R48-3200 Rectifier Datasheet (English)

R48-3200
Rectifier
-48 V DC, 3200 W
Features and Benefits
 Optimized depth-reduced footprint
allows installation in short-depth racks
and cabinets
 DSP (Digital Signaling Processor)means fewer components, optimized
operation and active load sharing for
increased reliability
DC Power
for Business-Critical Continuity™
Description
The R48-3200 rectifier converts standard AC supply voltages into stable nominal
-48V DC voltage adjustable to the needs of the application. The R48-3200 is a constant
power rectifier designed with the latest patented switch-mode technology using DSP
(Digital Signaling Processor) functionality for efficient operation.
For a higher load capacity, rectifiers can be connected in parallel and intelligent control
can be added with the help of a separate controller.
 Compliant with global standardsdelivers quality, performance
and reliability no matter what the
application or location demands
 High efficiency, up to 92%-reduces
power consumption for lower
operating costs
 Hot pluggable-facilitates future
extensions
 Wide input voltage range-operates in
the most demanding environments
where input voltage changes
 Wide temperature operating range
(-40°C / -40 °F to +75°C / 167°F) -meets
the harshest climatic environment
requirements
R48-3200
R48-3200
Technical Specifications, R48-3200
DC Output
Output voltage, adjustment range
Output power
Output power, derated for input voltage
Output current
Output current limit set point
Efficiency
Psophometric noise (system)
Temperature derating
Control and Monitoring
Rectifier Alarm and Signaling
Visual Indications
% of output power
120
100
80
60
40
20
0
-40
-20
0
20
40
60
80
100
300
350
Temperature(°C)
-42 to -58 V DC
3200 W @ Vout >48 V DC
See diagram
67 A
0 to 67 A
92%
<1mV
<32 dBrnc
See diagram
Output power vs.
Input voltage at Temp<45°C
120
100
80
60
40
20
0
0
50
Alarm and status reported via CAN bus to system Controller
Green LED: Normal Operation
Yellow LED: Alarm
Red LED: Failure
Flashing Red LED: Fan Failure
100
150
200
50
Input voltage (Vac)
Output voltage v.s.
Output current at max. Power 3200W
-40 to +75°C, -40 to +167°F
Output Voltage (V)
Environmental
Temperature Range, Operating
Temperature Range, Storage
Relative Humidity
Altitude
EMC
Output power vs.
Temperature at Uin > 176 Vac
200 to 250 VAC
85 to 290 VAC
45 to 55 Hz
20A
0.99
<5% from 50 to 100% of rated load
% of output power
AC Input
Input voltage, nominal
Input voltage, permitted variation
Line frequency
Max input current
Power factor
THD, Total harmonic distortion
-40 to +75°C, -40 to +167°F
Safety
0 to 95%
2000 m, 6560 ft at full power
ETSI EN 300 386 class B, FCC CFR 47 Part 15 class B,
Telcordia GR-1089-CORE class B
IEC 60950, EN 60950, UL 60950
Mechanics
Dimensions (H×W×D)
Weight
132×85.3×287mm,5.20×3.36×11.3 inches
3.5kg,7.7lbs
Other parts
Controller Units
See separate ACU, SCU, ACU+ and SCU+ datasheets
Ordering information
Product Name
Rectifier 48V,3200W
Product Code
1R483200XXX
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity™.
www.emersonnetworkpower.com
www.emersonnetworkpower.com/energysystems
www.DCpowerefficiency.com
60
50
40
30
20
10
0
0
5 10 15 20 25 30 35 40 45 50 55 60 65 70
Output Current (A)
AC Power
Embedded Power
Precision Cooling
Connectivity
Infrastructure Management & Monitoring
Racks & Integrated Cabinets
DC Power
Outside Plant
Services
Embedded Computing
Power Switching & Controls
Surge Protection
Business-Critical Continuity, Emerson Network Power
and the Emerson Network Power logo are trademarks
and service marks of Emerson Electric Co.
©2010 Emerson Electric Co.
Emerson Network Power reserves the right to alter without notice the specification, design or conditions of supply of any product or service.
2010.4