Battery BPL33-12 Valve regulated lead-acid rechargeable battery Datasheet

Valve Regulated Lead-Acid Rechargeable Battery
BPL33-12
The battery is constructed by plates,
separators, safety valves and container.
Since the electrolyte is held by a glassmat separator and plates, the battery
can be used in any direction and position
without leakage.
PERFORMANCE SPECIFICATIONS
Nominal Voltage(V)........................................................................................................................................12 volts(6cells in series)
Nominal Capacity(AH)
20 Hour rate F.V.(1.75V/cell) (1650mA to 10.50volts) .................................................................................................33.0A.H.
10 Hour rate F.V.(1.75V/cell) (3140mA to 10.50volts) ................................................................................................31.4A.H.
5 Hour rate F.V.(1.75V/cell) (5610 mA to 10.50volts) .................................................................................................28.1A.H.
30 Min rate F.V.(1.30V/cell) (33000mA to 7.80volts).....................................................................................................16.5A.H.
Approximate Weight............................................................................................................................................... 11500g(25.36lbs.)
Terminal
Standard................................................................................................................................................................................Type B7
Optional..............................................................................................................................................................Type I2
Internal Resistance (Fully Charged Battery)............................................................................................................................<9m
Maximum Discharge Current For 5 sec.(A)...............................................................................................................................495A
Maximum Charge Current(A)........................................................................................................................................................9.9A
Ambient Temperature
Charge..........................................................................................................................................................0oC(32oF)~40oC(104oF)
Discharge...................................................................................................................................................-20oC(-4oF)~50oC(122oF)
Storage.......................................................................................................................................................-20oC(-4oF)~40oC(104oF)
Vibration test:
Frequency: 16.7HZ
Amplitude: 4mm
Vibrate the battery horizontally or vertically for 60 minutes. The battery have no abnormality.
D e s i g n L i f e : 1 0 y e a r s f o r s t a n d b y u s e a t 2 0 OC
Case..................................................................................................................................................................................................ABS
Dimension(mm/inch)
Length
1.5mm....................................................................................................................................................210/8.27
Width
1.5mm....................................................................................................................................................129/5.08
Container Height 1.5mm....................................................................................................................................................168/6.61
Total Height
2mm.......................................................................................................................................................179/7.05
Application......................................................................Wheelchairs, Lawn Mowers, Electronic Medical Equipment, Golf-Carts.
Battery Charging Characteristics
BPL33-12 Battery discharge characteristics (25 O C/77 O F)
(Typical example of charge characteristic for the standby use)
13.0
5.61A 3.14A 1.65A
8.25A
10.0
19.8A
9.0
8.0
99A 66A
33A
15.0
120
0.18
14.0
100
80
60
40
Charge voltage(V)
Terminal Voltage(V)
11.0
0.21
Charge current(CA)
Charge volume(%)
12.0
140
0.15
0.12
0.09
0.06
20
0.03
0
0
Charge voltage
13.0
C ha rg e
vo lu m e
1 Discharge
100 %(0.1CA x10h)
50 %(0.1CA x 5h)
2 Constant voltage charging
Charge voltage:2.275V/cell
Charge current:0.1CA
3 Temperature 20 O C(68 O F)
12.0
11.0
10.0
Charge current
7.0
1
2
3
5
10
20
30
60
2
3
5
10
20
30
0
For standby
power Source
For
cycle service
Constant
voltage &
Constant
current
charging
(with current
restriction)
2.25~2.30
-3
2.40~2.50
Max. charging
current
(CA)
Charging time
o
0.1CA, 20 C
(h)
100%
discharge
50%
discharge
24
0.3
0.3
-4
25
Testing Conditions :Discharge Current : 0.25C Amp(F.V. 1.7v/cell)
Charging Current : 0.1C Amp
Charging Volume : 120% OF Discharge Capacity
Ambient Temperature : 20 o C(68 o F)
Retention Capacity(%)
Charging
method
20
Battery Life Characteristics of Cyclic Use
Charging Procedure
Temperature
compensation
coefficient of
charging voltage
o
(mV/ C/cell)
15
Charge Time (hr)
Discharge time
Application
10
5
Hr
Min
Charging
Voltage
o
at 20 C
(V/cell)
0
20
16
10
120
100
80
60
40
100%
50 %
(Depth of discharge) (D.O.D.)
30%
(D.O.D.)
20
*Temperature compensation of charging voltage is not needed, when using the batteries within5 o C to 35 o C range.
0
0
300
600
900
1200
1500
Number of cycles
TERMINAL TYPE
mm(inch)
OUTER DIMENSIONS
Constant power discharge characteristics at 25OC/77 OF
Terminal B7
Discharge time
6.2(0.24)
16.2(0.64)
6.5(0.26)
14.8(0.58)
6.9(0.27)
Final
Voltage
[M6 BOLT & NUT]
210 1.5(8.27 0.06)
195 1.5(7.68 0.06)
2.0(0.08)
M6
168 1.5(6.61 0.06)
179 2(7.05 0.08)
10Min
15Min
1Hr
30Min
3Hr
5Hr
10Hr
20Hr
Battery output power(W)
10.80V
1075
808.0
654.3
393.6
228.2
96.2
66.5
37.05
19.38
10.50V
1245
875.4
685.0
408.7
234.8
98.1
67.4
37.62
19.80
10.20V
1320
907.0
705.7
417.7
239.0
99.0
67.9
37.81
19.89
9.90V
1381
928.7
722.2
423.8
242.3
99.9
68.4
37.90
19.94
9.60V
1424
947.1
736.4
428.1
244.7
100.4
68.4
37.90
19.94
Terminal I2
129 1.5(5.08 0.06)
USA:
B&B BATTERY(USA) INC.
6415 RANDOLPH ST.COMMERCE,
CA,90040 U.S.A.
TEL:1-323-278-1900.1-800-278-8599
FAX:1-323-278-1268
E-Mail:[email protected]
EUROPE:
B&B BATTERY(EUROPE) B.V.
3 WIJNGAARDVELD, 9300 AALST,BELGIUM
TEL:(00)32-53781567
FAX:(00)32-53781567
E-Mail:[email protected]
5Min
TERMINAL POSITION
[M6 BOLT]
RAOPING, GUANG DONG,CHINA,515700
TEL:86-768-7601001-2
FAX:86-768-7601469
E-Mail:[email protected]
JAPAN:
B&B BATTERY(JAPAN) CO., LTD.
1375-11 NARAHARA-MACHI,HACHIOJI,
TOKYO 193-0803,JAPAN.
TEL:81-426-25-6375
FAX:81-426-25-6375
E-Mail:[email protected]
HONG KONG:
NATIONAL TRADING LTD.
TEL:852-2301-3800
FAX:852-2739-1182
E-Mail:[email protected]
TAIWAN:
B.B. BATTERY(TAIWAN) CO., LTD.
TEL:886-6-502-5150
FAX:886-6-589-8087
E-Mail:[email protected]
CHINA FACTORY:
REV. Jul. 2005
Similar pages