Liebert® eXM™ TXC™ User Manual–10-100kVA, 60Hz TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 1.0 LIEBERT EXM TXC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 1.1 Locating the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.2 Cable Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 1.2.1 1.2.2 1.2.3 1.3 Wiring Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Power Cable Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Input/Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Bolting Cabinets Together . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 1.3.1 1.3.2 1.3.3 Floor Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Cable Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Optional Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 2.0 INSTALLATION DRAWINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 3.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 FIGURES Figure 1 Single input UPS with external Liebert eXM TXC with optional dual transformer cabinet—Typical configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Figure 2 Schematic - Liebert eXM TXC to Maintenance Bypass Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Figure 3 Bolting Liebert eXM UPS to a Liebert eXM TXC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Figure 4 Cabinet arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Figure 5 Clearances—Front, side and rear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Figure 6 Liebert eXM TXC Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Figure 7 Busbars—Liebert eXM TXC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Figure 8 Lineup arrangement, Liebert eXM with Liebert eXM TXC, 10-40kVA . . . . . . . . . . . . . . . . . . . . . 13 Figure 9 Lineup arrangement, Liebert eXM with Liebert eXM TXC, 60-100kVA . . . . . . . . . . . . . . . . . . . . 13 Figure 10 Outline drawing, Liebert eXM TXC for Liebert eXM, 10-100kVA . . . . . . . . . . . . . . . . . . . . . . . . . 14 Figure 11 Liebert eXM TXC transformer location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Figure 12 Bend radius - Top feed power connections, 10-100kVA system . . . . . . . . . . . . . . . . . . . . . . . . . . 16 i TABLES Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 7 Table 8 Table 9 Table 10 Table 11 Table 12 Table 13 Table 14 Table 15 Wiring for Liebert eXM TXC to Liebert eXM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Hardware torque values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Physical standards and parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Liebert eXM TXC, 10-100k, mechanical characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Recommended lug sizes (compression type) M10, 3/8" bolt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Busbar torque for power wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Liebert eXM TXC heat dissipation, both transformers, full load . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Electrical data—Liebert eXM TXC, 480VAC input, 208VAC output, rectifier input, with 480V:208V transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Electrical data—Liebert eXM TXC, 480VAC input, 208VAC output, bypass input, with 480V:208V transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Terminal block torque with compression lugs for control wiring. . . . . . . . . . . . . . . . . . . . . . . . . . 19 Electrical data—Liebert eXM TXC, 208VAC or 220VAC input, rectifier input, with 208V:208V or 220V:220V transformer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Electrical data—Liebert eXM TXC, 600VAC input, 208VAC output, rectifier input, with 600V:208V transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Electrical data—Liebert eXM TXC, 600VAC input, 208VAC output, bypass input, with 600V:208V transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Electrical data—Liebert eXM TXC, 208VAC or 220VAC input, bypass input, with 208V:208V or 220V:220V transformer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Liebert eXM TXC Inrush Multiplier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 ii IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation of the Liebert eXM TXC (dual transformer cabinet). Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the UPS. Retain this manual for use by installing personnel. A properly trained and qualified electrical contractor should oversee the installation of the equipment. The Liebert eXM TXC cannot be put into operation until it is commissioned by the manufacturer or authorized engineer. Otherwise, human safety may be endangered and damage to the UPS will not be covered by the warranty. The Liebert eXM TXC is designed for commercial and industrial uses and cannot be used as life support equipment. ! WARNING Risk of moving heavy equipment and electric shock. Can cause equipment damage, injury and death. Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel. The Liebert eXM TXC’s weight ranges from 785 to 1969 lb. (356 to 893kg). Determine the unit’s weight and locate the center of gravity symbols before handling the Liebert eXM TXC. Test lift and balance the cabinet before transporting it. Never tilt equipment more than 15 degrees from vertical. In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires. Extreme caution is required when performing maintenance. Be constantly aware that the UPS system contains high DC as well as AC voltages. Check for voltage with both AC and DC voltmeters prior to making contact. ! AVERTISSEMENT Risque lors du déplacement de l'équipement lourd et de décharge électrique pouvant entraîner des dommages matériels, des blessures et même la mort. Faites preuve d'une extrême prudence lors de la manutention des armoires ASC afin d'éviter de les endommager ou de blesser le personnel. Les armoires Liebert eXM TXC pèsent de 785 à 1969 lb (de 356 à 893 kg). Déterminez le poids de l'unité et trouvez les symboles de centre de gravité avant de déplacer l'armoire Liebert eXM TXC. Faites des essais de levage et d'équilibre avant de transporter l'armoire. N'inclinez jamais l'équipement à plus de 15 degrés à la verticale. En cas d'incendie associé à du matériel électrique, n'utilisez que des extincteurs à dioxyde de carbone ou homologués pour la lutte contre les incendies d'origine électrique. Les opérations d'entretien requièrent une extrême prudence. Soyez toujours conscient du fait que le système ASC contient des tensions c.c. et c.a. élevées. Vérifiez les tensions avec des voltmètres c.a. et c.c. avant d'établir tout contact. 1 Liebert® eXM™ TXC™ ! WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous voltages are present within the UPS and battery enclosure even after input power has been disconnected. The risk of contact with these voltages is minimized as the live component parts are housed behind a metal panel. Further internal safety screens make the equipment protected to IP20 standards. Never remove panels or covers or open doors that will expose internal components to contact. Read and follow all warnings, cautions and safety and operating instructions to avoid serious injury or death from electric shock. No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating procedures. All equipment maintenance and servicing procedures involve internal access and should be carried out only by trained personnel. ! AVERTISSEMENT Risque de décharge électrique pouvant entraîner des dommages matériels, des blessures et même la mort. À l'instar des autres types d'équipement haute puissance, des tensions dangereuses sont présentes à l'intérieur de l'armoire ASC et du châssis de batteries même après le débranchement de l'alimentation d'entrée. Le risque de contact avec ces tensions est diminué, car les parties de composants sous tension sont abritées derrière un panneau métallique. D'autres écrans de sécurité internes protègent l'équipement en conformité avec les normes IP20. Ne retirez jamais les panneaux ou les couvercles et n'ouvrez pas les portes donnant accès aux composants internes avec lesquels vous pouvez entrer en contact. Veuillez lire et suivre l'ensemble des avertissements, des mises en garde et des instructions de sécurité et de fonctionnement afin d'éviter des blessures graves, voire la mort, pouvant être causées par une décharge électrique. Il n'y a aucun risque pour le personnel lorsque l'équipement est utilisé normalement, en suivant les procédures de fonctionnement recommandées. Toutes les procédures de réparation et d'entretien de l'équipement exigent un accès à l'intérieur de l'armoire et devraient être menées uniquement par du personnel compétent. Liebert® eXM™ TXC™ 2 Ground Leakage Currents ! WARNING Risk of electric shock from high leakage current. Can cause injury, property damage and death. EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY. Earth leakage current exceeds 3.5 mA and is less than 1000 mA. Transient and steady-state earth leakage currents, which may occur when starting the equipment, should be taken into account when selecting instantaneous RCCB or RCD devices. Residual Current Circuit Breakers (RCCBs) must be selected sensitive to DC unidirectional pulses (Class A) and insensitive to transient current pulses. Note also that the earth leakage currents of the load will be carried by this RCCB or RCD. This equipment must be earthed in accordance with the local electrical code of practice. ! AVERTISSEMENT Risque de décharge électrique due à un courant de fuite élevé pouvant causer des blessures, des dommages matériels et même la mort. IL EST PRIMORDIAL D'ASSURER UNE CONNEXION DE TERRE AVANT DE BRANCHER L'ALIMENTATION D'ENTRÉE. La fuite à la terre est supérieure à 3,5 mA et inférieure à 1 000 mA. Vous devez tenir compte des fuites de courant transitoires et permanentes à la terre, susceptibles de se produire au démarrage de l'équipement, lors de la sélection des dispositifs DDFT instantanés. Vous devez sélectionner des disjoncteurs différentiels de fuite à la terre (DDFT) sensibles aux impulsions unidirectionnelles c.c. (classe A) et insensibles aux impulsions de courant transitoires. Notez également que les courants de fuite à la terre de la charge seront acheminés par ce dispositif DDFT. Cet équipement doit être mis à la terre conformément au code national de l'électricité. ! WARNING Risk of electric shock. Can cause injury, property damage and death. Under typical operation and with all UPS doors closed, only normal safety precautions are necessary. The area around the UPS system should be kept free of puddles of water, excess moisture and debris. Special safety precautions are required for procedures involving handling, installation and maintenance of the UPS system and the internal batteries (internal batteries accommodated by the 10-40kVA frame only). Observe all safety precautions in this manual before handling or installing the UPS system as well as during all maintenance procedures. Observe all battery safety precautions before working on or near the battery. This equipment contains several circuits that are energized with high voltage. Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with AC and DC voltmeters to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high electric charges may exist within the UPS. All power and control wiring should be installed by a qualified electrician. All power and control wiring must comply with the NEC and applicable local codes. ONLY qualified service personnel should perform maintenance on the UPS system. When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats. The service personnel should wear insulating shoes for isolation from direct contact with the floor (earth ground). Never work alone, even if all power is removed from the equipment. A second person should be standing by to assist and summon help in case an accident should occur. 3 Liebert® eXM™ TXC™ ! AVERTISSEMENT Risque de décharge électrique pouvant causer des blessures, des dommages matériels et même la mort. Les précautions de sécurité habituelles suffisent lorsque le système ASC est en mode de fonctionnement normal et que toutes les portes sont fermées. La zone entourant le système ASC doit être exempte de flaques d’eau, d’humidité excessive et de débris. Des précautions de sécurité spéciales sont requises pour les procédures associées à la manutention, à l’installation et à l’entretien du système ASC. Observez toutes les précautions de sécurité décrites dans le présent manuel avant de manipuler ou d’installer le système ASC, ainsi que pendant toutes les procédures d’entretien. Cet équipement comporte plusieurs circuits à haute tension. Seuls des équipements d’essai conçus pour le dépannage doivent être utilisés. Cette mise en garde couvre notamment les oscilloscopes. Utilisez toujours des voltmètres c.a. et c.c. pour vérifier les tensions avant d’établir un contact ou d’utiliser des outils. Des tensions dangereusement élevées peuvent demeurer dans le système ASC même une fois l’alimentation coupée. Tous les câbles d’alimentation et de contrôle doivent être installés par un électricien qualifié. Tous les câbles d’alimentation et de contrôle doivent être conformes au Code national de l’électricité des États-Unis (NEC) et celui du Canada, ainsi qu’aux codes locaux en vigueur. L’entretien du système ASC ne doit être confié qu’à des professionnels qualifiés. Les responsables de l’entretien et l’équipement d’essai doivent reposer sur des tapis de caoutchouc lors de toute intervention sur une pièce d’équipement sous tension. Les responsables de l’entretien doivent porter des chaussures isolantes pour prévenir tout contact direct avec le plancher. Ne travaillez jamais seul, même si toute l’alimentation d’entrée est coupée de l’équipement. Une seconde personne devrait toujours être présente pour porter assistance ou chercher de l’aide en cas d’accident. NOTICE Risk of improper ground connection. Can cause equipment damage. Ground connection is essential before connecting the input supply. This equipment must be grounded in accordance with local electrical codes. Maximum load must not exceed that shown on the UPS rating label. NOTICE Risk of improper electromagnetic shielding. Can cause radio communication interference. This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. This unit is not designed for use in a residential area. Operation of this unit in a residential area may cause harmful interference that the user is solely responsible for correcting. Liebert® eXM™ TXC™ 4 GLOSSARY OF SYMBOLS Risk of electrical shock ! Indicates caution followed by important instructions AC input AC output i - Requests the user to consult the manual + Indicates the unit contains a valve-regulated lead acid battery PbH2SO4 R Recycle DC voltage AC voltage Equipment grounding conductor Bonded to ground 5 Liebert® eXM™ TXC™ Liebert eXM TXC 1.0 LIEBERT eXM TXC The Liebert eXM TXC offers 10-100kVA capacity to match the associated Liebert eXM frame offerings. Each of the Liebert eXM TXC capacities offer optional input 208V, 220V, 480V and 600V internal transformers in a dual input configuration. Figure 1 Single input UPS with external Liebert eXM TXC with optional dual transformer cabinet—Typical configuration MAINTENANCE BYPASS CABINET * Bypass AC Input 4 Wire + GND MBB BIB Output Busbar MIB AC Output 208V 4 Wire + GND RIB STATIC BYPASS * Rectifier AC Input 4 Wire + GND UPS CABINET BATTERY DUAL TRANSFORMER CABINET NOTES 1. Install in accordance with national and local electrical codes. 2. A neutral is required from the system AC input source. Emerson recommends a full capacity neutral conductor and grounding conductors. 3. Bypass and rectifier input and output cables must be run in separate conduits. 4. Control wiring must be run in separate conduits. 1.1 RIB - Rectifier Input Breaker BIB - Bypass Isolation Breaker MBB - Maintenance Bypass Breaker MIB - Maintenance Isolation Breaker * External Overcurrent Protection by Others Field-Supplied Wiring EXM11009 Rev. 0 Locating the Cabinet This Liebert eXM TXC may be mounted to the right of the UPS. Ensure that the unit is in a wellventilated area and that there is clearance for access to the switches and cable connections as required by national and local codes. Liebert® eXM™ TXC™ 6 Liebert eXM TXC 1.2 Cable Installation 1.2.1 Wiring Preparation Be sure that the unit is not connected to any AC utility power source or UPS before installing any wiring to this unit. This Liebert eXM TXC should be installed by a qualified / certified electrician. ! WARNING Risk of electrical shock and arc flash. Can cause property damage, injury and death. Read this section thoroughly before attempting to install wiring to this unit. Read and comply with all warnings and cautions in this manual. Removing the Cover Plates Plates cover the input and output terminals on the front of the Liebert eXM TXC (see Figure 7). Remove these and keep the screws and plates for reinstallation. 1.2.2 Power Cable Installation Refer to Table 42 when selecting cables. Refer to the electrical tables listed in the back of this manual. NOTE Transient and steady state earth leakage currents may occur when starting the equipment. This should be taken into account when selecting ground current detection devices because these will carry the earth leakage currents of both the UPS equipment and the load. 1.2.3 Input/Output Wiring Follow the steps below to connect the input wiring: NOTE Input wiring must be installed using conduit if cabinet is not mounted to the immediate right of the UPS. 1. Locate the input wiring access (top or bottom access), remove the conduit landing plate and punch the appropriate size hole for the size conduit being used. Pull the three/four input wires through the hole, allowing some slack for installation. For cabinets that are located to the immediate left of the UPS, the access plate is on the lower right of the cabinet. Remove the access plate and verify that the edge guarding is installed and intact. 2. Secure the conduit to the access plate of the Liebert eXM TXC. 3. Input power cables connect to the TXC at TB1 and TB2; refer to Figure 6, Tables 1 and 2. 4. Connect the ground cable from sources #1 and #2 to the TXC ground busbar and tighten them to 192 lb-in (22Nm) for M10 bolt. 5. Connect the neutral cable from sources #1 and #2 to the TXC neutral busbar and tighten them to 192 lb-in (22Nm) for M10 bolt.. NOTE If the Liebert eXM TXC is not to be bolted to the UPS, use either top or bottom access plate. 6. Connect the source #1 cables to TB1 (A-B-C) and tighten the connections to 192 lb-in (22Nm) for M10 bolt. 7. Connect the source #2 cables to TB2 (A-B-C) and tighten the connections to 192 lb-in (22Nm) for M10 bolt. 8. Connect the GEC from the Liebert eXM TXC to the customer GEC and tighten the connections to 192 lb-in (22Nm) for M10 bolt. 9. Connect the neutral cable between the Liebert eXM TXC and UPS and tighten the connections to 192 lb-in (22Nm) for M10 bolt. 11. 10. Connect the ground cable between the Liebert eXM TXC and UPS and tighten the connections to 192 lb-in (22Nm) for M10 bolt. 7 Liebert® eXM™ TXC™ Liebert eXM TXC NOTICE Risk of improper wiring connection. Can cause equipment damage. The control wire must be installed to ensure proper operation of the system and fully protect the load when switching between bypass cabinet and UPS. NOTES 1. All interconnection hardware supplied by Emerson. 2. AC connections must be made to the UPS module before attaching Liebert eXM TXC to UPS module. 3. Liebert eXM TXC’s must attach to the right side only of the Liebert eXM UPS. 4. Refer to the individual drawing of each piece of equipment for additional details. Table 1 Wiring for Liebert eXM TXC to Liebert eXM Figure 2 Run From To A Utility Source #1 B C D E C H Utility Neutral #1 Utility Ground #1 Utility Source #2 Utility Neutral #2 Utility Ground #2 TXC GEC Conductors TXC Rectifier Input TB1 TXC Neutral Busbar TXC Ground Busbar TXC Bypass Input TB2 TXC Neutral Busbar TXC Ground Busbar Customer GEC Phase A, B, C Neutral Ground Phase A, B, C Neutral Ground GEC Schematic - Liebert eXM TXC to Maintenance Bypass Cabinet Customer Main Input TB1 Phase A Phase B Phase C W04 W05 W06 X-A Isolation Transformer X-B H2 T1 X-C H1 H3 X0 W11 W12 W13 W14 Ground to Unit Frame Utility Input Customer Bypass Input TB2 Phase A Phase B Phase C W01 W02 W03 X-A Isolation X-B H2 Transformer T2 X-C H3 X0 H1 W07 TB2 TB4 W08 W09 W10 Narrow Side Mount Maintenance Bypass Cabinet Ground to Unit Frame Customer Input Neutral W15 CIN Customer Ground Busbar W16 Ground to Unit Frame Wiring Legend Factory Supplied Field Supplied Liebert® eXM™ TXC™ CMG Ground Electrode (See Note 2) NOTES: 607503 Rev. 1 1. Wiring furnished by the factory. Consult the installation manual for UPS connections 2. Customer-furnished grounding electrode conductor is to be installed in accordance with National Electric Code Article 250-26. 3. Refer to Liebert eXM MBC manual SL-25652 for additional details about connections to Liebert eXM UPS. 8 Liebert eXM TXC 1.3 Bolting Cabinets Together NOTE UPS wiring must be completed before the cabinets are bolted together. 1. Line up cabinets so that mounting holes are aligned. Figure 3 Bolting Liebert eXM UPS to a Liebert eXM TXC A Hex Head Bolt, M10 x 30mm Washer Split, M10 Washer Flat, M10 Place cabinets so mounting holes are aligned. A bolt from the adjacent cabinet may be screwed into the threaded top hole, or a bolt may be inserted through the lower hole and screwed into the threaded hole in the adjacent cabinet. DETAIL A 2. Using supplied hardware, bolt the cabinets together. The bolts may be inserted from either the UPS side or from the Liebert eXM TXC side, whichever is more convenient. ! WARNING Risk of heavy units tipping over while being moved. Can cause property damage, injury and death. The Liebert eXM TXC and battery cabinets must be properly prepared and secured for lifting. Improper lifting may cause the cabinets to fall, causing equipment damage, personal injury and death. Emerson recommends lifting the units with one of the following methods: • Installing four eyebolts in the factory-fabricated holes, one at each corner of the unit, attaching cables or similar strapping to the eyebolts and lifting with a suitable mechanism. • Placing suitable straps on the Liebert eXM TXC. The straps must go under the unit to be lifted. 9 Liebert® eXM™ TXC™ Liebert eXM TXC ! AVERTISSEMENT Le centre de gravité élevé des appareils présente un risque de renversement lors des déplacements, pouvant entraîner des dommages matériels, des blessures et même la mort. Les armoires Liebert eXM TXC et de batterie doivent être correctement préparées et sécurisées avant d’être levées. Un mauvais levage peut faire tomber les armoires, causant des dommages à l'équipement, des blessures, voire la mort. Emerson recommande de soulever les unités en suivant l'une des méthodes suivantes : • En installant quatre anneaux de levage dans les ouvertures fabriquées en usine, avec un anneau dans chaque coin de l’appareil, pour ensuite fixer les câbles ou sangles aux anneaux afin d'effectuer le levage à l'aide d'un mécanisme approprié. • En plaçant des sangles convenables sur l'armoire Liebert ou de batterie. Les sangles doivent passer sous l'unité à soulever. 1.3.1 Floor Installation If the Liebert eXM TXC is to be placed on a raised floor, the UPS should be mounted on a pedestal that will support the equipment point loading. Refer to the Liebert eXM UPS manual, SL-25648 or SL-25650, to design this pedestal. 1.3.2 Cable Entry Cables can enter the Liebert eXM TXC from the top or bottom through removable metal plates. Some plates have factory-punched holes and others are designed to allow the personnel to punch holes for fitting and securing the conduit. Once the conduit holes are punched, these plates should be reattached to the UPS. The conduit size and wiring method must be in accordance with all local, regional and national codes and regulations, including NEC ANSI/NFPA 70. NOTE When installing the UPS, the customer must provide a disconnect with overcurrent protection at the output of the UPS. 1.3.3 Optional Cabinets The Liebert eXM TXC must be bolted to right side of the Liebert eXM (see Figure 4). The Liebert eXM TXC must be cabled and bolted to the Liebert eXM before the UPS and bypass distribution cabinet are moved into their final position. Connect input wiring to the Liebert eXM TXC ONLY after the units are internally cabled and positioned. Battery cabinets may be bolted only to the left side of the Liebert eXM; see Figure 4. Figure 4 Cabinet arrangement ALL UNITS VIEWED FROM ABOVE Liebert eXM Liebert eXM Maintenance Bypass Cabinet Dual Transformer Cabinet Liebert eXM UPS connected to Liebert eXM TXC and Maintenance Bypass Cabinet (The Liebert eXM TXC must be on right side of the Liebert eXM UPS) Liebert® eXM™ TXC™ Battery Cabinet Battery Cabinet Maintenance Bypass Cabinet Dual Transformer Cabinet Liebert eXM UPS connected to Liebert eXM TXC and Battery Cabinets and Maintenance Bypass Cabinet (TXC must be on right side of the Liebert eXM) (Battery Cabinets must be on the left side of the Liebert eXM UPS) 10 Liebert eXM TXC Figure 5 Clearances—Front, side and rear 0 to 5" (127mm) REAR Rear clearance depends on anchoring method 0" Required Liebert eXM 0" Required FRONT Minimum of 36" (914mm) required for foot traffic with door fully open 11 Liebert® eXM™ TXC™ Installation Drawings 2.0 INSTALLATION DRAWINGS Figure 6 Liebert eXM TXC Main components TB1 Neutral Busbar Transformers Ground Busbar TB2 FRONT With Cover EXM15010 Rev. 1 RIGHT SIDE Panel Removed Busbars—Liebert eXM TXC See Detail C TB1 (See Detail A) Neutral Busbar (See Detail B) Transformer Ground Busbar (See Detail B) TB2 (See Detail A) 1.6" (41mm) 125A XFMR Lugs Transformer RIGHT SIDE VIEW with Panel Removed Ø0.38" (9.6mm) 6 Typical 1.75" (44mm) Typcial Notes: 1. All dimensions are in inches (mm). 2. Control wiring and power wiring must be run in separate conduits. 3. All wiring is to be in accordance with national and local electrical codes. 4. If maintenance bypass cabinet is attached to UPS, the Emerson will suppy the interconnection cables. 5. 225A panelboard for 10k - 40kVA only. 400A panelboard for 60k - 100kVA only. 375A XFMR Lugs Figure 7 FRONT Door Removed 1.75" (44mm) Typcial 1.5" (38mm) 1.25" (32mm) DETAIL A Terminal Blocks Liebert® eXM™ TXC™ Ø0.437" (11mm) 6 Typical DETAIL B Ground and Neutral Busbars 12 DETAIL C EXM16014 Rev. 1 Installation Drawings Figure 8 Lineup arrangement, Liebert eXM with Liebert eXM TXC, 10-40kVA 55.1" (1400mm) 7.9" (200mm) 23.6" (600mm) 23.6" (600mm) 78.7" (2000mm) UPS MBC Dual XFRMR Cabinet FRONT VIEW Figure 9 Notes: 1. All dimensions are in inches (mm). 2. 24" (610) minimum clearance above unit for air exhaust 36" (914) front access required for service. 3. Keep cabinet within 15 degrees of vertical. 4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace. 5. Unit bottom is structurally adequate for forklift handling. 6. Control wiring and power wiring must be run in separate conduits. 7. All wiring is to be in accordance with national and local electrical codes. 8. All battery cabinets must be positioned on the left side of the UPS. EXM13005 Rev. 1 Lineup arrangement, Liebert eXM with Liebert eXM TXC, 60-100kVA 59" (1500mm) 11.8" (300mm) 23.6" (600mm) 23.6" (600mm) Notes: 1. All dimensions are in inches (mm). 2. 24" (610) minimum clearance above unit for air exhaust 36" (914) front access required for service. 3. Keep cabinet within 15 degrees of vertical. 4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace. 78.7" 5. Unit bottom is structurally adequate for forklift handling. (2000mm) 6. Control wiring and power wiring must be run in separate conduits. 7. All wiring is to be in accordance with national and local electrical codes. 8. All battery cabinets must be positioned on the left side of the UPS. UPS MBC FRONT Dual XFRMR Cabinet EXM13011 Rev. 1 13 Liebert® eXM™ TXC™ Installation Drawings Figure 10 Outline drawing, Liebert eXM TXC for Liebert eXM, 10-100kVA 20.4" (519mm) 15.3" (387mm) See Detail A Leveler 34.5" (876mm) Ventilation 28.3" (718mm) Caster TOP 24" (608mm) 23.6" (600mm) DETAIL A BOTTOM Notes 1. 24" [610] minimum clearance above unit for air exhaust. 36" [914] front access required for service. 2. Keep cabinet within 15 degrees of vertical. 3. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace. 4. Unit bottom is structurally adequate for forklift handling. 5. Control wiring and power wiring must be run in separate conduits. 6. All wiring is to be in accordance with national and local electrical codes. 39.8" (1010mm) 78.7" (2000mm) FRONT Liebert® eXM™ TXC™ EXM12009 Rev. 1 RIGHT SIDE 14 Installation Drawings Figure 11 Liebert eXM TXC transformer location Transformer, T1 Transformer, T2 RIGHT SIDE REAR OF CABINET 15 Liebert® eXM™ TXC™ Installation Drawings Figure 12 Bend radius - Top feed power connections, 10-100kVA system NOTE Interconnection wiring between the UPS and bypass distribution cabinet is supplied by Emerson when the Liebert eXM TXC and Liebert eXM UPS are ordered as a system. Table 2 Hardware torque values Hardware Two Belleville Washers M10 (3/8") 240 lb-in. (27 Nm) M12 (1/2") 428 lb-in (48Nm) Liebert® eXM™ TXC™ 16 Specifications 3.0 SPECIFICATIONS Table 3 Physical standards and parameters Values Dual Transformer Cabinet Parameters Standard Color Black (ZP-7021) Front Door Opening (for serviceability) More than 180° IP 20 (with and without front door open) Degree of Protection for UPS Enclosure Minimum Clearance, Top 24" (610mm) Minimum Clearance, Back 0" (5" [127mm] when seismic brackets are used) Minimum Clearance, Sides 0" Cable Entrance Top or Bottom UL 71778 5th Ed.; CSA 22.2 107.3-14 ISTA Procedure 1H; WEEE Standards & Conformities Environmental Storage Temperature Range, °F (°C) -13°F to 158°F (-25°C to 70°C) 32°F to 104°F (0 to 40°C) 32°F to 86°F (0-30°C) when seismic brackets are used Operating Temperature Range, °F (°C) Up to 95% Non-Condensing (Operating and Non-Operating) Relative Humidity Maximum Altitude Above MSL, ft (m) Table 4 4920 (1500) (as per IEC 62040/3) 1% Maximum kW derate / 100m rise between 1500-3000m Liebert eXM TXC, 10-100k, mechanical characteristics Mechanical Characteristics Values Dimensions, W x D x H, in (mm) 23.625 x 39.375 x 78.75 (600 x 1000 x 2000) Color Protection Degree IEC (60529) ZP 7021 (Black) IP20 (finger-proof with front doors open or closed) Rated Power, kVA Weight, lb (kg) 10 827 (376) 15 883 (401) 20 941 (428) 30 1280 (582) 40 1307 (594) 60 1569 (713) 80 1815 (825) 100 2043 (929) 17 Liebert® eXM™ TXC™ Specifications Table 5 Liebert eXM TXC heat dissipation, both transformers, full load Liebert eXM TXC Rating kVA Liebert eXM TXC Heat Dissipation 208:208 Transformer BTU/Hr (kW) Liebert eXM TXC Heat Dissipation 220:220 Transformer BTU/Hr (kW) Liebert eXM TXC Heat Dissipation 480:208 Transformer BTU/Hr (kW) Liebert eXM TXC Heat Dissipation 600:208 Transformer BTU/Hr (kW) 10 3992 (1.152) 3616 (1.060) 3446 (1.010) 3500 (1.026) 15 5008 (1.468) 4640 (1.360) 4948 (1.450) 4906 (1.438) 20 5876 (1.722) 5186 (1.520) 5916 (1.734) 5972 (1.750) 30 9694 (2.842) 8816 (2.584) 8686 (2.546) 9792 (2.870) 40 11,352 (3.328) 10,332 (3.028) 10,010 (2.934) 9976 (2.924) 60 14,958 (4.384) 13,608 (3.988) 13,340 (3.910) 12,890 (3.798) 80 19,224 (5.634) 17,422 (5.106) 18,002 (5.276) 17,784 (5.212) 100 19,456 (5.702) 17,762 (5.206) 19,906 (5.834) 20,084 (5.886) NOTE The breakers and cables used must be in accordance with NEC ANSI/NFPA 70. A disconnect breaker must be provided for Rectifier and Bypass inputs. Recommended cable sizes are suitable for operation at a maximum temperature of 104°F (40°C). Table 6 Recommended lug sizes (compression type) M10, 3/8" bolt Cable Size T&B Copper Two Hole T&B Aluminum Two Hole #6AWG 256-030695-868 — #4AWG 256-030695-733 — #2-3AWG 54811BE — #1AWG 54857BE — #1/0AWG 256-30695-593 — #2/0AWG 54862BE 60238 #3/0AWG 54864BE 60244 #4/0AWG 54866BE 60250 250kcmil 54868BE 60256 300kcmil 54870BE 60262 350kcmil 54872BE 60267 400kcmil 54874BE 60269 500kcmil 54876BE 60273 600kcmil 54878BE 60275 700kcmil 54879BE 60277 750kcmil 54880BE 60278 Table 7 Busbar torque for power wiring Bolt Shaft Size Torque Lb-in (Nm) 3/8" (M10) 192 (22) 1/2" (M12) 428 (48) Liebert® eXM™ TXC™ 18 Specifications Table 8 Terminal block torque with compression lugs for control wiring AWG Wire Size or Range Torque Lb-in (Nm) #22 - #14 3.5 to 5.3 (0.4 to 0.6) NOTE Refer to the manufacturer’s data for proper torque for circuit breaker power connections. Table 9 Electrical data—Liebert eXM TXC, 480VAC input, 208VAC output, rectifier input, with 480V:208V transformer Liebert eXM TXC Rating kVA Maximum Rectifier Input Current, A 10 Phase Recommended Upstream Protection, A 75°C Wire Current A Total Copper Wire Aluminum Wire Bolt Size 15 3W + G 20 40 (1) #8 (1) #8 M10 15 23 3W + G 30 40 (1) #8 (1) #8 M10 20 31 3W + G 40 40 (1) #8 (1) #8 M10 30 46 3W + G 60 65 (1) #6 (1) #4 M10 40 61 3W + G 80 85 (1) #4 (1) #2 M10 60 91 3W + G 125 150 (1) #2 (1) 1/0 M10 80 122 3W + G 175 200 (1) 1/0 (1) 3/0 M10 100 152 3W + G 200 205 (1) 4/0 (1) 250 kcmil M10 See Notes on Tables on page 21. Table 10 Electrical data—Liebert eXM TXC, 480VAC input, 208VAC output, bypass input, with 480V:208V transformer Liebert eXM TXC Rating kVA Maximum System Input Current, A 10 Phase Recommended Upstream Protection, A 75°C Wire Current A Total Copper Wire Aluminum Wire Bolt Size 13 3W + G 20 40 (1) #8 (1) #8 M10 15 19 3W + G 25 40 (1) #8 (1) #8 M10 20 25 3W + G 35 40 (1) #8 (1) #8 M10 30 38 3W + G 50 65 (1) #6 (1) #4 M10 40 50 3W + G 70 85 (1) #4 (1) #2 M10 60 74 3W + G 100 150 (1) #2 (1) 1/0 M10 80 99 3W + G 125 200 (1) 1/0 (1) 3/0 M10 100 124 3W + G 175 205 (1) 4/0 (1) 250 kcmil M10 See Notes on Tables on page 21. 19 Liebert® eXM™ TXC™ Specifications Table 11 Electrical data—Liebert eXM TXC, 600VAC input, 208VAC output, rectifier input, with 600V:208V transformer Liebert eXM TXC Rating kVA Maximum Rectifier Input Current, A 10 Phase Recommended Upstream Protection, A 75°C Wire Current A Total Copper Wire Aluminum Wire Bolt Size 12 3W + G 20 40 (1) #8 (1) #8 M10 15 18 3W + G 25 40 (1) #8 (1) #8 M10 20 25 3W + G 35 40 (1) #8 (1) #8 M10 30 37 3W + G 50 50 (1) #8 (1) #6 M10 40 49 3W + G 70 85 (1) #4 (1) #3 M10 60 73 3W + G 100 100 (1) #3 (1) #1 M10 80 98 3W + G 125 130 (1) #1 (1) 2/0 M10 100 122 3W + G 175 150 (1) 1/0 (1) 3/0 M10 See Notes on Tables on page 21. Table 12 Electrical data—Liebert eXM TXC, 600VAC input, 208VAC output, bypass input, with 600V:208V transformer Liebert eXM TXC Rating kVA Maximum System Input Current, A 10 Phase Recommended Upstream Protection, A 75°C Wire Current A Total Copper Wire Aluminum Wire Bolt Size 10 3W + G 15 40 (1) #8 (1) #8 M10 15 15 3W + G 20 40 (1) #8 (1) #8 M10 20 20 3W + G 30 40 (1) #8 (1) #8 M10 30 30 3W + G 40 50 (1) #8 (1) #6 M10 40 40 3W + G 60 85 (1) #6 (1) #4 M10 60 60 3W + G 80 150 (1) #3 (1) #2 M10 80 79 3W + G 100 200 (1) #1 (1) 1/0 M10 100 99 3W + G 125 205 (1) 1/0 (1) 3/0 M10 See Notes on Tables on page 21. Table 13 Electrical data—Liebert eXM TXC, 208VAC or 220VAC input, rectifier input, with 208V:208V or 220V:220V transformer Liebert eXM TXC Rating kVA Maximum Rectifier Input Current, A 10 36 Phase Recommended Upstream Protection, A 75°C Wire Current A Total Copper Wire Aluminum Wire Bolt Size 3W + G 45 65 (1) #6 (1) #4 M10 15 53 3W + G 70 85 (1) #4 (1) #2 M10 20 71 3W + G 90 100 (1) #3 (1) #1 M10 30 107 3W + G 150 175 (1) 2/0 (1) 4/0 M10 40 141 3W + G 200 230 (1) 4/0 (1) 300 kcmil M10 60 211 3W + G 300 335 (1) 400 kcmil (2) 4/0 M10 80 281 3W + G 400 460 (2) 4/0 (2) 300 kcmil M10 100 352 3W + G 450 510 (2) 250 kcmil (2) 400 kcmil M10 See Notes on Tables on page 21. Liebert® eXM™ TXC™ 20 Specifications Table 14 Electrical data—Liebert eXM TXC, 208VAC or 220VAC input, bypass input, with 208V:208V or 220V:220V transformer Liebert eXM TXC Rating kVA Maximum System Input Current, A 10 Phase Recommended Upstream Protection, A 75°C Wire Current A Total Copper Wire Aluminum Wire Bolt Size 29 3W + G 40 65 (1) #6 (1) #4 M10 15 43 3W + G 60 85 (1) #4 (1) #2 M10 20 58 3W + G 80 100 (1) #3 (1) #1 M10 30 87 3W + G 110 150 (1) 1/0 (1) 3/0 M10 40 116 3W + G 150 230 (1) 4/0 (1) 300 kcmil M10 60 172 3W + G 225 285 (1) 300 kcmil (1) 400 kcmil M10 80 229 3W + G 300 350 (2) 2/0 (2) 4/0 M10 100 286 3W + G 400 460 (2) 4/0 (2) 300 kcmil M10 See Notes on Tables below. Table 15 Liebert eXM TXC Inrush Multiplier Liebert eXM TXC Rating kVA TXC 480V:208V TXC 600V:208V TXC 208V:208V TXC 220V:220V 10 11.7 11.1 8.9 10.8 15 11.3 7.85 6.4 10.2 20 7.8 8.3 6.4 7.7 30 7.4 7.85 6.4 7.7 40 7.65 8.5 6.8 8.2 60 6.7 7.45 5.1 6.2 80 7.1 7.1 6.2 7.5 100 7.1 7.8 6.9 7.4 Note: Inrush Current = NFLA x Tabel Value Notes on Tables Notes apply to Tables 9 through 14. 1. Nominal input current (considered continuous) is based on full rated output load maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current are defined in NEC 100. Recommended overcurrent protection is based on 80% rated devices. *The recommended overcurrent protection represents 125% of nominal full load current (continuous) per NEC 215. 2. Maximum input current is controlled by the current limit setting. 3. Recommended AC input external overcurrent protection is based on 80% rated devices and maximum input current limit setting. 4. Recommended AC output external overcurrent protection is based on 80% rated devices and full rated output current. 5. Input power factor of 0.99 is used for the calculations. 21 Liebert® eXM™ TXC™ Specifications Liebert® eXM™ TXC™ 22 Technical Support / Service Web Site www.liebert.com Monitoring [email protected] 800-222-5877 Outside North America: +00800 1155 4499 Single-Phase UPS & Server Cabinets [email protected] 800-222-5877 Outside North America: +00800 1155 4499 Three-Phase UPS & Power Systems 800-543-2378 Outside North America: 614-841-6598 Environmental Systems 800-543-2778 Outside the United States: 614-888-0246 Locations While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2014 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. SL-25655_REV1_01-16 Emerson Network Power Liebert www.emerson.com United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257 Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center Pasig City 1605 Philippines +63 2 687 6615 Fax: +63 2 730 9572