EPCOS B25671A4247A375 Film capacitors - power factor correction Datasheet

Film Capacitors – Power Factor Correction
PoleCap capacitor
Series/Type:
MKK440-D-15-P
Ordering code: B25671A4247A375
Date:
Version:
June 2009
2
Content of header bars 1 and 2 of data sheet will be automatically entered in headers and footers! Please fill in the
table and then change the color to "white". This ensures that the table disappears (invisible) for the customer PDF.
Don't change formatting when entering or pasting text in the table and don't add any cell or line in and to it!
Identification/Classification 1
(header 1 + top left bar):
Film Capacitors – Power Factor Correction
Identification/Classification 2
(header 2 + bottom left header bar):
PoleCap capacitor
Ordering code: (top right header bar)
B25671A4247A375
Series/Type: (top right header bar)
MKK440-D-15-P
Preliminary data (optional):
(if necessary)
Department:
FK PC PM PFC
Date:
June 2009
Version:
2
 EPCOS AG 2009. Reproduction, publication and dissemination of this publication, enclosures hereto and the information
contained therein without EPCOS' prior express consent is prohibited
Film Capacitors – Power Factor Correction
PoleCap capacitor
B25671A4247A375
MKK440-D-15-P
Construction







Dielectric: Polypropylene film
Gas impregnated / dry type
Concentric winding
Wave cut
Extruded round aluminum can with stud
Provided with ceramic discharge module
Triple safety system
Features




Three-phase, delta connected
Self-healing technology
Naturally air cooled
Outdoor mounting
Ambient
 Highest insulation strength for outdoor applications
(to IEC60831, 15 kV)
 Terminal cover, cable gland and connection cable
made of material resistant to weather, UV radiation
and aging
 Cable UV-resistant
 Housing of pure aluminum (corrosion-free operation)
 Double housing of terminals for protection against
hazardous parts, ingress of solid foreign bodies,
dust and harmful effects of water
Label design
Technical data and specifications
Characteristics
Rated capacitance CR
3 • 82 µF
Tolerance
–5 / +10%
Connection
D (Delta)
Rated voltage VR
440 V AC
Rated frequency fR
50 Hz
60 Hz
Output
15 kvar
18 kvar
Rated current IR
20 A
24 A
tan δ (dielectric)
0.2 W / kvar
FK PC PM PFC
Please read Cautions and warnings and
Important notes at the end of this document.
June 2009
Page 2 of 8
Film Capacitors – Power Factor Correction
PoleCap capacitor
B25671A4247A375
MKK440-D-15-P
Maximum ratings
Vmax (up to 8 h daily)
480 V AC
Vmax (up to 1 min)
570 V AC
Imax
1.3 • IR (A) (including combined
effects of harmonics,
overvoltages and capacitance
tolerance)
IS
200 • IR (A)
Test data
VTT
950 V AC / 50 Hz during 10 s
VTC
3000 V AC / 50 Hz during 10 s
tan δ (50 Hz)*
≤ 0.5 W / kvar
* Without discharge resistor & cable
Climatic category
–40/D
Tmin
–40 ºC
Tmax
+55 ºC
Humidity
av. rel. < 95%
Maximum altitude
4000 m
Mean life expectancy
Mean life expectancy tLD
Up to 100 000 h
Max. 5000 switchings per year to IEC60831
Design data
Dimensions (d × l)
125 × 217 mm
Weight approx
2.1 kg
Impregnation
Dry, inert gas, no PCB
Fixing
Threaded bolt M12
Max. torque (Al can stud)
10 Nm
Mounting position
Upright or horizontal mounting
position possible. See
“Maintenance and Installation
Manual” for further details.
FK PC PM PFC
Please read Cautions and warnings and
Important notes at the end of this document.
June 2009
Page 3 of 8
Film Capacitors – Power Factor Correction
PoleCap capacitor
B25671A4247A375
MKK440-D-15-P
Terminals
Enclosure
IP54 internally protected
Connection cables
Length 2 m (UV resistant and
water proof)
Cable cross section / Cable gland
6 mm2 / PG13.5
Maximum terminal current
50 A
Safety
Mechanical safety
Overpressure disconnector
Max. short circuit current
(AFC: 10 kA)
Discharge resistor time
≤ 60 s to 50 V or less
Reference standards
IEC60831–1/2
Dimensional drawing
FK PC PM PFC
Please read Cautions and warnings and
Important notes at the end of this document.
June 2009
Page 4 of 8
Film Capacitors – Power Factor Correction
PoleCap capacitor
B25671A4247A375
MKK440-D-15-P
Cautions and warnings
 In case of dents of more than 1 mm depth or any other mechanical damage, capacitors must not
be used at all.
 This applies also in cases of oil leakages.
 To ensure the full functionality of the overpressure disconnector, elastic elements must not be
hindered and a minimum space of 12 mm has to be kept above each capacitor.
 Do not handle the capacitor before it is discharged.
 Resonance cases must be avoided by appropriate application design in any case.
 Handle capacitors carefully, because they may still be charged even after disconnection due to
faulty discharging devices.
 Protect the capacitor properly against over current and short circuit.
 Failure to follow cautions may result, worst case, in premature failures, bursting and fire.
Discharging
Capacitors must be discharged to a maximum of 10% of rated voltage before they are switched in
again. This prevents an electric impulse discharge in the application, influences the capacitor’s
service life and protects against electric shock. The capacitor must be discharged to 75 V or less
within 3 minutes. There must be not any switch, fuse or any other disconnecting device in the circuit
between the power capacitor and the discharging device. PoleCap-capacitors have a pre-mounted
ceramic discharge module; alternatively discharge reactors are available from EPCOS. Discharge and
short circuit capacitor before handling!
Service life expectancy
Electrical components do not have an unlimited service life expectancy; this applies to self-healing
capacitors too. The maximum service life expectancy may vary depending on the application the
capacitor is used in.
Safety
Electrical or mechanical misapplication of capacitors may be hazardous. Personal injury or property
damage may result from bursting of the capacitor or from expulsion of oil or melted material due to
mechanical disruption of the capacitor.
 Ensure good, effective grounding for capacitor enclosures.
 Provide means of disconnecting and insulating a faulty component/bank.
 The terminals of capacitors, connected bus bars and cables as well as other devices may also be
energized.
 Follow good engineering practice.
Thermal load/over-temperature
After installation of the capacitor it is necessary to verify that maximum hot-spot temperature is not
exceeded at extreme service conditions.
FK PC PM PFC
Please read Cautions and warnings and
Important notes at the end of this document.
June 2009
Page 5 of 8
Film Capacitors – Power Factor Correction
PoleCap capacitor
B25671A4247A375
MKK440-D-15-P
Overpressure disconnector
To ensure full functionality of an overpressure disconnector, the following must be observed:
1. The elastic elements must not be hindered, i.e.
 Connecting lines must be flexible leads (cables).
 There must be sufficient space (min. 12 mm) for expansion above the connections. This will
enable a longitudinal extension of the can to secure the overpressure disconnector work.
 Folding beads must not be retained by clamps.
2. The maximum allowed fault current of 10000 A in accordance with UL 810 standard must be
assured by the application.
3. Stress parameters of the capacitor must be within the IEC60831 specification.
Resonance cases
Resonance cases must be avoided by appropriate application design in any case. Maximum total
RMS capacitor current (incl. fundamental harmonic current) specified in technical data must not be
exceeded.
Re-switching vs. phase-opposition
In case of voltage interruption, a sufficient discharge time has to be ensured to avoid phaseopposition and resulting high inrush currents.
Vibration resistance
The resistance to vibration of capacitors corresponds to IEC 68, part 2–6.
Max. test conditions:
Test duration
6 h*
Frequency range 1
10 ... 55 Hz*
Displacement amplitude 0.75 mm*
*corresponding to max. 98.1 m/s or 10 g
These figures apply to the capacitor alone. Because the fixing and the terminals may influence the
vibration properties, it is necessary to check stability when a capacitor is built in and exposed to
vibration. Irrespective of this, you are advised not to locate capacitors where vibration amplitude
reaches the maximum in strongly vibrating equipment.
Mechanical protection
The capacitor has to be installed in a way that mechanical damages and dents in the aluminum can
are avoided.
Grounding
The threaded bottom stud of the capacitor has to be used for grounding. In case grounding is done
via metal chassis that the capacitor is mounted to, the layer of varnish beneath the washer and nut
should be removed. The maximum tightening torque is 10 Nm.
FK PC PM PFC
Please read Cautions and warnings and
Important notes at the end of this document.
June 2009
Page 6 of 8
Film Capacitors – Power Factor Correction
PoleCap capacitor
B25671A4247A375
MKK440-D-15-P
Choosing the best spot for mounting
Especially in regions with long periods of sunshine and high temperatures, the PoleCap should be
installed in such a way that it is located in the shadow of the pole for most of the daylight. The
combination of the natural cooling by the wind and the single-housing of the capacitor helps to keep
the hot spot temperature at the lowest level possible.
Maintenance
 Check tightness of the connections/terminals periodically.
 Take current reading twice a year and compare with nominal current. Use a harmonic analyser or
true effective RMS-meter.
 In case of current above the nominal current check your application for modifications.
 If a significant increase in the amount of non-linear loads has been detected, then a consultant
has to be called in for a harmonic study.
 In case of the presence of harmonics installation of a de-tuned capacitor bank (reactors) must be
considered.
 Check the discharge resistors/reactors and in case of doubt, check their function:
(1) Power the capacitor up and down.
(2) After ≤ 60 seconds the voltage between the terminals must decline to 50 V or less.
 Check the temperature of capacitors directly after operation for a longer period, but make sure
that the capacitors have been switched off. In case of excessive temperature of individual
capacitors, it is recommended to replace these capacitors, as this should be an indication for loss
factor increase, which is a sign for reaching end of life.
Storage and operating conditions
Do not use or store capacitors in corrosive atmosphere, especially where chloride gas, sulfide gas,
acid, alkali, salt or the like are present. In dusty environments regular maintenance and cleaning
especially of the terminals is required to avoid conductive path between phases and/or phases and
ground.
Note
For detailed information about PFC capacitors and cautions, refer to the latest version of EPCOS PFC
Product Profile.
FK PC PM PFC
Please read Cautions and warnings and
Important notes at the end of this document.
June 2009
Page 7 of 8
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical
requirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application. As a
rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them
than the customers themselves. For these reasons, it is always ultimately incumbent on the
customer to check and decide whether an EPCOS product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of electronic components or failure
before the end of their usual service life cannot be completely ruled out in the current state
of the art, even if they are operated as specified. In customer applications requiring a very high
level of operational safety and especially in customer applications in which the malfunction or
failure of an electronic component could endanger human life or health (e.g. in accident
prevention or life-saving systems), it must therefore be ensured by means of suitable design of the
customer application or other action taken by the customer (e.g. installation of protective circuitry
or redundancy) that no injury or damage is sustained by third parties in the event of malfunction or
failure of an electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as hazardous). Useful information on this will be found in our Material
Data Sheets on the Internet (www.epcos.com/material). Should you have any more detailed
questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products. Consequently,
we cannot guarantee that all products named in this publication will always be available.
The aforementioned does not apply in the case of individual agreements deviating from the
foregoing for customer-specific products.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version of
the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, BAOKE, Alu-X, CeraDiode, CSMP, CSSP, CTVS, DSSP, MiniBlue,
MKK, MLSC, MotorCap, PCC, PhaseCap, PhaseCube, PhaseMod, PhiCap, SIFERRIT, SIFI,
SIKOREL, SilverCap, SIMDAD, SIMID, SineFormer, SIOV, SIP5D, SIP5K, ThermoFuse, WindCap
are trademarks registered or pending in Europe and in other countries. Further information will
be found on the Internet at www.epcos.com/trademarks.
Page 8 of 8
Similar pages