E3 Series® Combined Fire and MNS System Combined Fire and MNS System Description The Gamewell-FCI, E3 Series® Broadband Emergency Voice Evacuation System and the E3 Series Broadband Networked Fire Alarm System can be combined on the common network to form a combination Fire and Mass Notification (MNS) System in accordance with the NFPA and UL Standard UL2572 requirements. The E3 Series modules, nodes and control panels are peer-to-peer, selfregenerating, token ring passing networks consisting of either of the following: • 2 to 64 nodes • up to 122 nodes with the addition of an ANX Note: The ANX is used for Fire applications only. The E3 Series System is a modular design. This adaptable design allows a wide range of configurations to form an integrated, distributed fire alarm system in combination with the audio evacuation for use with both Fire and Mass Notification functions. In addition, the design can be used as a dedicated, standalone Mass Notification System without a fire alarm service. The network communication conveys all of the following Fire Alarm and Mass Notification control functions: • Audio evacuation • Voice paging • Fire fighter communications over a single pair of wires or fiber-optic cable A Region contains only one ACU (Autonomous Control Unit), and multiple LOCs (Local Operating Consoles). Speaker circuits cannot be shared by Regions. The individual node types and modules in the E3 Series System family are interconnected to form the ACU and the LOC panels for Mass Notification as well as the following: • Fire Command • Control and Detection • AV Signaling • Audio functional units within the overall network system E3 Series Combined Fire and MNS System Features • Listed under ANSI/UL® Standard UL2572 for Mass Notification. • Listed under ANSI/UL Standard 864, 9th Edition. • IBC Seismic Certified. • Offers the Base Platform for the Emergency Communications System. • Provides true, seamless and scalable integration for Fire and Mass Notification that is configured applying the E3 Series building blocks using up to 122 nodes. • Includes a cost-effective, supervised, “Style 7” network wiring using a single pair of wire or fiber-optics at 625K baud. • Contains a compact, Local Operating Console (LOC) that is designed for installation in lobbies, doorways and hallways allowing quick access to do the following: - Broadcast MNS announcements. - View the System Status messages. • Designed with a user-friendly, color touchscreen display that provides all Fire and MNS Events at all locations. • Installs a simple configuration of multiple LOCs with expandability from 16 to 64 programmable switches for status, message activation and control. SIGNALING ® E3 Series is a registered trademark of Honeywell International Inc. ® UL is a registered trademark of Underwriter’s Laboratories Inc. S1869 S1949 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com 9021-60758 Rev. C page 1 of 3 ©2016 by Honeywell International Inc. All rights reserved. Features (Continued) • Uses fully supervised wiring outputs for outstanding protection • Broadcasts a digital, audio, resonant sound to meet the intelligibility requirements • Supports each audio node with up to 150 watts of audio power, provided by three, 50 watt amplifiers in addition to providing 50 watts of standby power • Stores distributed, digital message storage at each audio amplifier location for maximum survivability • Applies Advanced Boolean Logic programming to reduce equipment costs by providing software solutions to complex configurations using the following devices. - Timers - Sequencing - Schedulers E3 Series Fire / ACU LOC-TEL LOC LOC-TEL NGA INX Transponder Figure 1 In-Building MNS Setup MASS NOTIFICATION SYSTEM CABINET CONFIGURATIONS CONTROLS ACU MAIN COMMAND CENTER INCC-CAB-C INCC-CAB-C w/Gateway AUDIO LOC REMOTE COMMAND CENTER INCC-CAB-D CAB AA E3 LOC-MIC CAB AA E3 LOC-TEL INCC-CAB-B E3 LOC E3 BROADBAND SYSTEM (DISTRIBUTED AUDIO) INX-CAB-B INX-CAB-C Figure 2 Mass Notification System Cabinet Configurations GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9021-60758 Rev. C page 2 of 3 www.gamewell-fci.com INX-CAB-D Ordering Information Ordering Information (Continued) E3 Cabinets and Remote Cabinets for MNS E3 Cabinets and Remote Cabinets for MNS Part Number Part Number Description REMOTE “AA” CAB SIZE Description CABINET “C” SIZE Dimensions: 19 3/8” W x 30” H x 4 1/2” D (49 W x 76 H x 11 D cm) E3BB-BC/INCC Enclosure, Combination Fire/ACU Black “C” Size E3BB-RC/INCC Enclosure, Combination Fire/ACU Red “C” Size E3BB-BC/INX Enclosure, Transponder, “C” Size, Black E3BB-RC/INX Enclosure, Transponder, “C” Size, Red MOUNTING PLATE, “C” CAB E3-INCC-CPLATE ACU Command Center Module Mounting Plate, “C” Size E3-INX-CPLATE Transponder Module Mounting Plate “C” Size INNER DOOR, “C” SIZE E3ID3-C Assembly, Door, Inner, 3-Bay, “C” Size Remote “AA” CAB Replaces E3BB-BA Dimensions: 19 1/4” W x 10” H x 4 1/2” D (49 W x 25 H x 11 D cm) E3BB-BAA Enclosure, LOC, “AA” Size, Black E3BB-RAA Enclosure, LOC, “AA” Size, Red E3ID3-A Assembly, Door, Inner, 3 Slots, “AA” (NGA, ASM-16 and MIC) E3ID2-TA Assembly, Door, Inner, 2 Slots, “AA” (INCC-TEL and ASM-16) 90510 Kit, AOM-TEL Plate, E3 (LOC) 90492 Thumb Lock REMOTE “AA1 & A2” CAB SIZE Remote “AA1 & A2” CAB Remote “AA1”CAB Replaces E3BB-BA1 Dimensions: 8 3/4” W x 10” H x 4 1/2” D (22.2 W x 25 H x 11 D cm) E3BB-BAA1 Enclosure, “AA1” Size, Black E3BB-RAA1 Enclosure, “AA1” Size, Red Remote “A2” CAB Dimensions: 13 1/4” W x 10” H x 4 1/2” D (40 W x 25 H x 11 D cm) E3BB-BA2 Enclosure, “A2” Size, Black (Deep) E3BB-RA2 Enclosure, “A2” Size, Red (Deep) Flush Cabinet A2 Annunciators E3BB-NGA-FLUSH CAB A2 Remote Flush NGA ANN with Password Protection E3 SERIES CABINETS “B”, “C”, “D” SIZES CABINET “B” SIZE Dimensions: 19 3/8 W x 19 3/8” H x 4 1/2” D (49 W x 49 H x 11 D cm) E3BB-BB Enclosure, LOC “B” Size, Black E3BB-RB Enclosure, LOC “B” Size, Red 1100-0453 INCC-IDT, Inner Door with 2 Slots, INCC-TEL LOC 1100-0454 INCC-ID-6, Inner Door with 6 Slots, INCC-CAB-LOC 1100-0460 INX-CAB, Enclosure, Transponder, B Size, Black 1100-0461 INX-CAB-R, Enclosure, Transponder, B Size, Red CABINET “D” SIZE Dimensions: 19 3/8” W x 41” H x 4 1/2” D (49 W x 104 H x 11 D cm) E3BB-BD/INCC Enclosure, Combination Fire/ACU Black “D” Size E3BB-RD/INCC Enclosure, Combination Fire/ACU Red “C” Size E3BB-BD/INX Enclosure, Transponder, “D” Size, Black E3BB-RD/INX Enclosure, Transponder, “D” Size, Red MOUNTING PLATE “D” CAB E3-INCC-DPLATE ACU Command Center Module Mounting Plate, “D” Size E3-INX-DPLATE Transponder Module Mounting Plate, “D” Size INNER DOOR, “D” SIZE E3ID3-D Assembly, Door, Inner, 3-Bay, “D” Size OPTIONAL EXTENDER PLATE AM-50 Plate AM-50 Extender Plate E3 SERIES TRIMKIT E3-TRIMKIT-A E3-TRIMKIT-A1 E3-TRIMKIT-A2 E3-TRIMKIT-B E3-TRIMKIT-C E3-TRIMKIT-D Assembly, FNL, TrimRing, CAB A/AA Assembly, FNL, TrimRing, CAB AA1 Assembly,FNL, TrimRing, CAB A2, E3 Assembly, FNL, TrimRing, CAB C, E3 Assembly, FNL, TrimRing, CAB C, E3 Assembly, FNL, TrimRing, CAB D, E3 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 www.gamewell-fci.com 9021-60758 Rev. C page 3 of 3