NetSure 501 Datasheet (English)

NETSURETM 501
DC Power System, -48 V DC, 1.7 – 20.4 kW, 35 – 420 A
Benefits
:9Fem[h\eh
8ki_d[iiø9h_j_YWb9edj_dk_jo
NetSure 501 is the new more compact, and yet more flexible,
Cost and space effective system
configurations thanks to smart and
flexible Multi Function Unit, MFU.
(The MFU houses the controller,
DC and Battery breakers, shunts,
alarm boards and optionally disconnection of loads and/or batteries.
DC power system from Emerson. It is especially developed for
Wide AC input window with high
rectifier DC output.
possibility to very space effectively house both batteries and DC
AC current input limitation possible
on rectifiers. This function enables the
user to employ 10A AC breakers, or
smaller, if desired.
Based upon factory pretested units, subrack and complete
the needs of typical telecom applications in the range between
1.7-20.4 kW.
The packaging of the NetSure 501 system configurations gives the
power system in 400 mm deep configurations.
configurations, new customer configurations and adaptations can
quickly, easily and cost effectively be created with NetSure 501,
and you can trust that the telecom norms and standards specified
for the product are always adhered to.
As the business grows, NetSure 501 is easily extended with
additional capacity and can be upgraded with supplementary
features and functions during live operation.
With NetSure 501 the process of finding a suitable location for an
application and its power supply is facilitated, thanks to the wide
tolerance window of NetSure 501 when it e.g. comes to operating
temperature, AC input window of AC input breaker size.
6.8 kW
15.3 kW
17.0 kW
NETSURETM 501
DC Power System, -48 V DC, 1.7 – 20.4 kW, 35 – 420 A
Technical Specifications
Emerson Network Power
Energy Systems AB SE-141 82 Stockholm, Sweden Phone: +46 8 721 60 00 Fax: +46 8 721 71 77
Typical Applications
Base Transceiver Stations (BTS) and Node B
Small Microwave units
Digital Subscriber line (DSL) Fiber repeaters
Point of Presence (PoP)
Digital Loop Carrier
Electrical System Specification
Nominal system voltage:
Adjustable range for operating voltage:
Output power, system:
Input voltage, nominal:
Input voltage, permitted variation:
Line frequency:
Maximum AC input fuse:
-48 V DC
-42 V DC to 58 V DC
20.4kW @ Vout > 48 V DC
200 – 250 V AC, 1 phase ±20%
85 – 300 V AC ±10%
45 – 65 Hz
normally 16A, but the rectifier can limit
the maximum input AC if smaller AC input fuse
is required
Mechanical system Specification
Dimensions: (HxDxW),
wall/battery rack mounted cabinet:
Dimensions (HxDxW),
stand-alone power cabinet: Dimensions (HxDxW),
stand-alone power cabinet: Details: Front access and top cabling
360/450x400x600 mm
800/1200/1600/1800x400x600 mm
1200/1600/1800/2000/2200x600x600 mm
Environmental System Specification
Temperature range, operating
Relative humidity, operating
EMC
Safety
Cabinet
-5°C to +65°C (full power up to +45°C)
<90%
EN 300 386-2 class B, FCC part 15 class B
IEC 60950, EN 60950-1
IP 20
System units
Cabinet(s)
Control units available
AC terminals
Rectifiers / Power Supply Units
Multi Function Unit, 3U high
:9Fem[h\eh
8ki_d[iiø9h_j_YWb9edj_dk_jo
Wall mounted, battery rack mounted or standard
stand-alone cabinets
Standard Control Unit (see separate SCU datasheet)
Advanced Control Unit (see separate ACU datasheet)
AC terminals for up to 12 rectifiers
Various connection types
R48-1700 (see separate rectifier data sheet)
Up to 12x R48-1700 rectifiers (20.4 kW) per cabinet
1 position for controller housing SCU or ACU, size 2x3 U)
32x13mm circuit breaker positions OR
23x18mm circuit breaker positions
for DC distribution breakers and battery breakers
0 – 2 contactors for optional disconnection levels of
loads and/or batteries
Emerson Network Power
Energy Systems, North America
1122 ”F” Street, Lorain, OH 44052
Phone: 440-246-6999
Fax: 440-246-4876
www.emersonnetworkpower.com/
energysystems/
Emerson Network Power
Co Ltd., China
No. 1 Kefa Rd., Science &
Industry Park
Nanshan District 518057,
Shenzhen, China
Phone: 86-755-860 108 08
www.emersonnetworkpower.com.cn
For global contact, visit:
www.emersonenergy.com
EN/LZT 145 279 RA
© Emerson Network Power Energy Systems 2006
Optional units
Extension DC distribution unit
AC distribution
SM-AC (Supervision Module AC)
SM-BAT (Supervision Module Batteries)
SM-IO (Supervision Module for generic equipment)
A
B
C
D
E
F
G
H
I
40x13 mm circuit breaker positions OR
28x18 mm circuit breaker positions
AC distribution for up to 12 rectifiers
Optional surge protection, RCD and service outlets
See separate data sheet
See separate data sheet
See separate data sheet
Cabling space
DC distribution unit (extension, optional)
Cabling space (incl. AC terminals if no distribution)
Multi function unit
Connection board
Controller
Rectifier rack
Rectifier rack (extension)
AC distribution unit (optional)
A
B
C
E
D
F
G
H
I
;c[hiedD[jmehaFem[h$
J^[]beXWbb[WZ[h_d[dWXb_d]
8ki_d[iiø9h_j_YWb9edj_dk_joJC$
79Fem[h
9edd[Yj_l_jo
:9Fem[h
;cX[ZZ[Z9ecfkj_d]
;cX[ZZ[ZFem[h
Ced_jeh_d]
Ekji_Z[FbWdj
Fem[hFhej[Yj_ed
Fh[Y_i_ed9eeb_d]9edjhebi
HWYai?dj[]hWj[ZIebkj_edi
I[hl_Y[i
Ikh][Fhej[Yj_ed
;c[hiedD[jmehaFem[h$Yec
;c[hiedD[jmehaFem[hWdZj^[;c[hied
D[jmehaFem[hbe]eWh[jhWZ[cWhaiWdZ
i[hl_Y[cWhaie\;c[hied;b[Yjh_Y9e$
ž(&&,;c[hied;b[Yjh_Y9e$