Willow D2RH-2012-23-1110-WTLD Industrial interface relay Datasheet

D2RS series
industrial interface relays
• miniature - saves DIN rail space
• lockable test feature (not D2RG)
• optional no test lever
• mechanical operation indicator
• LED indication
• High voltage DC switching version
• RoHS Compliant
Contacts
D2RS-2011
Contact number & arrangement
SPDT (1C)
Contact material
Ag alloy
Max. switching voltage
Min. breaking capacity
Rated load (resistive - cos φ=1)
D2RH-2011
SPDT (1C)
D2RS-2012
DPDT (2 C)
AC/DC 250VAC, 30VDC
D2RG-2022
DPST-NO (2A)
220VDC
W 0.3W
AC1/DC1 10A
16A
Max. switching power
2500VA / 300W 4000VA /480W
Initial resistance
≤ 100mΩ, max. at 1A/24VDC
5A
5A
1250VA / 150W 1100W
Coil
Rated voltage
Operating range of supply voltage
DC 6...125V
6...125V
6...125V
6...125V
AC 12...230V
12...230V
12...230V
Not available
See coil tables 1 & 2
Insulation
Insulation resistance
≥3000MΩ at 500VDC, 50%RH, 25°C
Dielectric strength
coil to contact 5000Vrms, 1min (50Hz)
contact to contact 1000Vrms, 1min (50Hz)
General Data
Operating time
mS ≤ 15
Release time
mS ≤ 15 , ≤ 20 (with diode)
Operating frequency
1200 op/hr at nominal load
Electrical life
ops 1 x 105
Mechanical life
ops 1 x 106 (AC Coil) / 2 x 106 (DC Coil)
Dimensions
Weight
L x W x H 29 x 13 x 36 mm (see Fig 1 for more information)
≤ 21g
Ambient temperature
operating -40 to 70°C
Shock resistance
10G
Vibration resistance
DA 1.5mm 10-55Hz
Page 1 of 3
Ref: D2RS 010713JHM
www.aecsensors.com
Sales Department Tel: (888) 847-6552
See coil table 1
D2RS series
industrial interface relays
DC Coil Data (at 20°C)
Table 1
Coil Resistance (Ω) ±10%
Must Operate Voltage max.
(VDC)
Must Release Voltage min.
(VDC)
Coil Voltage Code
Nominal Voltage (VDC)
1012
12
300
9.0
1.2
1024
24
1200
19.2
2.4
1048
48
4800
38.4
4.8
1110
110
23500
88.0
11.0
1125
125
32500
100.0
12.5
Blue mechanical test button - green LED indicator (see ordering codes)
AC (50/60Hz) Coil Data (at 20°C) Not available for D2RG
Coil Voltage Code
Nominal Voltage (VAC)
Table 2
Coil Resistance (Ω) ±10%
Must Operate Voltage max.
(VAC)
Must Release Voltage min.
(VAC)
5012
12
80
9.6
1.2
5024
24
320
19.2
2.4
5048
48
1350
38.4
4.8
5110
110
6900
88.0
11.0
5230
230
28000
184.0
23.0
Red mechanical test button - red LED indicator (see ordering codes)
Ordering codes
Contact Material
Type
D
2
R
-
2
Contact
arrangement
0
Cover protection
and mounting
-
2
3
Coil code
-
-
Style
S
-
SPDT: 10A/230VAC ,
DPDT: 5A/230VAC
H
-
SPDT: 16A/230VAC
G
-
DPST-NO: 5A / 220VDC
Contact material
20
-
see Tables 1 & 2
AgNi 90/10
Contact arrangement
11
-
SPDT (1C/O) D2RS & D2RH
12
-
DPDT (2 C/O) D2RS only
22
-
DPST-NO (2N/O) D2RG only
Cover protection category
2
-
in cover, IP40
Connection mode
3
-
plug-in, for sockets
NIL
-
No options
WT
-
Test Lever (not available for D2RG)
L
-
LED Indicator = Red; Green for D2RG type. A1+
D
-
Diode (DC Coils only). A1+
Options
Page 2 of 3
Ref: D2RS 010713JHM
www.aecsensors.com
Sales Department Tel: (888) 847-6552
L
D2RS series
industrial interface relays
Overall Dimensions
D2RS-2011-23 - **** - WTL SPDT
D2RH-2011-23 - **** - WTL SPDT
Fig. 1
D2RS-2012-23 - **** - WTL DPDT
D2RG-2022-23 - 10** - L DPST-NO
Wiring Diagrams
Fig. 2
D2RS-2012-23 - ****
D2RS-2011-23 - ****
D2RH-2011-23 - ****
D2RG-2022-23 - ****
DIN Rail mounting sockets for D2R Series relays
D14F-1Z-D2RS
Fig. 3
D14F-2Z-D2RS
Specifications are subject to change without notice. E&OE.
Page 3 of 3
Ref: D2RS 010713HM
American Electronic Components Inc., 1101 Lafayette St. Elkhart, IN46516
www.aecsensors.com
Sales Department Tel: (888) 847-6552
Notes:
1) D14F-1Z-D2RS fits DR2RS-2011 & D2RH-2011 SPDT types
2) D14F-2Z-D2RS fits D2RS-2012 DPDT & D22RG DPST-NO types.
2) Includes retaining clip
4) Can be used with DM**-BK optional plug-in modules