LEM DHR1000C5 Ac/dc current transducer Datasheet

AC/DC Current Transducer DHR-C5
The transducer for the electronic measurement of DC & distorted AC
waveform currents, with galvanic isolation between the primary circuit
(power) and the secondary circuit (measurement). True RMS 0-5V
voltage output.
IPN = 500 .. 1000 A
Electrical data
Primary Nominal
DC & AC Current
IPN (A.t.RMS)
500 2)
600 2)
1000 2)
RL
VC
IC
VSL
ÎP
Primary AC Current
Max. Peak Value 1)
IP (A)
1800
1800
1800
Output voltage
(Analog)
VOUT (VDC)
0-5
0-5
0-5
Load resistance
Supply voltage2)
Current consumption
Output voltage limitation (0 - 5 V)
Overload capability (Ampere Turns)
Type
Features
DHR 500 C5
DHR 600 C5
DHR 1000 C5
≥ 10
+ 20 .. 50
30
< 7
30000
kW
V DC
mA
V
A.t
Performance data
X
Accuracy @ IPN, TA = 25°C (excluding offset)
Linearity
error (1% of IPN .. ± IPN)
L
VOE
Electrical offset voltage, TA = 25°C
TCVOE Temperature coefficient of VOE ( 0..+60 °C)
(-40..+70 °C)
TCVOUT Temperature coefficient of VOUT (% of reading)
tr
Response time to 90 % of IPN step
BW
Frequency bandwidth (± 1 dB) e
< ± 1
% of IPN
< ± 1.0
% of IPN
< ± 1.0
% of IPN
± 2.0
mV/K
± 4.0
mV/K
± 0.1 %/K
< 150
ms
DC 20..6000
Hz
General data
TA
TS
m
IPxx
Surrounding operating temperature
Surrounding storage temperature
Mass
Protection degree
- 40 .. + 70
- 40 .. + 85
260
IP20
°C
°C
g
Notes : 1) The Max. Peak AC Current is the highest peak level of the primary signal that is taken into account for accurate True RMS calculation. Yet the device is designed for maximum continuous True RMS value equal to
IPN, whereas the output is limited by the above specified output limitation.
2)
According to the UL 508 Standard for Safety for Industrial Control Equipment the primary current must not exceed 475 A.t.RMS through the
transducer hole and the supply voltage must not exceed 42VDC..
●● VFD and SCR waveforms current
measurement
●● True RMS output
●● Panel mounting
●● Eliminates insertion loss
●● Isolated plastic case recognized
according to UL94-V0
Advantages
●● Large aperture for cable up to
Ø32mm
●● High isolation between primary
and secondary circuits
●● Easy installation
Applications
●● VFD Controlled Loads
VFD output indicates how the
motor and attached load are
operating.
●● SCR Controlled Loads
Acurate measurement of phase
angle fired or burst fired (time
proportioned) SCRs. Current
measurement gives faster
response than temperature
measurement.
●● Switching Power Supplies and
Electronic Ballasts
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
Application domain
●● Energy and Automation
Page 1/4
120426/00
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Current Transducer DHR-C5
Isolation characteristics
Vb
Vd
Vw
dCp
dCl
CTI
Rated isolation voltage rms 3)
300
V
according to the standard IEC 61010-1 and with the following conditions:
- Reinforced isolation
- Over voltage category CAT III
- Pollution degree PD2
- Heterogeneous field
Rms voltage for AC isolation test 4), 50 Hz, 1min
4.0
kV
Impulse withstand voltage 4), 1.2/50 uS
7.3 kV
Creepage distance
7.2
mm
Clearance distance
7.2
mm
Comparative tracking index (Group I)
> 600
Notes :3) Between primary conductor voltage and ground. The voltage category could be improved according to the insulation characteristic given by the cable manufacturer. The UL 508 Standard for Safety for Industrial Control Equipment requires that only insulated conductors are used as primary circuit with this transducer..
4)
Between primary (completely filling the aperture) and secondary.
Transfer characteristics
Output in V
5
-Ipn
0
+Ipn
Page 2/4
120426/00
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Current Transducer DHR-C5
Safety and warning notes
In order to guarantee safe operation of the transducer and to be able to make proper use of all features and functions,
please read these instructions thoroughly!
Safe operation can only be guaranteed if the transducer is used for the purpose it has been designed for and within the
limits of the technical specifications.
Ensure you get up-to-date technical information that can be found in the latest associated datasheet under www.lem.com.
Caution! Risk of danger
Ignoring the warnings can lead to serious injury and/or cause damage!
The electric measuring transducer may only be installed and put into operation by qualified personnel
that have received an appropriate training.
The corresponding national regulations shall be observed during installation and operation of the transducer and any electrical conductor.
The transducer shall be used in electric/electronic equipment with respect to applicable standards and
safety requirements and in accordance with all the related systems and components manufacturers’
operating instructions.
Caution! Risk of electrical shock
When operating the transducer, certain parts of the module may carry hazardous live voltage (e.g.
primary conductor, power supply).
The user shall ensure to take all measures necessary to protect against electrical shock.
The transducer is a built-in device containing conducting parts that shall not be accessible after installation.
A protective enclosure or additional insulation barrier may be necessary.
The transducer shall not be put into operation if the jaw opening is open (split core version) or the
installation is not completed.
Installation and maintenance shall be done with the main power supply disconnected except if there
are no hazardous live parts in or in close proximity to the system and if the applicable national regulations are fully observed.
Safe and trouble-free operation of this transducer can only be guaranteed if transport, storage and installation are carried
out correctly and operation and maintenance are carried out with care.
Page 3/4
120426/00
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Dimensions DHR-C5 (in mm. 1 mm = 0.0394 inch)
Dimensions DHR-C5 (in mm. 1 mm = 0.0394 inch)
25
Dimensions DHR-C5 (in mm. 170mm = 0.0394 inch)
25
70
60
60
25
70
70
2.50 10
20.34
4
15
2.50
25.60
4.60
25.60
8.30
8.30
78
6
8.30
6
Plug in connector:
FKC2.5/4-ST-5.08
(Phoenix Contact)
Plug in connector:
Plug in connector:
FKC2.5/4-ST-5.08
FKC Contact)
2.5/4-ST-5.08-RF
(Phoenix
(Phoenix Contact)
78
Connections
Connections
DHR
• Wires
up to up
∅2
●● Wires
to mm
Ø 2 mm
Connections
DHR
• Female
connector
provided
(spring
terminal
blocks)
●● Female
connector
provided
(spring
terminal
blocks)
• Wires up to ∅ 2 mm
• User-friendly
spring-cage
connection
for no-tool
direct
conductor
●● User-friendly
spring-cage
connection
for no-tool
direct
• Female connector provided (spring terminal blocks)
connection
conductor connection
• User-friendly spring-cage connection for no-tool direct conductor
connection
Output Connector
1(Vcc) 2(NC) 3(Vout) 4(GND)
24 VDC Power
4
7
78
15
15
7
4.60
33.80
33.80
4.60
33.80
90
25.60
22.28
6
70
40
10
40
4
90
90
10
6.80
2.50
8.30
6.80
8.30
32
40
6.80
6.80
6.80
15
8.30
25
15
25
25
15
22.28
4.
60
6.80
22.28
4.
60
4.
60
32
32
70
60
Output Connector
1(Vcc) 2(NC) 3(Vout) 4(GND)
Mechanical characteristics
Mechanical characteristics
24 VDC Power
(+)
●● General tolerance
±1 mm
±1 mm
Ø 32.0 mm
•
Primary
aperture
∅
32.0
mm Ø 4.6 mm
●
●
Panel
mounting
• General tolerance
±1 mm 4 holes
•
Panel
mounting
4
holes
4.6 &mm
●
●
Distance
between
holes
70.0
78 mm
• Primary aperture
∅ 32.0 mm ∅mm
• Distance
holes
70.0
& 78 mm
(see between
above dimensions)
• Panel
mounting
4 holes
∅ mm
4.6 mm
(see&above
dimensions)
panel holes
mounting, use70.0
M4 screws
(not
supplied)
with
• DistanceFor
between
mm
78
mm
(see
above
For panel
mounting,
replace
M4
screws
bydimensions)
new
one
(not supplied)
appropriate
length
to panel´s
thickness,
and
tighten
to
Forwith
panel
mounting,
replace
M4panel´s
screws thickness.
by new one (not supplied)
appropriate
lengthtorque.
to
0.75Nm +/-20%
Mechanical
characteristics
• General
tolerance
●● Primary
aperture
(+)
(-)
(-)
(-)
(-)
10k
10k
(+)
Load (+)
Loadmeter etc)
(Controller,
with appropriate length to panel´s thickness.
(Controller, meter etc)
Remarks
Remarks
●● The temperature of the primary busbar can not exceed
Remarks
+24VDC
+24VDC
Is
Is
Ip
OUT
OUT
Ip
GND
GND
120426/00
080725/15
080725/15
• The temperature
of the primary busbar can not exceed 90 °C.
90 °C.
• The
temperature
of the primary
canwith
not exceed
90 busbar
°C.
• Dynamic
performances
arebusbar
the
a primary
●● Dynamic
performances
arebest
the best
with
a primary
• Dynamic performances are the best with a primary busbar
completely
the primary
busbarfilling
completely
filling aperture.
the primary aperture.
completely filling the primary aperture.
• This
a standard
model.
For different
versions
(supply voltages,
●● is
This
is a standard
model.
For different
versions
• This is a standard model. For different versions (supply voltages,
different
outputs,
bidirectional
please
(supply
voltages,
different measurements...),
outputs, bidirectional
different outputs, bidirectional measurements...), please
contact
us.
measurements...),
please
contact
us.
contact us.
Page 4/4
Page 4/4
LEM
reserves
rightto
to carry
carry out
its its
transducers,
in order
to improve
them, without
prior notice.
LEM
reserves
thetheright
outmodifications
modificationsonon
transducers,
in order
to improve
them, without
prior notice.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 4/4
www.lem.com
www.lem.com
www.lem.com
Similar pages