EPCOS B25838L4156K004 Mkv ac capacitors damping Datasheet

MKV AC Capacitors
B25832
MKV AC capacitors
Damping, Commutating
Ordering code:
Date:
B25838
September 2005
© EPCOS AG 2005. Reproduction, publication and dissemination of this data sheet, enclosures hereto and the
information contained therein without EPCOS' prior express consent is prohibited.
MKV AC Capacitors
B25838
Damping
Features
■ High dielectric strength
■ High peak-current capability
Applications
■ For damping and commutating in the upper frequency range
Construction
■
■
■
■
■
■
■
Self-healing
Plastic dielectric
Oil-impregnated tubular windings (no PCB)
Metal-sprayed end faces ensure reliable contacting
Cylindrical aluminum case
Ceramic lead-throughs
Mounting bolts M8 or M12
Terminals
■ Screw terminals M10
■ Tab connectors 6.3 mm
■ Dual tab connectors 6.3 mm
Mounting
■ If the vibration stress is ≤ 5 g and the capacitors are ≤ 60 mm in diameter
and ≤ 160 mm in height the bolt is used for mounting.
Grounding
■ Mounting bolt for grounding in accordance with VDE 0100
■ Grounding identification in accordance with DIN 40 011
Individual data sheets
Individual data sheets contain detailed specification incl. thermal data.
Upon request, these data sheets are available for each capacitor type.
Please read Cautions and warnings and
Important notes at the end of this document.
2
09/05
MKV AC Capacitors
B25838
Damping
Technical data
Standards
Dielectric dissipation factor
IEC 1071-1/2
EN 61071-1/2
VDE 0560 part 120 and 121
tan δ0
2 · 10 –4
± 10%
Capacitance tolerance
Max. repetitive rate
of voltage rise
(dv/dt)max
Max. non-repetitive rate
of voltage rise
(dv/dt)s
î
---C
IS
---C
Min. operating temperature
Tmin
– 25 °C
Max. operating temperature
Tmax
+ 85 °C
Climatic data:
≤ 95 %
Average relative humidity
Failure quota
αFQ(co)
300 failures per 109 component hours
Load duration
tLD(co)
100 000 h
Storage temperature limit
Tstg
– 55/+ 85 °C
IEC climatic category
(IEC 68-1 and 2)
25/085/56
Test data:
AC test voltage
between terminals
V TT
1,25 · V R, 50 Hz, 10 s (or DC 1.75 x V R, 10 s)
between terminals and case
VTC
2 · V i + 1000 V, 50 Hz, 10 s
Insulating voltage Vi = max. recurrent peak
voltage v̂ / 2
Insulation resistance
R ins
CR ≤ 1 μF: ≥ 10 000 MΩ
Self-discharge time constant
τ =R ins · C
Dissipation factor (50 Hz)
tan δ
CR > 1 μF: ≥ 10 000 s
≤ 3 . 10 –4
Please read Cautions and warnings and
Important notes at the end of this document.
3
09/05
MKV AC Capacitors
B25838
Damping
Characteristics and ordering codes
CR1)
Imax
î
Is
Rins Lself Dimensions Fig.
20 °C
d×l
Appr. Ordering code
weight
μF
A
A
A
mΩ
g
20
40
80
80
80
80
80
350
880
750 1900
1600 4000
2400 6000
3500 8800
5300 13000
7500 19000
20
20
40
80
80
80
80
80
80
280
700
620 1500
1300 3300
1900 4800
2800 7000
3400 8400
4200 10500
6200 15000
9200 23000
VR = AC 1100 V
1,0
2,2
4,7
10
12
15
18
22
20
20
80
80
80
80
80
80
8.0
4.5
2.4
2.2
1.7
1.4
1.1
60
70
90
140
140
140
140
VTT = AC 750 V, 10 s
VTC = AC 2100 V, 10 s
40.0 × 57
40.0 × 95
64.2 × 115
79.2 × 194
79.2 × 194
79.2 × 194
79.2 × 194
3
2
1
1
1
1
1
v̂ = 1100 V
vs = 1500 V
VR = AC 900 V
1.0
2.2
4.7
6.8
10
12
15
22
33
mm
v̂ = 750 V
vs = 1000 V
VR = AC 600 V
2.2
4.7
10
15
22
33
47
nH
600
1300
2800
6000
7200
9000
11000
13000
9.6
4.9
3.1
2.0
1.9
1.7
1.5
1.2
1.1
60
60
70
90
140
140
140
140
140
90
70
170
170
170
170
170
170
40.0 × 57
50.0 × 57
50.0 × 95
64.2 × 115
79.2 × 194
79.2 × 194
79.2 × 194
79.2 × 194
89.3 × 194
3
3
2
1
1
1
1
1
1
90
130
220
450
1100
1100
1100
1100
1500
B25838K6105K001
B25838K6225K001
B25838K6475K009
B25838L6685K004
B25838L6106K004
B25838L6126K004
B25838L6156K004
B25838L6226K004
B25838L6336K004
VTT = AC 1400 V, 10 s
VTC = AC 3000 V, 10 s
40,0 × 95
50,0 × 95
64,2 × 194
79,2 × 194
89,3 × 194
89,3 × 194
89,3 × 194
89,3 × 194
3
3
1
1
1
1
1
1
1) Other capacitance values upon request
Please read Cautions and warnings and
Important notes at the end of this document.
B25838K4225K001
B25838K4475K009
B25838L4106K004
B25838L4156K004
B25838L4226K004
B25838L4336K004
B25838L4476K004
VTT = AC 1150 V, 10 s
VTC = AC 2600 V, 10 s
v̂ = 1400 V
vs = 1900 V
1500 13,0
3300 6,5
7000 3,5
15000 2,1
18000 2,0
23000 1,7
27000 1,5
33000 1,4
90
140
450
1100
1100
1100
1100
4
09/05
140
220
750
1100
1500
1500
1500
1500
B25838K8105K001
B25838K8225K001
B25838L8475K004
B25838L8106K004
B25838L8126K004
B25838L8156K004
B25838L8186K004
B25838L8226K004
MKV AC Capacitors
B25838
Damping
Dimensional drawing 1
Screw terminals M10
Dimensional drawing 2
Dual tab connectors 6.3 mm
l1
Hex nut
M10 DIN 439
Washer
10,5 DIN 433
Tab connector
A 6,3 x 0,8
DIN 46 244
l1
l
l
~4
k
57 _ 3
24,5 _ 2
M10
16+1
l2
ød 1
d
d
M12
9 min.
13 min.
35 1)
21±1
KLK1440-3
Dimensions in mm
Dimensions in mm
d –1,2 I –4 ∅ d1 –0,4 I1 min Creepage
distance k
64.2 115 60.2
78 20
64.2 194 60.2
150 20
79.2 194 75.2
150 20
89.3 194 85.2
150 20
Max. torque terminals*)
7 Nm
KLK1441-B
Clearance
13
13
13
d +0,5
–0,2
I +1
–2
40
95
50
95
l1 max l 2 +1**) Creepage
distance
28
8
10
32
12
14
**) 8 mm = threaded bolt M8
12 mm = threaded bolt M12
13
*) The terminal torque must not act upon the ceramic. So the lead should be locked between to nuts.
1) Dimensions only for orientation, subject for modifications
Mounting parts (included in delivery)
Threaded bolt
Max. torque
Toothed washer
Hex nut
M8
4 Nm
J 8.2 DIN 6797
M 8 DIN 439
M12
10 Nm
J 12.5 DIN 6797
M12 DIN 439
Please read Cautions and warnings and
Important notes at the end of this document.
5
09/05
Clearance
9
9
MKV AC Capacitors
B25838
Damping
l1
Dimensional drawing 3
Tab connectors 6.3 mm
d
l2
l
Tab connector
A 6,3 x 0,8
DIN 46 244
9 min.
21±1
KLK1442-J
Dimensions in mm
d +0,5
–0,2
I +1
–2
40
57
40
57
40
95
50
57
50
95
*) 8 mm =
l1 max l 2 +1*) Creepage
distance
28
8
10**)
32
8
14
32
8
14
32
12
14
32
12
14
Clearance
9
9
9
9
9
threaded bolt M 8, 12 mm =threaded bolt M12
**) Type B25838K4225K001
Mounting parts (included in delivery)
Threaded bolt
Max. torque
Toothed washer
Hex nut
M8
4 Nm
J 8,2 DIN 6797
M 8 DIN 439
M12
10 Nm
J 12,5 DIN 6797
M 12 DIN 439
Please read Cautions and warnings and
Important notes at the end of this document.
6
09/05
MKV AC Capacitors
B25838
Damping, Commutating
Cautions and warnings
Safety
■ In case of dents of more than 1 mm depth or any other mechanical damage, capacitors must not
be used at all. This applies also in cases of oil leakage.
■ Electrical or mechanical misapplication of capacitors may be hazardous. Personal injury or prop-
■
■
■
■
■
■
erty damage may result from bursting of the capacitor or from expulsion of oil or melted material
due to mechanical disruption of the capacitor.
Ensure good, effective grounding for capacitor enclosures.
Observe appropriate safety precautions during operation (self-recharging phenomena and the
high energy contained in capacitors).
Handle capacitors carefully, because they may still be charged even after disconnection.
The terminals of capacitors, connected bus bars and cables as well as other devices may also
be energized.
Follow good engineering practice.
Failure to follow cautions may result, worst case, in premature failures, bursting and fire.
Thermal load
After installation of the capacitor it is necessary to verify that maximum hot-spot temperature is not
exceeded at extreme service conditions (see www.epcos.com/thermal_design).
Mechanical protection
The capacitor has to be installed in a way that mechanical damages and dents in the aluminum can
are avoided.
Storage and operating conditions
Do not use or store capacitors in corrosive atmosphere especially where chloride gas, sulfide gas,
acid, alkali, salt or the like are present. In dusty environments, regular maintenance and cleaning
especially of the terminals is required to avoid conductive path between phases and/or phases and
ground.
Overpressure disconnector
To ensure full functionality of an overpressure disconnector, the following must be observed:
■ The elastic elements must not be hindered, i.e.
– connecting lines must be flexible leads (cables),
– there must be sufficient space (minimum 12 mm) above the connections for expansion of the
overpressure disconnector,
– folding crimps must not be retained by clamps.
■ Stress parameters of the capacitor must be within the IEC61071 specification.
Service life expectancy
Electrical components do not have an unlimited service life expectancy; this applies to self-healing
capacitors too. The maximum service life expectancy may vary depending on the application the
capacitor is used in.
7
09/05
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical requirements that are often placed on our products in the areas of application concerned. We nevertheless expressly point out that such statements cannot be regarded as binding statements
about the suitability of our products for a particular customer application.
As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with
them than the customers themselves. For these reasons, it is always ultimately incumbent on the
customer to check and decide whether an EPCOS product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of passive electronic components
or failure before the end of their usual service life cannot be completely ruled out in the
current state of the art, even if they are operated as specified. In customer applications requiring a very high level of operational safety and especially in customer applications in which the
malfunction or failure of a passive electronic component could endanger human life or health
(e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of suitable design of the customer application or other action taken by the customer (e.g. installation of
protective circuitry or redundancy) that no injury or damage is sustained by third parties in the
event of malfunction or failure of a passive electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this publication may contain substances subject to restrictions in certain jurisdictions (e.g. because they are classed as “hazardous”). Useful information on this will be found in our Material
Data Sheets on the Internet (www.epcos.com/material). Should you have any more detailed
questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products. Consequently, we cannot guarantee that all products named in this publication will always be available.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version
of the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, CeraDiode, CSSP, PhaseCap, PhaseMod, SilverCap, SIFI, SIMID,
SIKOREL, SIOV, SIP5D, SIP5K, TOPcap, UltraCap, WindCap are trademarks registered or
pending in Europe and in other countries. Further information will be found on the Internet at
www.epcos.com/trademarks.
8
09/05
Similar pages