Littelfuse D0900 Fits into wide range of arc-flash application Datasheet

Protection Relays & Controls
Arc-Flash Monitoring
D0100 series & D0900 series
Arc-Flash Relay
Description
The D0100/D0900 Arc-Flash relays provide a simple and costeffective solution for Arc-Flash monitoring. Two light sensors
can be connected directly to one relay, or optional junction
boxes allow up to 16 sensors per relay.
Light Sensors react to light and are available with 180º or 360º
detection area. Sensors are supplied with 5, 10 or 15 m of
cable and a mounting bracket. 1-2 sensors are recommended
per cubicle or drawer.
Installation Diagram
Features & Benefits
Features
Compact module
Fits into wide range of Arc-Flash applications
BENEFITS
Trip time <1 ms
Limits Arc-Flash damage and risk of injury
Two optical
sensor types
Point sensors with 180° or 360° detection area
depending on specific installation
Single Arc-Flash relay can monitor 2 sensors or
junction boxes
Sensor expansion Junction box allows for up to 16 sensors per Arc-Flash
option
relay (8 sensors/box)
Dual sensor input
Place sensors in direct line
of sight to possible arc faults,
preferably pointing down from the ceiling.
Control power
D0100.0010
D0100.0020
D0900.0010
48-220 Vdc
24 Vdc
220-250 Vac
accessories
requirement
A0033.0010 Detector cable
2 x 0.25 mm w/screen. 100 m
Optional
© 2013 Littelfuse Protection Relays & Controls
Littelfuse.com/d0900
Service mode
Allows for system test without tripping
A
Ordering Number
D1100.0010 Diode Logic Unit
Allows for operation in bright environments and
maximum sensitivity in dark environments
Accessories
Ordering Information
A0200.0010 Light Sensor 180˚; 5 m cable
A0200.0020 Light Sensor 180˚; 10 m cable
A0200.0030 Light Sensor 180˚; 15 m cable
A0300.0010 Light Sensor 360˚; 5 m cable
A0300.0020 Light Sensor 360˚; 10 m cable
A0300.0030 Light Sensor 360˚; 15 m cable
D0400.0010 Junction Box.
For 8 sensors, without indication
D0500.0010 Junction Box.
For 8 sensors, with indication
Adjustable light
sensitivity
A0200 (180˚)/A0300 (360˚) Light Sensors
Line-of-sight light sensor detects an arc as small
as 3 kA within a 2-m half-sphere. Available in
180˚ or 360˚; 5, 10, or 15 m cable.
D0400/D0500 Junction Box for parallel connection
of more than 2 sensors for one relay. Designed
to connect up to 8 sensors, and is available with
and without indication. Max. 2 junction boxes
can be connected to one Arc-Flash relay.
Specifications
D0100.0010: 48-220 Vdc
D0100.0020: 24 Vdc
D0900.0010: 220-250 Vac
D0900.0020: 220-250 Vac
D0900.0030: 110 Vac
Thyristor Output
250 Vac/Vdc, 8 A cont., 25 A. for 0.1s, min. load 50 mA
Sensitivity
Adjustable 2,000-24,000 lux
Number of Sensors
Max. 16 pcs. with 2 junction boxes
Response Time
Less than 1 ms
Power Consumption D0100: 4.3 W; D0900: 3.5 W
Ambient Temperature –25°C to + 70°C
EMC
EN50081-1/2 and EN50082-1/2
Dimensions
H 90 mm (3.5”); W 105 mm (4.1”); D 75 mm (3.0”)
Voltage Supply
Required: At least 1 sensor
per cubicle or drawer
Optional
Optional
Optional
Rev: 4-A-050213