Product PDF

SmartOnline 230V 3kVA 2.1kW Double-Conversion
UPS, Tower, SNMPWEBCARD Option, DB9 Serial
MODEL NUMBER: SUINT3000XL
Highlights
3000VA on-line,
double-conversion, extended-run
tower UPS system
Maintains 220/230/240V
selectable output within +/-2%
during overvoltages to 280V and
brownouts as low as 80V
(50/60Hz auto-sensing)
Network communications
supported via serial port and
SNMP/Web card slot
Fault-tolerant auto-bypass and
current monitoring
Input: C20 inlet / Output: 8 x C13
outlets (3 x C13-to-C14 jumper
cables included)
Description
Tripp Lite's SmartOnline SUINT3000XL on-line, double-conversion UPS protects critical server, networking and
telecommunications equipment from blackouts, voltage fluctuations and transient surges. Space-saving upright
tower format. Large capacity 3000VA/2100W UPS continuously converts incoming AC to DC, then back to
perfect sine wave AC output at selectable 220/230/240V AC (+/-2%). Removes harmonic distortion, fast
electrical impulses, frequency fluctuations and other hard-to-solve power problems not addressed by other UPS
types. True sine wave output and zero transfer time offers guaranteed compatibility with all equipment types.
Package Includes
SUINT3000XL UPS System
PowerAlert Sofware CD-ROM
and cabling
3 C13-to-C14 jumper cables
Owner's manual with warranty
information
Includes 8 C13 outlets. Battery support can be extended through the addition of external battery packs. Includes
slot for internal SNMP/Web card, plus DB9 enhanced serial monitoring port for unattended shutdown, remote control and monitoring of UPS system and
power data.
Features
True on-line, double conversion UPS provides pure sine wave AC output at all times
Maintains continuous operation with zero transfer time through blackouts, voltage fluctuations and surges
Removes harmonic distortion, electrical impulses, frequency variations and other hard-to-solve power problems
Corrects brownouts and overvoltages from 175-280V at full load. Input voltage range extends to 80-280V at 50% load or less
3000VA/2100W power capacity with 8 C13 outlets
IEC320-C20 input connection accepts a variety of detachable cordsets to match country or site-specific wall receptacles
Standard internal battery set provides 14 min. runtime at half load and 5 min. runtime at full load
Intelligent battery management system extends battery life
Expandable runtime with multiple external battery packs
DB9 serial port for network interface; SNMP compatible
Slot for optional SNMP/Web card(part# SNMPWEBCARD)
PowerAlert unattended shutdown software and network cable included
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
Diagnostic LEDs
Optional PDUBHV20 bypass PDU enables hot-swappable UPS replacement
with no disruption to connected equipment
1/5
Optional PDUBHV20 bypass PDU enables hot-swappable UPS replacement with no disruption to connected equipment
3 C13-to-C14 jumper cables included
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
3000
Output kVA Capacity (kVA)
3
Output Watt Capacity (Watts)
2100
Output kW Capacity (kW)
2.1
Power Factor
0.7
Crest Factor
3:1
Nominal Output Voltage(s)
Supported
220V; 230V; 240V
Nominal Voltage Details
230V default
Frequency Compatibility
50 / 60 Hz
Frequency Compatibility Details
Output frequency matches input nominal on startup, defaults to 50 Hz on cold-start
Output Voltage Regulation (Line
Mode)
+/- 2%
Output Voltage Regulation
(Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery
Mode)
+/- 2%
Output Receptacles
(8) C13
Included Output Power Cables
Includes 3 C13 to C14 output power cables
Hot-Swap PDU options
PDUBHV20 (2U / 6 C13, 2 C19 outlets)
Output AC Waveform (AC Mode)
Sine wave
Output AC Waveform (Battery Mode)
Pure Sine wave
INPUT
Rated input current (Maximum Load)
13.6A (220V), 13A (230V), 12.5A (240V)
Nominal Input Voltage(s) Supported
220V AC; 230V AC; 240V AC
UPS Input Connection Type
C20 inlet
UPS Input Connection Description
IEC320-C20 input connection accepts a variety of detachable cordsets to match country or site-specific wall
receptacles
Input Circuit Breakers
20A
Input Phase
Single-Phase
2/5
BATTERY
Full Load Runtime (min.)
5 min. (2100w)
Half Load Runtime (min.)
14 min. (1050w)
Expandable Battery Runtime
Extended runtime supported via optional external battery packs
External Battery Pack Compatibility
BP72V15-2U (limit 1); BP72V28RT-3U(multi-pack compatible)
DC System Voltage (VDC)
72
Battery Recharge Rate (Included
Batteries)
Less than 6 hours from 10% to 90%
Battery Replacement Description
Hot-swappable, user replaceable batteries
Expandable Runtime
Yes
VOLTAGE REGULATION
Voltage Regulation Description
Online, double-conversion power conditioning
Overvoltage Correction
2% output voltage regulation during overvoltages to 280
Undervoltage Correction
2% output voltage regulation during undervoltages to 175
Severe Undervoltage Correction
2% output voltage regulation during undervoltages to 80 (under 50% load only)
USER INTERFACE, ALERTS & CONTROLS
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation
Alarm Cancel Operation
Power-fail alarm can be silenced using alarm-cancel switch
Audible Alarm
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
LED Indicators
14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery
and fault status information; 4-LED meter displays load and battery charge levels
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
570
UPS AC Suppression Response
Time
Instantaneous
EMI / RFI AC Noise Suppression
Yes
PHYSICAL
Primary Form Factor
Tower
UPS Power Module Dimensions
(hwd, in.)
14.7 x 5.5 x 16.7
UPS Power Module Dimensions
(hwd, cm)
37.3 x 14 x 42.4
UPS Power Module Weight (lbs.)
67.2
UPS Power Module Weight (kg)
30.5
3/5
UPS Shipping Dimensions (hwd / in.)
19.4 x 9.8 x 23.8
UPS Shipping Dimensions (hwd /
cm)
49.3 x 24.9 x 60.5
Shipping Weight (lbs.)
73.8
Shipping Weight (kg)
33.5
Cooling Method
Fan
UPS Housing Material
Steel
ENVIRONMENTAL
Operating Temperature Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity
0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)
793.3
AC Economy Mode BTU / Hr. (Full
Load)
455.7
Battery Mode BTU / Hr. (Full Load)
973.6
AC Mode Efficiency Rating (100%
Load)
90%
AC Economy Mode Efficiency Rating
(100% Load)
94%
Audible Noise
< 45 dB at front side 1m
COMMUNICATIONS
Communications Interface
DB9 Serial; Contact closure; Slot for SNMP/Web interface
Network Monitoring Port Description
Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure
communications
PowerAlert Software
Included
Communications Cable
DB9 cabling included
LINE / BATTERY TRANSFER
Transfer Time
No transfer time (0 ms.) in online, double-conversion mode
Low Voltage Transfer to Battery
Power (Setpoint)
175V (100% load), 80V ( <50% load)
High Voltage Transfer to Battery
Power (Setpoint)
280
SPECIAL FEATURES
Cold Start (Startup in Battery Mode
During a Power Failure)
Cold-start operation supported
High Availability UPS Features
Automatic inverter bypass
4/5
CERTIFICATIONS
UPS Certifications
CE
UPS Certification Details
CE EN62040-1-1, EN62040-2 Class A
WARRANTY
Product Warranty Period (Worldwide)
2-year limited warranty
© 2016 Tripp Lite. All rights reserved. All product and company names are trademarks or registered trademarks of their respective holders. Use of them does
not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies:
http://www.tripplite.com/products/product-certification-agencies
5/5