. 84 max. (Including height of DIN track) (A2) 1 Figures in parentheses indicate DIN standard numbers. Note: The applicable models of the K7L depend on the model of the Socket. If the correct Socket is not used, the K7L nameplate will be upside down. Terminal Arrangement/ Internal Connection Diagram (TOP VIEW) 56.5 max. 56.3 52.4 A2 (1) 28.1 27.6 A1 (8) (3) 90 max. 35.5 27.25 3.9 2 3 dia. 3.5 dia. hole 6 3 5 4 30 max. Front-mounting Sockets P2RF-08-PU 48 max. (22) 31.5 4 19.5 max. 1.5 M3 screws 2 Terminal 4 dia. 9.5 Arrangement (Top view) Terminal Arrangement (Top view) 27.6 36.3 45 52.1 83 max. (3) 15.5 max. Note: The applicable models of the K7L depend on the model of the Socket. If the correct Socket is not used, the K7L nameplate will be upside down. 12 (2) 14 (4) 22 (7) 24 (5) 11 (3) 21 (6) Note: The numbers in parentheses are traditionally used terminal numbers. * The Terminal Block is made of nylon 66. Mount the Terminal Block in locations not subject to liquid chemicals using M3 screws. 17 K7L-U@/-UD@ Liquid Leakage Point Sensor F03-16PS F03-16PS-F 8 10 Bottom View 2 Electrode Overall length 2,000 mm Sheath: Fluoroplastic, 0.66 dia. 32 dia. 5.5 dia. Conductor cross section: 0.079 mm2 2.6-dia. vinyl-insulated round cable with 2 conductors Point Sensor Mounting Bracket F03-26PS R5 10 19.2 1 24 1 R3 22.5 6 dia. * Secure the Sockets with M3 screws at a torque of 0.78 to 1.18 N·m. 18 12 8.85 3 K7L-U@/-UD@ Safety Precautions Warning Indications WARNING Indicates a potentially hazardous situation which, if not avoided, will result in minor or moderate injury, or may result in serious injury or death. Additionally there may be significant property damage. Precautions for Safe Use Supplementary comments on what to do or avoid doing, to use the product safely. Precautions for Correct Use Supplementary comments on what to do or avoid doing, to prevent failure to operate, malfunction, or undesirable effects on product performance. Application Precautions You must allow sufficient leeway in ratings and performance, and provide proper fail-safe or other safety measures when using these products in any of the following applications. Be sure also to consult with your OMRON representative before actually attempting any of these applications. 1. Applications under conditions or environments not specified in user documentation 2. Applications for nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, or safety equipment 3. Applications that may have a serious influence on lives and property and thus require particularly attention to safety Meaning of Product Safety Symbols Used for general prohibitions for which is no specific symbol. WARNING This product cannot be used as a detection device for protecting human life. Precautions for Safe Use Observe the following points to ensure safe operation. 1. Be sure to use a power supply voltage within the specified range. Not doing so may result in burning or malfunction. 2. Do not use the product in locations subject to flammable gases or combustible objects. Doing so may result in fire. 3. Insert the connection points into Sockets until the connection is locked securely. Not doing so may result in burning or malfunction. 4. Do not short-circuit loads connected to output terminals. Doing so may result in burning. 5. Be sure to connect the power supply with the correct polarity. Not doing so may result in malfunction. Precautions for Correct Use Installation Attach to a panel of thickness 1 to 5 mm. Do not install in the following locations. 1. Locations subject to shock or vibration 2. Locations where the temperature or humidity lies outside the specified range, or where condensation is likely to occur (To detect liquids with high impedances, do not use in locations with high humidity.) 3. Locations subject to dust 4. Locations subject to corrosive gases (particularly sulfide and ammonia gases) 5. Outdoors or locations subject to direct sunlight 6. Near devices that generate strong high-frequency noise (e.g., high-frequency welding devices etc.) 19 K7L-U@/-UD@ Liquid Leakage Sensor Amplifier K7L FAQs Some questions that are frequently asked about the K7L are given below. Use this information when selecting a model. Q A Can one K7L Amplifier be used for detection in more than one place? Yes. By using Terminal Blocks to connect Sensing Bands in parallel, detection can be performed in more than place with only one K7L Amplifier. Q A Total: 400 m max. Can a different terminal block (e.g. a commercially available terminal block or a terminal block constructed by the user) be used instead of the one provided? Yes. When using another terminal block, however, be sure to check that all the terminals are mutually isolated, and that there is no danger of ground faults in connecting cables or Sensing Bands. Terminal Block K7L-U Q A Note: 1. When wiring, be sure not to exceed the maximum possible wiring distances for both the connecting cable and the Sensing Band. Exceeding these distances may lead to faulty operation. Connect one Sensing Band to each Terminal Block. 2. Not applicable to the K7L-UD. Q A 20 Can the K7L Amplifier be used as a replacement for the 61F-GPN-V50 Water Leakage Detector? Yes. Because the surge withstand capability is different, however, do not use in locations where it will be exposed to impulses and surges, such as outdoor roofs or in pump panels. Also, items such as the power supply voltage and the connection sockets are different. Check these items before application. Can the K7L Amplifier detect pure water? Yes. Even pure water, which has a resistance exceeding 10 MWΩ ⋅cm, can nearly always be detected if the K7L is used at its maximum sensitivity. This is because impurities are mixed with the water when it is leaked and the resistance drops. Impurities in the air Pure water Inpurities on the drain pan Q A Can the K7L Amplifier detect oil? No. F03-16PE/-16PT/-15/-16PS Sensing Band/Point Sensor F03-16PE F03-16PT Liquid Leakage Sensing Band Fluoroplastic Sensing Band • SUS316 used for core and polyethylene used for sheath to ensure high • Compared to the F03-16PE (polyethylene), the F03-16PT has higher resistance to both acidic and alkaline liquids. • Sensing Band Stickers that use the same material as the Sensing Band's insulating resin are available in 2 types: adhesive-tape type and screw type. • Detection precision remains constant even with a loopback, thanks to a two- resistance to both high temperatures and chemicals. sided detection design. Ordering Information Ordering Information Name Name Model number Liquid Leakage Sensing Band Sensing Band Stickers Model number F03-16PE Fluoroplastic Sensing Band F03-16PT F03-26PES Fluoroplastic Sensing Band Stickers F03-26PTN Specifications F03-26PEN Specifications Sheath PTFE fluoroplastic Sheath Polyethylene Core SUS316 stainless steel Core SUS316 stainless steel Ambient operating temperature –50 to 200°C Ambient operating temperature –15 to 55°C Weight Approx. 16 g (1 m) Weight Approx. 16 g (1 m) Dimensions Sensing Band F03-16PE Dimensions Fluoroplastic Sensing Band F03-16PT (Unit: mm) (Unit: mm) Appearance Appearance 4 20 1.2 Structure 1.7 1.2 10 1.7 Structure 8 5 2.7 19/0.12x0.6t SUS316 Materials: Electrodes: SUS316 stainless steel, Sheath: Fluoroplastic Materials: Electrodes: SUS316 stainless steel, Sheath: Fluoroplastic Sensing Band Stickers F03-26PEN (screws) (Unit: mm) Fluoroplastic Sensing Band Stickers F03-26PTN (screws) Appearance 22 5 5 Appearance 32 6.5 Structure 1.0 3.0 6.5 Two, 3.5 dia. Cut section 25 Material: Polyethylene F03-26PES (adhesive tape) (Unit: mm) 12 Structure (Unit: mm) 15 Two, 3.5 dia. 3.0 Material: Fluoroplastic PTA Appearance 19.2 5 Structure 13 Adhesive tape * Material: Polyethylene * The shape of the adhesive tape shown above is for securing the F03-16PE. Chemical Resistivity Polye thylene SUS316 Fluoro plastic Polye thylene SUS316 Fluoro plastic Water A A A Toluene C B B Acetone C A A Phenol B A B Ammonia A A A Butanol B --- A Ethanol B A A Fluorine A C A Hydrochloric acid A C A Hexane C --- A Hydrogen peroxide solution A A A Benzene C A A Methanol B A A Xylene B A A Sulfuric acid C B A Cyclohexane C --- A Phosphoric acid A B B Trichloroethylene C A A Note: 1. The F03-16PE Sensing Band is made from the following materials. Core: SUS316 Insulated sheath: Polyethylene 2. In order to prevent secondary fire damage, consider the effect of the atmosphere of the environment and the solution to be detected on the Sensing Band. 3. If the Sensing Band changes shape or color when a liquid is detected, replace the Sensing Band. A: Not affected at all or only very slightly affected. B: Slightly affected but, depending on the conditions, sufficient for use. C: Affected but may still be used. (Replace the Sensing Band immediately after detection.) 21 F03-16PE/-16PT/-15/-16PS Indicates models that allow free cutting. F03-15 F03-16PS Sensing Band Liquid Leakage Point Sensor • Ideal for harsh electrical room environments that are dusty and humid. • For installation in locations requiring insulated materials. Ordering Information Name Model number Liquid Leakage Sensing Band F03-15 Sensing Band Stickers F03-25 • • • • Can be used in conjunction with Sensing Bands. Stud screw mounting requires no tools for installation. No tools means the Sensor can be wiped clean quickly and easily. The optional Mounting Bracket enables faster installation than three-screw mounting. • Connect multiple Sensors to one K7L Amplifier for significant cost savings. Ordering Information Specifications Sheath Name Flexible, transparent vinyl chloride Model number F03-16PS Core SUS304 stainless steel Liquid Leakage Point Sensor Ambient operating temperature −15 to 50°C Mounting Brackets *2 F03-26PS Weight Approx. 48 g (1 m) Terminal Block *3 F03-20 Dimensions Sensing Band F03-15 (Unit: mm) F03-16PS-F *1 *1. The electrodes have a fluorine coating. *2. Use a commercially available bonding agent for PVC. One bag contains 10 Brackets. *3. One bag contains 10 Blocks. Specifications Appearance Material Electrode pairs Structure Conductors (Stainless steel wire 0.3 mm x 12-wire braided cable) 8 25 Flexible, transparent vinyl chloride 333 (3 pairs/m) Sensing Band Stickers F03-25 (Unit: mm) Appearance (0.5) (5) Structure Polyethylene Conductor Outer sheath: PVC, Inner sheath: Fluorine resin Core F03-16PS: SUS304 stainless steel F03-16PS-F: SUS304 and fluorine coating Ambient operating temperature range −10 to 60°C Weight Approx. 30 g Maximum number of Point Sensors connected per Amplifier You can use as many Point Sensors as required as long as the following conditions are met. K7L-AT50 (K7L-AT50D cannot be used): 60 m max. K7L-U (K7L-UD cannot be used): 400 m max. 61F-WLA or 61F-GPN-V50: 200 m max. Wiring Diagram 25±2 (3) Sensor Amplifier 15±1 Adhesive tape (1) Material: SUS304 Any number of Sensors can be connected in parallel as long as the following cable lengths are not exceeded for the Sensing Bands and connecting cables. K7L-AT50 (operate resistance of 50 MW max.): 60 m max. K7L-U (operate resistance of 1 MW max.): 400 m max. However, the leakage areas cannot be determined with the K7L-AT50. 5 6 7 4 3 2 8 1 4 3 2 4 3 2 4 3 2 4 3 2 4 3 2 4 3 2 Liquid Leakage Point Sensor F03-16PS Liquid Leakage Sensor Amplifier K7L-AT50 or K7L-U Liquid Leakage Point Sensor F03-16PS Sensing Band Terminal Block F03-20 K7L-AT50 K7L-U : Total length of 60 m max. (Sensing Bands: 10 m max.) : Total length of 400 m max. Dimensions Refer to pages 17 and 18. 22 F03-16PE/-16PT/-15/-16PS Connecting the Sensing Band Connecting F03-20 Terminal Blocks and Sensing Cables The F03-20 Terminal Block is provided to connect the connecting cable from the K7L Liquid Leakage Sensor Amplifier to a Sensing Band in a liquid detection application. Stripping and Connecting Terminals 1. Cut into the Sensing Band approximately 4 to 6 cm in from the end as shown in the diagram below. 2. Strip away approximately the last 9 mm of the sheath to expose the core (SUS line). 3. To connect to the Terminal Block, insert the screwdriver * from the top of the Terminal Block and insert the stripped end of the core from the side. (Refer to Dimensions on page 17.) 4 to 6 cm 9 mm Insert Exposed part of core F03-20 Terminal Block Note: Check that the wiring is secure before using the K7L in applications. * You can use a commercially available screwdriver, but we recommend either 1) a 210-350/01 Screwdriver or 2) a 209-132 Operating Tool from Wago. Information: //www.wago.com When you install a Sensing Band, use Sensing Band Stickers (e.g., F03-26PES) to hold it in place. If required by your application, another method can be used (e.g., installation with suitable connectors). After installation, confirm that a reliable electrical connection has been achieved. Interval Between Stickers When securing the Sensing Band with Stickers, attach the Stickers at intervals of 20 to 30 cm in places where the core is not exposed. Secure the Sensing Band as close to a Terminal Block or Terminator as possible. 20 to 30 cm Sensing Band Sticker Terminal Block or Terminator Note: 1. When using the F03-26PES (adhesive-tape model), be sure to wipe all moisture, oil, and dust from the surface to which the Sticker is to be attached. Failure to do so may result in insufficient adhesion, and the Sticker may peel away from the surface. 2. When using the F03-26PEN (screw model), before installing the Sensing Band, it is necessary to perform stud welding. For details on the pitch of the studs, refer to the information on the dimensions of Sensing Band Stickers. 3. If you connect a Sensor Band with an F03-20 Terminal Block and F03-20T Terminator, secure the Sensing Band with Sensing Stickers near the Terminal Block and Terminator to help adsorb stress, e.g., from something pulling on the Sensing Band. Bending the Sensing Band To change the direction of the Sensing Band, bend the Sensing Band in one or two places where the core is not exposed. Bent in 1 place Bent in 2 places Note: Bend the Sensing Band approximately 4 cm (i.e., twice the distance between places where the core is exposed) away from places where a Sticker is attached. If the Sensing Band is bent at places further away than this, the Sensing Band may come away from the surface. 23 F03-16SF/-16SFC Liquid Leakage Sensing Band F03-16SF/F03-16SFC Liquid Leakage Sensing Band Greater flexibility and superior workability compared with the F03-16PE. The sheath becomes transparent to reveal the red inner sheath if liquid leakage occurs, thereby enabling visual confirmation. After drying, the Sensing Band color will return to white. F03-16SF F03-16SFC (with color indication) Ordering Information Type Length Liquid Leakage Sensing Band (without color indication) F03-16SF Liquid Leakage Sensing Band (with color indication) F03-16SFC Model Model 5m F03-16SF-5M F03-16SFC-5M 10 m F03-16SF-10M F03-16SFC-10M 20 m F03-16SF-20M F03-16SFC-20M 30 m F03-16SF-30M F03-16SFC-30M 50 m F03-16SF-50M F03-16SFC-50M 100 m F03-16SF-100M F03-16SFC-100M Note: When you select a Sensing Band, confirm the suitability for the detection liquid and the specifications of the Water/Liquid Leakage Sensor. Specifications Sheath Special plastic fiber braided cable with water-absorbent and water-repellent characteristics Core Tin-plated, copper-stranded wire 0.75mm2 Ambient operating temperature −15 to 60°C Weight Approximately 20 g (1 m) Note: 1. In order to prevent secondary fire damage, consider the effect of the atmosphere of the environment and the solution to be detected on the Sensing Band. 2. If the Sensing Band becomes misshapen, discolored, or otherwise abnormal after detection, replace the Sensing Band. Dimensions Sensing Band Type Item (Unit: mm) Cable Sticker Liquid Leakage Sensing Band F03-16SF Electrode Liquid Leakage Sensing Band (with color indication) F03-16SFC Internal braiding Appearance Appearance F03-25 External braiding Dimensions Structure 5 mm max. 24 External braiding (white) Internal braiding (red) Electrode External braiding (white) Internal braiding (white) Electrode 5 mm max. 25±2 (5) (3) (0.5) 15±2 Adhesive tape * Material: SUS304 (1) Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron.com/global/ or contact your Omron representative for published information. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted. Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Programmable Products. Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof. Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability. Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to confirm actual specifications of purchased Product. Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions. OMRON Corporation Industrial Automation Company Authorized Distributor: Kyoto, JAPAN Contact: www.ia.omron.com Regional Headquarters OMRON EUROPE B.V. Wegalaan 67-69, 2132 JD Hoofddorp The Netherlands Tel: (31)2356-81-300/Fax: (31)2356-81-388 OMRON ELECTRONICS LLC 2895 Greenspoint Parkway, Suite 200 Hoffman Estates, IL 60169 U.S.A. Tel: (1) 847-843-7900/Fax: (1) 847-843-7787 OMRON ASIA PACIFIC PTE. LTD. No. 438A Alexandra Road # 05-05/08 (Lobby 2), Alexandra Technopark, Singapore 119967 Tel: (65) 6835-3011/Fax: (65) 6835-2711 OMRON (CHINA) CO., LTD. Room 2211, Bank of China Tower, 200 Yin Cheng Zhong Road, PuDong New Area, Shanghai, 200120, China Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200 © OMRON Corporation 2016 All Rights Reserved. In the interest of product improvement, specifications are subject to change without notice. CSM_1_1_0316 Cat. No. N211-E1-01 0316(0316)