Bulletin No. DLC-J Drawing No. LP0495 Released 09/16 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 www.redlion.net DUAL LOOP CONTROLLER MODULAR BUILDING BLOCK FOR MULTI-ZONE PROCESS CONTROL TWO INDEPENDENT PID CONTROL LOOPS PID CONTROL WITH REDUCED OVERSHOOT UNIVERSAL INPUTS ACCEPT TC, RTD, 0-10 V AND 0/4-20 mA SIGNALS TWO DC ANALOG OUTPUTS (OPTIONAL) WINDOWS® CONFIGURATION SOFTWARE RS485 MODBUS™ PROTOCOL C UL US LISTED R 3RSD PROCESS CONTROL EQUIPMENT CHANNEL B CAN BE ASSIGNED AS A SECOND ANALOG INPUT TO CHANNEL A FOR REMOTE SETPOINT OPERATION SETPOINT CONTROLLER OPTION FOR TIME VS. TEMP./PROCESS (RAMP/SOAK) AND SPECIAL BATCH/RECIPE APPLICATIONS SQUARE ROOT EXTRACTION FOR FLOW SENSOR APPLICATIONS GENERAL DESCRIPTION SAFETY SUMMARY All safety related regulations, local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. Do not use the controller to directly command motors, valves, or other actuators not equipped with safeguards. To do so can be potentially harmful to persons or equipment in the event of a fault to the controller. An independent and redundant temperature limit indicator with alarm outputs is strongly recommended. The Model DLC, Dual Loop Controller, is a full featured, DIN rail mounted, dual input PID controller. The DLC is designed as a modular building block for multi-zone process control applications. The controller has two independent “A” & “B” input channels. Each channel’s input can be configured to accept a wide range of thermocouple, RTD, 0-10 V, 0/4-20 mA, or resistive signals. Each channel can also be configured to extract the square root of the input in both process voltage or process current modes for applications such as flow measurement using a differential flow sensor. Channel B can be assigned as a Remote Setpoint for Channel A. The two time-proportioning or DC Analog outputs can be programmed to control two independent processes. The two alarms per channel can be configured for various alarm modes, or provide a secondary control output for heat/cool applications. The control and alarm outputs are N channel open drain MOSFETs capable of switching up to 1 Amp DC. For applications requiring larger loads or A/C loads, several DIN rail mount relays are available. The controller operates in the PID Control Mode for both heating and cooling, with on-demand auto-tune, that establishes the tuning constants. The PID tuning constants may be fine-tuned through the serial interface. The controller employs a unique overshoot suppression feature, which allows the quickest response without excessive overshoot. The controller can be transferred to operate in the Manual Mode, providing the operator with direct control of the output, or the On/Off Control Mode with adjustable hysteresis. The controller’s high density packaging and DIN rail mounting saves time and panel space. The controller snaps easily onto standard top hat (T) profile DIN rails. CAUTION: Risk of Danger. Read complete instructions prior to installation and operation of the unit. ALARMS The DLC’s two solid-state alarms can be configured independently for absolute high or low acting with balanced or unbalanced hysteresis. They can also be configured for deviation and band alarm. In these modes, the alarm trigger values track the setpoint value. Adjustable alarm trip delays can be used for delaying output response. The alarms can be programmed for Automatic or Latching operation. Latched alarms must be reset with a serial command. A standby feature suppresses the alarm during power-up until the temperature stabilizes outside the alarm region. The outputs can also be manually controlled with Modbus register or coil commands. SETPOINT CONTROLLER OPTION The Setpoint Controller option is suitable for time vs. temperature/process control applications. The controller allows a profile of up to 20 ramp/soak segments. Profile conformity is assured by using the Error Band Mode and Error Band parameter. The Profile Cycle Count allows the profile to run continuously or a fixed number of cycles. Power-on options automatically stop, abort, start, resume, or pause a running profile. DIMENSIONS In inches (mm) 11 4.47 (114) RED LION CONTROLS OUT - 10 RED LION CONTROLS MODEL DLC PWR/COMM. 4.02 (102) ALL FLASHING = CHECKSUM ERROR OPTIONAL OUT + 9 MADE IN U.S.A. OUT - 8 YORK, PA. OUT + 7 ANALOG OUTPUT 2 0-10V, 0-20mA 6 ANALOG OUTPUT 1 0-10V, 0-20mA TC+ OR RTD 5 CH B OUTPUTS I2V2I2+ V2+ I1V1I1+ V1+ INPUT COMMON 4 0-10V, 0-20mA RTD EXC. 3 DEFAULT SERIAL SETTING CH A INPUTS 0-10V, 0-20mA RTD EXC. TC+ OR RTD TBB INPUT COMMON PROCESS CONTROL EQUIPMENT 2 10 CH A OUTPUTS 10V 20mA RTD 10V 20mA RTD 3RSD 1 9 MODEL DLC AL1 ! JUMPERS CH B INPUTS 8 AL2/OP2 OP1 DC- / (AC) DC+ / (AC) FACTORY JUMPER SETTINGS 7 AL2/OP2 6 AL1 5 OP1 4 ต ต 3 +24VDC OUT 2 OUTPUT COMMON TBA DC 18-36V, 13W AC 24V ±10%, 50/60 Hz, 15VA POWER: (FULL LOAD) ต 1 CH A OP CH A ALM ORDERING INFORMATION BOTH FLASHING = INPUT ERROR MODEL NO. AUTOTUNE CH B OP CH B ALM DLC BOTH FLASHING = INPUT ERROR SF RS485 MODBUS PROTOCOL CBPRO 1.97 (50) DESCRIPTION PART NUMBERS Dual Loop Controller DLC00001 Dual Loop Controller w/ 2 Analog Outputs DLC01001 Dual Setpoint Controller w/ 2 Analog Outputs DLC11001 PC Configuration Software for Windows SFDLC Programming Interface Cable CBPRO007 CBJ Cable RJ11 to RJ11 (6 inch jumper) CBJ11BD5 DRR RJ11 to Terminal Adapter DRRJ11T6 RS485 to RJ11 Cable CBLRLC00 See our RSRLYB, RLY6, and RLY7 literature for details on DIN rail mountable relays. 1 7. TEMPERATURE INDICATION ACCURACY: ± (0.3% of span, +1°C). Includes NIST conformity, cold junction effect, A/D conversion errors, temperature coefficient and linearization conformity at 23 °C after 20 minute warm up. 8. PROCESS INPUT: COMMUNICATIONS The RS485 serial communications allows the DLC to be multi-dropped, with Baud rates up to 38400. The CBPRO007 programming cable converts the RS232 port of a PC to RS485 and is terminated with an RJ11 connector. The bi-directional capability of the CBPRO007 allows it to be used as a permanent interface cable as well as a programming cable. INPUT RANGE SOFTWARE The DLC is programmed with Windows® based SFDLC software. The software allows configuration and storage of DLC program files, as well as calibration. Additionally, all setup and control parameters can be interrogated and modified through MODBUS™ register and coil commands. 10 VDC (-1 to 11) 20 mA DC (-2 to 22) ANALOG OUTPUT OPTION SPECIFICATIONS 1. POWER: 18 to 36 VDC, 13 W (4 W if +24 VDC Output excitation is unused) 24 VAC, ±10% 50/60 Hz, 15 VA (7 VA if +24 VDC Output excitation is unused) Must use a Class 2 or SELV rated power supply. 2. +24 VDC OUTPUT POWER: 24 VDC, +15%, -5%, 200 mA max 3. MEMORY: Non-volatile memory retains all programmable parameters. 4. INPUT: Sample Time: 100 msec (9.5 Hz) Failed Sensor Response: Open or shorted (RTD only) sensor coils indication, error code returned in Process Value Common Mode Rejection: >110 dB, 50/60 Hz Normal Mode Rejection: >40 dB, 50/60 Hz Temperature Coefficient: 0.013%/°C Overvoltage: 50 VDC max Step Response Time: 300 msec typ., 400 msec max 5. THERMOCOUPLE INPUTS: Types: T, E, J, K, R, S, B, N, C, linear mV Input Impedance: 20 MΩ Lead Resistance Effect: 0.25 µV/Ω Cold Junction Compensation: Less than ±1°C typical (±1.5°C max) over 0 to 50°C ambient temperature range or less than ±1.5°C typical (2°C max) over -20 to 65°C maximum ambient temperature range. Resolution: 1° or 0.1° for all types except linear mV (0.1 or 0.01 mV) T E J K R S B N C W5/W6 mV WIRE COLOR MEASUREMENT RANGE -200 to +400°C -328 to +752°F -200 to +750°C -328 to +1382°F -200 to +760°C -328 to +1400°F -200 to +1250°C -328 to +2282°F 0 to +1768°C +32 to +3214°F 0 to +1768°C +32 to +3214°F +149 to +1820°C +300 to +3308°F -200 to +1300°C -328 to +2372°F 0 to +2315°C +32 to +4199°F -5 mV to 56 mV ANSI BS 1843 (+) Blue (-) Red (+) Violet (-) Red (+) White (-) Red (+) Yellow (-) Red (+) White (-) Blue (+) Brown (-) Blue (+) Yellow (-) Blue (+) Brown (-) Blue (+) White (-) Blue (+) White (-) Blue No Standard No Standard No Standard No Standard (+) Orange (-) Red (+) Orange (-) Blue No Standard No Standard N/A N/A 6. RTD INPUTS: Type: 2 or 3 wire Excitation: 150 µA Lead Resistance: 15 Ω max Resolution: 1 or 0.1° for all types TYPE INPUT TYPE 385 100 Ω platinum, Alpha = .00385 392 100 Ω platinum, Alpha = .003919 672 120 Ω nickel, Alpha = .00672 ohms Linear Resistance IMPEDANCE MAX CONTINUOUS OVERLOAD RESOLUTION 1 MΩ 50 V 1 mV 10 Ω 100 mA 1 µA 0.10% of reading +0.02 V 0.10% of reading +0.03 mA * Accuracies are expressed as ± percentages after 20 minute warm-up. 9. ISOLATION LEVEL: 500 VAC @ 50/60 Hz, for one minute (50 V working) between the following groups: Ch A Input Ch B Input Control and Alarm Outputs RS485/Analog Output 1 Power Supply Note: 1 RS485 and Analog Outputs are not internally isolated. Their commons must not be connected together externally for proper unit function (i.e., earth ground). 10. SERIAL COMMUNICATIONS: Type: RS485; RTU and ASCII MODBUS modes Baud: 300, 600, 1200, 2400, 4800, 9600, 19200, and 38400 Format: 7/8 bits, odd, even, and no parity Transmit Delay: Programmable: See Transmit Delay explanation. Transmit Enable (TXEN): (primarily for 20 mA loop converter) open collector VOH = 10 VDC max, VOL = 0.5 VDC @ 5 mA max current limit 11. A/D CONVERTER: 16 bit resolution 12. CONTROL AND ALARM OUTPUTS: Type: Non-isolated switched DC, N Channel open drain MOSFET Current Rating: 1 A max VDS ON: 0.3 V @ 1 A VDS MAX: 30 VDC Offstate Leakage Current: 0.5 mA max 13. MAIN CONTROL: Control: PID or On/Off Output: Time proportioning or DC Analog Cycle Time: Programmable Auto-Tune: When selected, sets proportional band, integral time, derivative time values, and output dampening time Probe Break Action: Programmable 14. ALARM: 1 or 2 alarms Modes: Manual (through register/coil) Absolute High Acting (Balanced or Unbalanced Hysteresis) Absolute Low Acting (Balanced or Unbalanced Hysteresis) Deviation High Acting Deviation Low Acting Inside Band Acting Outside Band Acting Reset Action: Programmable; automatic or latched Standby Mode: Programmable; enable or disable Hysteresis: Programmable Sensor Fail Response: Upscale 15. COOLING: Software selectable (overrides Alarm 2). Control: PID or On/Off Output: Time proportioning or DC Analog Cycle Time: Programmable Proportional Gain Adjust: Programmable Heat/Cool Deadband Overlap: Programmable 16. ANALOG DC OUTPUTS: (optional) Control or retransmission, programmable update rate from 0.1 sec or 1 to 250 sec Step Response Time: 100 msec The optional dual DC Analog Output (10 V or 20 mA) can be independently configured and scaled for control or re-transmission purposes. These outputs can be assigned to separate channels, or both outputs can be assigned to the same channel. Programmable output update time reduces valve or actuator activity. TYPE ACCURACY * (18 to 28°C) (10 to 75% RH) RANGE -200 to +600°C -328 to +1100°F -200 to +600°C -328 to +1100°F -80 to +215°C -112 to +419°F 0 to 320 Ω OUTPUT RANGE** 0 to 10 V 0 to 20 mA 2 ACCURACY * (18 to 28°C) (10 to 75% RH) 0.10% of FS + 1/2 LSD 0.10% of FS + 1/2 LSD COMPLIANCE RESOLUTION (TYPICAL) 10 KΩ min 1/18000 500 Ω max 1/18000 OUTPUT RANGE** ACCURACY * (18 to 28°C) (10 to 75% RH) COMPLIANCE RESOLUTION (TYPICAL) 4 to 20 mA 0.10% of FS + 1/2 LSD 500 Ω max 1/14400 * Accuracies are expressed as ± percentages after 20 minute warm-up. ** Outputs are independently jumper selectable for either 10 V or 20 mA. The output range may be field calibrated to yield approximate 10% overrange and a small underrange (negative) signal. 17. ENVIRONMENTAL CONDITIONS: Operating Temperature Range: -20 to +65°C Storage Temperature Range: -40 to +85°C Operating and Storage Humidity: 85% max relative humidity, noncondensing, from -20 to +65°C Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g Shock to IEC 68-2-27: Operational 30 g Altitude: Up to 2000 meters 18. CERTIFICATIONS AND COMPLIANCE: CE Approved EN 61326-1 Immunity to Industrial Locations Emission CISPR 11 Class A Safety requirements for electrical equipment for measurement, control, and laboratory use: EN 61010-1: General Requirements EN 61010-2-030: Particular Requirements for Testing and Measuring Circuits RoHS Compliant UL Listed: File #E179259 IP20 Enclosure rating 19. CONSTRUCTION: Case body is black high impact plastic. Installation Category I, Pollution Degree 2. 20. CONNECTIONS: Wire clamp screw terminals. Removable terminal blocks. 21. MOUNTING: Snaps on to standard DIN style top hat (T) profile mounting rails according to EN50022 -35 x 7.5 and -35 x 15. 22. WEIGHT: 10.5 oz. (298 g.) BLOCK DIAGRAM +24V OUT +5V MAIN DIG +5Vo DIG +5VC DIG +5VC -3.6VC +5VS DIG +5VS -3.6VS +18V +13.3V -0.6V +2.5V TBA 1 INPUT POWER POWER SUPPLY 2 24VDC 24 VDC 3 OUTPUT COMM. 4 TBB ISOLATED 5VC 1 INPUT B COMMON 2 INPUT B TC+ / RTD 3 INPUT B 0-10V, 0-20mA RTD EXC 4 INPUT A COMMON 5 INPUT A TC+ / RTD 6 INPUT A 0-10V, 0-20mA RTD EXC 7 DEFAULT SERIAL SETTINGS 8 ANALOG OUT 1 + 0-10V, 0-20mA 9 ANALOG OUT 1 - 10 ANALOG OUT 2 + 0-10V, 0-20mA 11 ANALOG OUT 2 - C A/D CONV. 5VC 4.99K 20M 976K C 5VC 10 Ω 4.02K D C 24V I OP1 5 ISOLATED ANNUNCIATORS 24V 5VS S 2 AL1 E MEMORY I 6 24V A/D CONV. 5VS AL2/OP2 I 7 PROCESS CIRCUITRY 10 Ω 24V AL1 S DIP SWITCHES I 9 24V AL2/OP2 S 4.02K D I 8 20M 976K 5VS 24V OP1 4.99K 5V MAIN DIG ISOLATED D/A CONV. (PWM) I 10 V+ +18V I+ O O V- I O 25.5 Ω 5Vo DIG BA+ GND 5V MAIN DIG D/A CONV. (PWM) 5V MAIN DIG V+ V- TXEN O 25.5 Ω U U (DO NOT CONNECT O AND U I+ O O I- +18V D RS485 O ) 3 O I- EMC INSTALLATION GUIDELINES effective. The following EMI suppression devices (or equivalent) are recommended: Fair-Rite part number 0443167251 (Red Lion Controls #FCOR0000) Line Filters for input power cables: Schaffner # FN2010-1/07 (Red Lion Controls #LFIL0000) 6. To protect relay contacts that control inductive loads and to minimize radiated and conducted noise (EMI), some type of contact protection network is normally installed across the load, the contacts or both. The most effective location is across the load. a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide varistor (MOV) across an AC inductive load is very effective at reducing EMI and increasing relay contact life. b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor switch, care must be taken not to exceed the breakdown voltage of the transistor when the load is switched. One of the most effective ways is to place a diode across the inductive load. Most Red Lion products with solid state outputs have internal zener diode protection. However external diode protection at the load is always a good design practice to limit EMI. Although the use of a snubber or varistor could be used. Red Lion part numbers: Snubber: SNUB0000 Varistor: ILS11500 or ILS23000 7. Care should be taken when connecting input and output devices to the instrument. When a separate input and output common is provided, they should not be mixed. Therefore a sensor common should NOT be connected to an output common. This would cause EMI on the sensitive input common, which could affect the instrument’s operation. Although Red Lion Controls products are designed with a high degree of immunity to Electromagnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, source or coupling method into a unit may be different for various installations. Cable length, routing, and shield termination are very important and can mean the difference between a successful or troublesome installation. Listed are some EMI guidelines for a successful installation in an industrial environment. 1. A unit should be mounted in a metal enclosure, which is properly connected to protective earth. 2. Use shielded cables for all Signal and Control inputs. The shield connection should be made as short as possible. The connection point for the shield depends somewhat upon the application. Listed below are the recommended methods of connecting the shield, in order of their effectiveness. a. Connect the shield to earth ground (protective earth) at one end where the unit is mounted. b. Connect the shield to earth ground at both ends of the cable, usually when the noise source frequency is over 1 MHz. 3. Never run Signal or Control cables in the same conduit or raceway with AC power lines, conductors, feeding motors, solenoids, SCR controls, and heaters, etc. The cables should be run through metal conduit that is properly grounded. This is especially useful in applications where cable runs are long and portable two-way radios are used in close proximity or if the installation is near a commercial radio transmitter. Also, Signal or Control cables within an enclosure should be routed as far away as possible from contactors, control relays, transformers, and other noisy components. 4. Long cable runs are more susceptible to EMI pickup than short cable runs. 5. In extremely high EMI environments, the use of external EMI suppression devices such as Ferrite Suppression Cores for signal and control cables is Visit http://www.redlion.net/emi for more information on EMI guidelines, Safety and CE issues as they relate to Red Lion products. STEP 1 SETTING THE JUMPERS AND DIP SWITCHES ANALOG DC OUTPUTS (OPTIONAL) The jumpers are accessible from the bottom of the controller. Needle-nose pliers are needed to remove the jumpers. They should be set prior to installation. To insure proper operation, the jumpers must match the controller software configuration. Analog Output 1 and Analog Output 2 can be configured for voltage (V) or current (I), independent of each other. Both V/I + and V/I - jumpers of the same channel must be set for the same type of output signal. Analog Output 2 Jumpers (current) Analog Output 1 Jumpers (current) I2V2+ I2V2+ I1V1+ I1V1+ Analog Output 2 Jumpers Analog Output 1 Jumpers INPUTS Channel A and Channel B can be configured independent of each other. Jumper position can be ignored for thermocouple and millivolt inputs. Channel A Input Jumpers (RTD) Channel B Input Jumpers M2802X 4 X1 28 X6 4 X3 2 X1 6 X8 X4 X2 X1 SWB: ADDRESS SWB: ADDRESS X1 28 X6 4 X3 2 X1 6 X8 X4 X2 X1 SWA SWA The DLC Serial Communications Settings can be set via DIP Switches or through the serial communications port (software selectable). The software selectable serial settings method using the serial communications port must be set using “RLCPRO” or another software program to write to the DLC Modbus registers (40401-40407). When using the DIP switches to configure the serial settings, the Modbus mode is limited to “RTU” mode only. M2802X SERIAL DIP SWITCH SETTINGS DEFAULT PARITY BAUD RATE DEFAULT PARITY BAUD RATE (As set from factory) 10V 20mA RTD Channel A Input 10V 20mA RTD Channel B Input SWA DEFAULT SERIAL SETTINGS SWITCH POSITION BAUD RATE 1 Use DIP Switch or Software Serial Settings DN Use Default Serial Settings UP PARITY SWB 3 None DN DN None DN UP Even UP DN Odd UP UP 4 5 6 300 DN DN DN 600 DN DN UP 1200 DN UP DN 2400 DN UP UP 4800 UP DN DN 9600 UP DN UP 19200 UP UP DN 38400 UP UP UP UNIT ADDRESS Software Selectable Serial Settings 1 1 (128) 2 (64) 3 (32) 4 (16) 5 (8) 6 (4) 7 (2) 8 (1) DN DN DN DN DN DN DN DN DN DN DN DN DN DN DN UP 2 DN DN DN DN DN DN UP DN 3 DN DN DN DN DN DN UP UP 4 DN DN DN DN DN UP DN DN 5 DN DN DN DN DN UP DN UP 6 DN DN DN DN DN UP UP DN Serial Communication Defaults: 7 DN DN DN DN DN UP UP UP Protocol: RTU Address: 247 Baud Rate:9600 8 DN DN DN DN UP DN DN DN UP UP UP UP DN UP UP UP SWITCH POSITION 2 SWITCH POSITION / (BIT WEIGHT) SWITCH POSITION Stop Bit: 1 Parity: none Start Bit 1 … 247* *- Unit will use address 247 for binary switch settings above 247 STEP 2 INSTALLING THE CONTROLLER INSTALLATION The controller is designed for attachment to standard DIN style top hat (T) profile mounting rails according to EN50022 -35 x 7.5 and -35 x 15. The controller should be installed in a location that does not exceed the maximum operating temperature and provides good air circulation. Placing the controller near devices that generate excessive heat should be avoided. T Rail Installation To install the DLC on a “T” style rail, angle the controller so that the top groove of the mounting recess is located over the lip of the top rail. Push the controller toward the rail until it snaps into place. To remove a controller from the rail, insert a screwdriver into the slot on the bottom of the controller, and pry upwards until it releases from the rail. STEP 3 IDENTIFYING THE LEDs - LED FUNCTIONALITY On power-up, all LEDs are turned on briefly in an alternating pattern to allow visual check of LED functionality. CONDITION PRIORITY PWR/COMM CH A OP CH A ALM AUTOTUNE CH B OP CH B ALM Power Applied Communicating OP1 On (Channel A) ** OP1 On (Channel B) ** AL1 On (Channel A) * AL1 On (Channel B) * AL2 On (Channel A) * AL2 On (Channel B) * OP2 On [Cool](Channel A) OP2 On [Cool](Channel B) Auto-Tune On (Channel A) Auto-Tune On (Channel B) Input Error (Channel A) Input Error (Channel B) Calibration Mode Checksum Error 1 1 4 4 4 4 4 4 5 5 3 3 3 3 2 1 On Flashing ------------------------------------------------------------------------------------- ------------On ------------------- ------------------------On ------Fast Flashing ------------------------------Slow Flashing ------On Slow Flashing ------------------------------------------------------------On Fast Flashing ------------On Slow Flashing ------------------On ------------------------------Fast Flashing ------------------Slow Flashing On Slow Flashing ------------------------------On ------Fast Flashing ------------------------------Slow Flashing On Slow Flashing ------Fast Flashing ------------------Slow Flashing ------On Slow Flashing * If AL1 & AL2 outputs are on at the same time, the ALM annunciator will alternate between On and Fast Flashing every ½ second. ** If OP1 and AL2/OP2 (configured for cool) outputs are on at the same time, the annunciator will only show the OP1 state. The OP2 state is only shown when OP1 is off. 5 STEP 4 WIRING THE CONTROLLER WIRING CONNECTIONS All conductors should meet voltage and current ratings for each terminal. Also, cabling should conform to appropriate standards of good installation, local codes and regulations. When wiring the controller, use the numbers on the label to identify the position number with the proper function. Strip the wire, leaving approximately 1/4" (6 mm) of bare wire exposed. Insert the wire into the terminal, and tighten the screw until the wire is clamped tightly. (Pull wire to verify tightness.) Each terminal can accept up to one #14 AWG (2.55 mm), two #18 AWG (1.02 mm), or four #20 AWG (0.61 mm) wires. 24 VAC POWER (AC) ~ (AC) TBA + 2 ~ DC- 1 2 For best results, the power should be relatively “clean” and within the specified limits. Drawing power from heavily loaded circuits or from circuits that also power loads that cycle on and off should be avoided. It is recommended that power supplied to the controller be protected by a fuse or circuit breaker. 18 to 36 VDC POWER 1 CONTROLLER POWER CONNECTIONS DC+ TBA INPUT CONNECTIONS INPUT COMMON TBB TBA TBB 3 6 TBB Vs +24VDC OUT (200 mA max) INPUT COMMON CH A = Terminals 4, 5 & 6 CH B = Terminals 1, 2 & 3 Comm TBA 3 6 Out 0-10V, 0-20mA RTD EXC. 2 5 3 6 2 5 LOAD TC+ OR RTD 1 4 +24VDC OUT (200 mA max) INPUT COMMON CH A = Terminals 4, 5 & 6 CH B = Terminals 1, 2 & 3 3 Wire Current or Voltage Signal Requiring DLC Excitation ** 0-10V, 0-20mA RTD EXC. 3 + DC- CH A = Terminals 4, 5 & 6 CH B = Terminals 1, 2 & 3 2 Wire Current Signal Requiring DLC Excitation ** - 1 4 TC- CH A = Terminals 4, 5 & 6 CH B = Terminals 1, 2 & 3 TC+ OR RTD TC+ OR RTD 1 4 1 4 TBB INPUT COMMON TC+ OR RTD 0-10V, 0-20mA RTD EXC. LOAD Sense TC+ DC+ 3 2 5 TC+ OR RTD 3 6 Sense 0-10V, 0-20mA RTD EXC. 2 5 3 6 0-10V, 0-20mA RTD EXC. 1 4 Exc./ Jumper Voltage or Current 2 5 Thermocouple and Millivolt RTD and Resistance * INPUT COMMON TBB CH A = Terminals 4, 5 & 6 CH B = Terminals 1, 2 & 3 * For two wire RTDs, install a copper sense lead of the same gauge and length as the RTD leads. Attach one end of the wire at the probe and the other end to input common terminal. Complete lead wire compensation is obtained. This is the preferred method. If a sense wire is not used, then use a jumper. A temperature offset error will exist. The error may be compensated by programming a temperature offset. ** +24 VDC OUT (Terminal 3) shares common with Ch A Inputs & All Control/Alarm Outputs. CONTROL AND ALARM OUTPUT CONNECTIONS CH A = Terminals 5, 6, & 7 CH B = Terminals 8, 9, & 10 + DC- / (AC) ต DC+ / (AC) CH A = Terminals 5, 6, & 7 CH B = Terminals 8, 9, & 10 6 AL1 OP1 OUTPUT COMMON +24VDC OUT 3 - 7 10 - AL2/OP2 6 9 Load +24VDC OUT ต TBA + Load - 5 8 + Load 4 OUTPUT COMMON + + 2 7 10 OP1 Combined External Power For Load and Controller ต DC- / (AC) 1 TBA 6 9 ต DC+ / (AC) - AL1 5 8 ต DC- / (AC) Load - AL2/OP2 4 +24VDC OUT (200 mA max) + Load - 3 OUTPUT COMMON + Load 2 OP1 + 1 7 10 6 9 5 8 + - AL1 4 Load - AL2/OP2 3 + Load - 2 + Load Separate External Power For Load and Controller + + 1 Load Power from DLC External Controller Power ต DC+ / (AC) TBA CH A = Terminals 5, 6, & 7 CH B = Terminals 8, 9, & 10 DEFAULT SERIAL SETTING CONNECTIONS ANALOG DC OUTPUT CONNECTIONS 8 10 Output 1 = Terminals 8 & 9 Output 2 = Terminals 10 & 11 TBB 7 9 11 + OUT + ANALOG OUTPUT 0-10V, 0(4)-20mA DEFAULT SERIAL SETTING 4 - Controller, Recorder If using software selectable serial settings and the serial settings are unknown or forgotten, they can be temporarily reset to the defaults by connecting the “Default Serial Setting” terminal 7 to “Output Common” terminal 4 with a jumper. TBB OUT - OUTPUT COMMON TBA Defaults: Note: Analog Outputs & RS485 are not internally isolated and must not share the same common (i.e., earth ground). Protocol: RTU Address: 247 Baud Rate: 9600 Data Bits: 8 Parity: none RS485 SERIAL CONNECTIONS There are two modular connectors located on the front for paralleling communications. The CBPRO007 programming cable converts the RS232 port of a PC to RS485 and is terminated with an RJ11 connector. The bi-directional capability of the CBPRO007 allows it to be used as a permanent interface cable as well as a programming cable. STEP 5 INSTALLING SFDLC (Software for DLC) After downloading RLCPro for DLC Series (http://www.redlion.net/ SFDLC) open the ZIP archive and then run dlc207.exe to install the software. STEP 6 PROGRAMMING - Getting Started You will be prompted to select the proper device, Run RLCPro by double-clicking the icon, or use the start menu. and then the model. Use the FILE pull-down menu to select a NEW file. 7 STEP 7 PROGRAMMING THE PID SETTINGS Note: The register numbers correspond to (Channel A/Channel B).Channel B PID control is not functional when the input is assigned as a Remote Setpoint. The Auto-Tune procedure of the controller sets the Proportional Band, Integral Time, Derivative Time, Digital Filter, Control Ouput Dampening Time, and Relative Gain (Heat/Cool) values appropriate to the characteristics of the process. Proportional Band (40007/40023): Proportional band, entered as percent of full input range, is the band from the setpoint where the controller adjusts the percent output power based on how close the process value is to the setpoint. For temperature inputs, the input range is fixed per the entered thermocouple or RTD type. For process inputs, the input range is the difference between the entered Process Low Scaling Value and the Process High Scaling Value. The proportional band should be set to obtain the best response to a process disturbance while minimizing overshoot. A proportional band of 0.0% forces the controller into On/Off Control with its characteristic cycling at setpoint. Integral Time (40008/40024): Integral time is defined as the time, in seconds, it takes the output power due to integral action alone to equal the output power due to proportional action alone during a constant process error. As long as the error exists, integral action repeats the proportional action each integral time. Integral action shifts the center point position of the proportional band to eliminate error in the steady state. The higher the integral time, the slower the response. The optimal integral time is best determined during PID Tuning. If time is set to zero, the previous Integral output power value is maintained. Offset Power can be used to provide Manual Reset. Integral Action can be disabled by writing a ‘1’ to the Disable Intergral Action register (40044/40052). Derivative Time (40009/40025): Derivative time, entered as seconds per repeat, is the time that the controller looks ahead at the ramping error to see what the proportional contribution will be and it matches that value every Derivative time. As long as the ramping error exists, the Derivative action is repeated by Proportional action every derivative time. Increasing the derivative time helps to stabilize the response, but too high of a derivative time, coupled with noisy signal processes, may cause the output to fluctuate too greatly, yielding poor control. Setting the time to zero disables Derivative Action. Control Mode (40041/40049): In Automatic Mode, the percentage of Output Power is automatically determined by PID or On/Off Control. In Manual Mode, the percentage of Output Power is entered manually. For more information, see Control Mode Explanations Section. Output Power (40005/40021): This parameter can only be changed by direct entry in Manual Mode. For more details on this parameter, see the Control Mode Explanations Section. Offset Power (Manual Reset) (40010/40026): If the Integral Time is set to zero (Automatic Reset is off), it may be necessary to modify the output power to eliminate errors in the steady state. The offset power is used to shift the proportional band to compensate for errors in the steady state. If Integral Action is later invoked, the controller will re-calculate the internal integral value to provide “bumpless” transfer. Auto-Tune Code (40013/40029): Prior to starting Auto-Tune, this code should be set to achieve the necessary dampening level under PID Control. When set to zero, it yields the fastest process response with possible overshoot. A setting of 2 yields the slowest response with the least amount of overshoot. If the Auto-Tune Code is changed, Auto-Tune needs to be reinitiated for the changes to affect the PID settings. Auto-tune is initiated by writing a ‘1’ to the Auto-Tune start register (40011/40027). The Auto-Tune phase will be shown in register (40012/40028). For more information, see PID Tuning Explanations Section. STEP 8 PROGRAMMING THE INPUT SETUP Input Type (40101/40201): Select the proper input type from the pull down menu. Make sure the input jumpers are set to match the input signal selection. Scale (40102/40202): Select either degrees Fahrenheit or Celsius. For mV, resistance, voltage or current types, this has no effect. If changed, check all temperature related values, as the DLC does not automatically convert these values. Resolution (40103/40203): For all temperature and ohms Input Types low (x1) resolution selects whole units of measure. In these same modes, high (x10) resolution selects tenth of units of measure. For mV mode, low selects tenths of mV and high selects hundredths of mV. If changed, be sure to check all parameters because the controller does not automatically convert related parameter values. For voltage or current types, this has no effect. Rounding (40104/40204): Rounding selections other than 1 cause the process value to round to the nearest rounding increment selected. (For example, rounding of 5 causes 122 to round to 120 and 123 to round to 125.) Rounding starts at the least significant digit of the process value. If the signal is inherently jittery, the process value may be rounded to a value higher than 1. If the range of the signal exceeds the required resolution (for example, 0-1000 psi, but only 10 psi resolution is required), a rounding increment of 10 will effectively make the reading more stable. Digital Filtering (40105/40205): The filter is an adaptive digital filter that discriminates between measurement noise and actual process changes. If the signal is varying too greatly due to measurement noise, increase the filter value. If the fastest controller response is needed, decrease the filter value. Span Correction (40106/40206): This value is the correction slope. A span of 1.0000 applies no correction. Span only applies to temperature sensor, millivolt, and ohms inputs. Offset Correction (40107/40207): This value offsets the temperature value by the entered amount. Offset only applies to temperature sensor, millivolt, and ohms inputs Channel B Assignment (40198): This is used to configure Channel B to operate as a Remote Setpoint to Channel A. Channel B PID control is not functional when the input is assigned as a Remote Setpoint. 8 Local/Remote Setpoint Transfer Mode (40199): When cycling from/to Local or Remote Setpoint (register 40046), the response of the controller can be programmed to act in a variety of ways. The table summarizes the responses for Setpoint transfer options. LOCAL/REMOTE SETPOINT TRANSFER MODE 0 - Normal LOCAL TO REMOTE REMOTE TO LOCAL Output may bump. Output may bump. 1 - Auto No output bump. Process error eliminated at rate of integral action. Ramping disabled during transfer. No output bump. Process error eliminated at rate of integral action. Ramping disabled during transfer. 2 - Track Output may bump. Local Setpoint (40002) assumes value of Remote Setpoint (tracks). No output bump. Note: In situations where an output bump may occur, the Setpoint ramp function can be used to reduce or eliminate bumping when switching Setpoint modes. The setpoint ramp feature ramps the setpoint from the old setpoint to the new Setpoint. Remote Setpoint Ratio Multiplier (40206): This value is used for channel B when it is assigned as a Remote Setpoint Input. The Ratio Multiplier applies to all input types (0-15). Remote Setpoint Bias Offset (40207): This value is used for channel B when it is assigned as a Remote Setpoint Input. Scaling Points (40111-40114/40211-40214): Low and high scaling points are necessary to scale the controller for process voltage and current inputs. Each scaling point has a coordinate pair of input and process value entries. The process value will be linear between and continue past the entries up to the limit of the input range. Reverse acting measurement can be accomplished by reversing the Input or Process entries, but not both. (Do not reverse the input wires to change the action.) To scale a 4-20 mA Input signal to provide process values of 0 to 100.00 (% in hundredths), the Input Low (40113/40213) and Input High (40114/40214) values would be 4000 and 20000 (0.001 mA resolution), and the Process Low (40111/40211) and Process High (40112/40212) values would be 0 and 10000. Process Decimal Point (Dec Pt) (40115/40215): The decimal point position is used to enable SFDLC display in desired engineering units for voltage and current Process values. It is not used internally by the DLC. STEP 9 PROGRAMMING THE SETPOINTS Setpoint (40002/40018): Enter the setpoint value. Deviation of Process Value (40001/40017) from setpoint value can be viewed in the Setpoint Deviation register (40006/40022). Low Limit (40108/40208); High Limit (40109/40209): The controller has programmable high and low setpoint limit values to restrict the setting range of the setpoint. Set the limits so that the setpoint value cannot be set outside the safe operating area of the process. Ramp Rate (40110/40210): The setpoint ramp rate can reduce sudden shock to the process and reduce overshoot on startup or after setpoint changes, by ramping the setpoint at a controlled rate. The ramp rate is 0.1° for input types 0-11, 0.1 Ω for input type 12, 0.01 for input type 13, and 0.1 unit for input types 14-15 per minute. Writing a ‘0’ disables setpoint ramping. The Disable Setpoint Ramping register (40042/40050) can also be used to disable ramping. The Setpoint Ramping In-Process register (40043/40051) will be a ‘1’ during setpoint ramping. While ramping is enabled, the Ramping Setpoint can be viewed in register (40045/40053). The Ramp Rate for CHB is not functional when it is assigned as a Remote Setpoint Input. Once the ramping setpoint reaches the target setpoint, the setpoint ramp rate disengages until the setpoint is changed again. If the ramp value is changed during ramping, the new ramp rate takes effect. If the setpoint is ramping prior to starting Auto-Tune, the ramping is suspended during Auto-Tune and then resumed afterward using the present Process value as a starting value. Deviation and band alarms are relative to the target setpoint, not the ramping setpoint. A slow process may not track the programmed setpoint rate. At power-up, the ramping setpoint is initialized to the starting process value. Remote/Local Setpoint Select (40046): Channel A setpoint mode can be switched between Local Setpoint operation and Remote Setpoint operation. The Channel B input must be assigned as a remote setpoint (register 40198). STEP 10 PROGRAMMING PROFILE SETUP (Optional) Profile Power Cycle Mode (40321/40421): Upon controller power-on several profile operating modes exist. Stop: If the Profile was running when powered down, upon power-up, "Stop" places the profile into the stop or off mode, regardless of the mode prior to the power-down. The active Setpoint is the setpoint of the last segment that ran before power-down. Abort: If the Profile status was running, paused, or in Error Delay when powered down, upon power-up, "Abort" will place the controller in manual mode at 0% Output Power. The Setpoint and Ramp Rate are the values they were prior to running the profile. If the Setpoint Controller was 'paused,' they will be set to the values that they were at power-down. Start: The Start power cycle mode causes the controller to automatically start the profile at Power-up. This will occur if the unit was in manual or automatic control mode. During maintenance or at other times when this action is not desired, the Profile Power Cycle mode should be changed appropriately. Resume: At Power-up, Resume causes the profile to continue from the point and phase when power was removed. If the unit was in ramp phase, the ramping setpoint will start ramping from the initial process value at power-up. Pause: Upon Power-up, the controller pauses and maintains control at the initial process value (on power-up), at the phase where the controller was powered down. The user can then determine how to proceed based on the process that is being controlled. 9 Profile Error Band Mode (Guaranteed Soak) (40322/40422): Profile conformity can be assured by using the profile Error Band Mode and Error Band parameter. If the process value deviates outside the error band value while a profile is running, the controller enters the delay mode. In the delay mode, the profile phase timer is held (delayed) until the process value is within the deviation error band value - the Error band hysteresis value. At this time, the profile continues running unless the process value again deviates. These actions assure that the actual process value conforms to the profile. Disable Error Band: Error band operation is disabled. Ramp Phase Only Error Band: The Profile Error Band only applies to the ramp phases of the running profile. Hold Phase Only Error Band: The Profile Error Band only applies to hold phases of the running profile. Ramp & Hold Phase Error Band: The Profile Error Band applies to both ramp and hold phases of the running profile. Profile Error Band (40323/40423): During a hold phase, the profile is paused when the process error is >= the Profile Error Band. The profile will remain paused until the process error (deviation) is within the Profile Error Band (Error Band-Error Band Hysteresis). Profile Error Band Hysteresis (40324/40424): Controls the process value at which the profile will come out of an error band delay. If in error band delay, the profile phase timer is held (delayed) until the process value is within the deviation error band value - the Error band hysteresis value. Profile End Segment (40325/40425): The Profile End Segment indicates the last segment (i.e., the number of segments to be used in a profile) that is to be ran in the profile before it stops or re-starts (dependent on Profile Cycle Count/Profile Cycle Count remaining). Profile Cycle Count (40326/40426): Once a profile is started, it runs the number of cycles programmed in this register and then automatically defaults to the Profile End Control Mode. If this parameter is changed while the profile is active, the new value (if less than 250) will not take effect until the profile is stopped and re-started. If the Profile Cycle Count is set to 250 (continuous profile cycling), the change will take affect immediately. Profile End Control Mode (40327/40427): This parameter sets the type of control action that will be used when the number of profile cycles as programmed in the Profile Cycle Count parameter has run to completion. Control Outputs Off : Control is turned off by putting the controller in manual mode at 0% Power. Control can be resumed by changing the Control Mode (40041/40049) to Automatic. Automatic: When configured for Automatic the controller will continue controlling at the last setpoint value. Setpoint Controller Setpoint Segment Registers 1-20 (40601-40620[ChA]/4070140720[ChB]): The setpoints for the profile are written in these registers. The values are limited by the Setpoint Lo and Setpoint Hi limits registers. Register (40601/40701) is the Setpoint for the 1st segment of the profile. Setpoint Controller Ramp Rate Segment Registers 1-20 (40621-40640[ChA]/4072140740[ChB]): The Ramp Rates for the profile are written in these registers. Register (40621/40721) is the Ramp Rate for the 1st segment of the profile. A ramp rate of 0 disables setpoint ramping. Setpoint Controller Hold Time Segment Registers 1-20 (40641-40660[ChA]/4074140760[ChB]): The Hold Times for the profile are written in these registers. Register (40641/40741) is the Hold Time for the 1st segment of the profile. Segment Hold times of 0 can be used to achieve a ramp with multiple slopes. STEP 11 MONITORING PROFILE OPERATION (Optional) Profile Operating Status/Mode (40065/40073) Stop/Off: The Stop/Off status indicates the profile is dormant or off. A profile can be stopped by setting this register to 0, by allowing a profile to run to completion, or by removing and re-applying power when the Power Cycle Mode is configured for stop. If the profile was terminated during a ramp phase, the unit will continue to ramp to the active setpoint. Abort: Abort is a command action that can be used quickly to stop the profile and turn off the control outputs. The controller is placed into manual mode at 0% output power. Following the abort command the Profile Operating Status will go to 0 (Stop/Off). Run/Start: The profile is in the run mode when it is executing. While running, the profile can be stopped (0), paused (3), or advanced to the next phase. A profile can be started and placed into the Run mode automatically when the controller is powered-up (see Profile Power Cycle Mode). If the profile was previously stopped, when it is placed in to the Run/Start mode (2), the controller will be put into automatic control (if it was in manual) and start the profile at the first segment. If the controller was in manual mode prior to starting the profile, the controller will start ramping from the current process value. If the profile was "paused," it will resume operation. The advancement of the profile can be viewed in the Profile Phase (40066/40074) and Profile Segment register (40067/40075). 10 Pause: Pause signifies that a profile is active but the time base (Profile Phase Timer) is paused. The pause mode can only be invoked by writing a 3 in the Profile Operating Status register. Pausing a profile during a ramp phase pauses the ramp and the controller maintains control at the ramping setpoint value (40045/40053) at the instant of the pause action. The use of pause, effectively lengthens the total run time of a profile. The unit will remain in pause mode until it is placed back in the run mode by writing a 2 (Run/Start) into the Profile Operating Status Register. Error Delay (Guaranteed Soak): The Error Delay Setting is used only as a status indication. It indicates that a profile is active but the phase timer or profile advancement has stopped. This is caused by automatic action of the controller when the process deviates more than a specified amount from the active profile segment. The Error Delay is similar to pause, except the error delay status can only be invoked automatically. See "Profile Error Band Mode (40322/40422)." Do not write a "4 - Error Delay," to the Profile Operating Status Register. Doing so will instead put the controller in pause mode (3). Profile Phase (40066/40074): When the profile is active, this register indicates whether the controller is in a ramp (0) or hold (1) phase. Profile Segment (40067/40075): Indicates the current active segment while the profile is running. A zero indicates that the profile is stopped or off. Profile Phase Timer (40068/40076): This register shows the remaining segment phase time in 10ths of minutes. The remaining phase time can be changed "on the fly" to accelerate or decelerate the phase time. The change in phase time will only affect the running profile and not the stored parameters. If the phase time is changed during the ramp phase, a new ramp rate will be calculated which will achieve the desired phase time. The Profile Phase Timer will stop while the unit is paused or during an error delay caused by Profile Error Band operation (guaranteed soak). Profile Cycle Count Remaining (40069/40077): Indicates the number of profile cycles that are yet to be run. If the Profile Cycle Count register (40326/40426) is set to 250, the Profile Cycle Count Remaining Register will run continuously, resetting to "250" when reaching "0". This register value can be changed, however, it will only affect the current run cycle. When the profile is stopped and re-started, the Profile Cycle Count Remaining Register will be reloaded based on the "Profile Cycle Count (40326/40426)" value. Advance Profile Phase (40070/40078): Writing a "1" to this register while the profile is running will cause the controller to advance immediately to the beginning of the next ramp or hold phase. Using the advance operation shortens the total run time of the profile. If the profile is "paused," the profile will advance but the profile will remain paused. The Profile can also be advanced while in the error delay mode. STEP 12 PROGRAMMING THE OUTPUTS Cycle Time (40116/40216): The cycle time, entered in seconds, is the combined time of an on and off cycle of a time proportioning control output OP1/OP2. With time proportional output, the percentage of control power is converted into output on time of the cycle time value. (If the controller calculates that 65% power is required and has a cycle time of 10 seconds, the output will be on for 6.5 seconds and off for 3.5 seconds.) For best control, a cycle time equal to one-tenth of the process time constant, or less, is recommended. When using the DC Analog output signal for control, a setting of zero will keep output OP1 off. The status of OP1 can be read through registers 40014/40030. Control Action (40117/40217): This determines the control action for the PID loop. Programmed for direct action (cooling), the DLC output power will increase if the Process value is above the Setpoint value. Programmed for reverse action (heating), the output power decreases when the Process Value is above the Setpoint Value. For heat and cool applications, this is typically set to reverse. This allows OP1 to be used for heating, and AL2/OP2 to be used for cooling. Power Low Limit (40118/40218); High Limit (40119/40219): These parameters may be used to limit controller power due to process disturbances or setpoint changes. Enter the safe output power limits for the process. If Alarm 2 is selected for cooling, the range is from -100 to +100%. At 0%, both OP1 and OP2 are off; at 100%, OP1 is on; and at -100%, OP2 is on. When the controller is in Manual Control Mode, these limits do not apply. Sensor Fail Power Preset (40120/40220): This parameter sets the power level for the control outputs in the event of a sensor failure or extreme overdriven/underdriven input. If Alarm 2 is not selected for cooling, the range is from 0% (OP1 output full off) to 100% (OP1 output full on). If AL2 is selected for cooling, the range is from -100 to +100%. At 0%, both OP1 and OP2 are off; at 100%, OP1 is on; and at -100%, OP2 is on. The alarm outputs are upscale drive with an open sensor, and downscale drive with a shorted sensor (RTD only), independent of this setting. Manual Control overrides the sensor fail preset. Dampening Time (40121/40221): The dampening time, entered as a time constant in seconds, dampens (filters) the calculated output power. Increasing the value increases the dampening effect. Generally, dampening times in the range of one-twentieth to one-fiftieth of the controller’s integral time (or process time constant) is effective. Dampening times longer than these may cause controller instability due to the added lag effect. On/Off Control Hysteresis (40122/40222): The controller can be placed in the On/Off Control Mode by setting the Proportional Band to 0.0%. The On/Off Control Hysteresis (balanced around the setpoint) eliminates output chatter. In heat/cool applications, the control hysteresis value affects both Output OP1 and Output OP2 control. It is suggested to set the hysteresis band to 2 (Factory Setting) prior to starting Auto-Tune. After AutoTune, the hysteresis band has no effect on PID Control. On/Off Control Hysteresis is illustrated in the the On/Off Control Mode section. 11 STEP 13 PROGRAMMING THE ALARMS Alarm 1 and 2: The controller is equipped with two alarms for each channel. The status of these alarms can be read through AL1 registers 40015/40031 and AL2 registers 40016/40032. Action (40131/40231), (40136/40236): Select the action for the alarms. See Alarm Action Figures for a visual explanation. Manual: In Manual mode, the alarms are forced on and off by writing ‘0’ or ‘1’ to the appropriate alarm output register. In this mode, the alarms will not respond to Alarm and Hysteresis Values. Absolute HI (balanced or unbalanced hysteresis): The alarm energizes when the Process Value exceeds the alarm. Absolute LO (balanced or unbalanced hysteresis): The alarm energizes when the Process Value falls below the alarm. Deviation HI, Deviation LO, Band Acting: In these actions, Alarm 1 and 2 value tracks the Setpoint value. Cooling (OP2): For heat/cool applications, select Cool for Alarm 2. The controller then utilizes the Alarm 2 output as the Cooling Output (OP2). If cooling is selected, the remaining Alarm 2 parameters are not available. ALARM ACTION FIGURES AL + ½Hys SP AL + Hys AL Hys Hys AL - ½Hys SP + (-AL) Hys AL ALARM STATE OFF ON ALARM STATE OFF ALARM STATE TRIGGER POINTS OFF OFF ON ON OFF ON TRIGGER POINTS TRIGGER POINTS Absolute High Acting (Balanced Hys) Deviation High Acting (AL< 0) Absolute Low Acting (Unbalanced Hys) SP + AL AL + ½Hys SP + AL AL Hys Hys SP Hys SP AL - ½Hys Hys SP - AL OFF ALARM STATE ON ALARM STATE OFF OFF TRIGGER POINTS ON OFF ALARM OFF STATE TRIGGER POINTS Absolute Low Acting (Balanced Hys) ON OFF Hys SP Hys SP - AL OFF OFF SP + AL Hys ALARM STATE ON Band Outside Acting SP AL - Hys OFF TRIGGER POINTS Deviation High Acting (AL > 0) AL ON ALARM STATE TRIGGER POINTS Absolute High Acting (Unbalanced Hys) SP - AL Hys OFF ON TRIGGER POINTS Deviation Low Acting (AL > 0) OFF ALARM STATE ON OFF ON OFF ON TRIGGER POINTS Band Inside Acting Note: Hys in the above figures refers to the Alarm Hysteresis. Value (40003/40019), (40004/40020): The alarm values are entered as process units or degrees. Hysteresis (40134/40234), (40139/40239): The Hysteresis Value is either added to or subtracted from the alarm value, depending on the alarm action selected. See the Alarm Action Figures for a visual explanation of how alarm actions are affected by the hysteresis. Trigger Points: Trigger points are the Process Values where the alarm state changes. Their values cannot be entered directly, but are shown as a reference in the SFDLC software. The alarm value, hysteresis value, and setpoint alarm type determine the trigger points. With Deviation or Band actions, the alarm value and setpoint value are combined to determine the trigger points. Trigger points must not be greater than +32000 or less than -32000. If these limits are exceeded, the alarm may not function properly. Reset (40132/40232), (40137/40237): The alarms can be programmed for Automatic or Latched. In Automatic mode, an energized alarm turns off automatically once the Process Value leaves the alarm region. In Latched mode, an energized alarm requires a manual reset. This is done by writing ‘0’ to the appropriate output status register. After writing ‘0’, the Automatic or Latched alarm will not turn on again until after the Process Value first returns to the alarm off region. Only alarms configured for Manual action can be energized by writing a ‘1’ to its’ alarm output status register. On Delay (40135/40235), (40140/40240): The time, in seconds, required for the Process Value to be in the alarm region before the alarm will activate. It is used to allow temporary or short excursions into the alarm region without tripping the alarm. Enable Standby Delay (40133/40233), (40138/40238): Standby prevents nuisance (typically low level) alarms after a power up or setpoint change. After powering up the controller or changing the setpoint, the process must leave the alarm region. Once this has occurred, the standby is disabled and the alarm responds normally until the next controller power up or setpoint change. 12 STEP 14 PROGRAMMING THE COOLING To enable Cooling in Heat/Cool applications, the Alarm 2 Action must first be set for Cooling. When set to cooling, the output no longer operates as an alarm but operates as an independent cooling output. The OP2 terminals are the same as AL2. Cooling output power ranges from -100% (full cooling) to 0% (no cooling, unless a heat/cool deadband overlap is used). The Power Limits in the Output category also limits the cooling power. Cycle Time (40141/40241): This cycle time functions like the OP1 Output Cycle Time but allows independent cycle time for cooling. A setting of zero will keep output OP2 off. The status of OP2 can be read through registers (40016/40032). Relative Gain (40142/40242): This defines the gain of the cooling relative to the heating. It is generally set to balance the effects of cooling to that of heating. This is illustrated in the Heat/Cool Relative Gain Figures. A value of 0.0 places the cooling output into On/Off Control. This may be done independent of the OP1 Output PID or On/Off Control Modes. Deadband (40143/40243): This defines the area in which both heating and cooling are active (negative value) or the deadband area between the bands (positive value). If a heat/cool overlap is specified, the percent output power is the sum of the heat power (OP1) and the cool power (OP2). If Relative Gain is zero, the cooling output operates in the On/Off Control Mode, with the Deadband value becoming the cooling output hysteresis (positive value only). This is illustrated in the On/Off Control Mode section. For most applications, set this parameter to 0.0 prior to starting Auto-Tune. After the completion of Auto-Tune, this parameter may be changed. HEAT/COOL RELATIVE GAIN FIGURES O1 +100% 2X PROPORTIONAL BAND O2 -100% O1 +100% % DEADBAND POSITIVE VALUE RELATIVE GAIN 2 1 .5 O2 -100% % OUTPUT POWER OUTPUT POWER HEAT TEMPERATURE COOL TEMPERATURE HEAT SETPOINT SETPOINT Heat/Cool Deadband = 0 RELATIVE GAIN = .5 COOL Heat/Cool Deadband > 0 DEADBAND NEGATIVE VALUE RELATIVE GAIN O1 +100% 2 1 .5 O2 -100% % OUTPUT POWER TEMPERATURE RELATIVE GAIN = .5 COOL HEAT SETPOINT Heat/Cool Deadband < 0 13 STEP 15 PROGRAMMING THE ANALOG OUTPUT (Optional) Note: The register numbers correspond to (Analog Output 1/Output 2). Assignment (40301/40309): This setting selects the value that the Analog Output will retransmit, or track. The Analog output can be assigned for the following: SELECTION DESCRIPTION Output Power A Transmits the Output Power demand of Channel A. Used if linear control is desired. Process Value A Retransmits Process Value Channel A Setpoint A Retransmits Setpoint Value Channel A Ramping Setpoint A Retransmits Ramping Setpoint Channel A Deviation A Retransmits Deviation (difference of Setpoint Value - Process Value) Channel A Direct Entry Value 1 Retransmits Direct Entry Value 1 (Manual Analog Control) Output Power B Transmits the Output Power demand of Channel B. Used if linear control is desired. Process Value B Retransmits Process Value Channel B Setpoint B Retransmits Setpoint Value Channel B Ramping Setpoint B Retransmits Ramping Setpoint Channel B Deviation B Retransmits Deviation (difference of Setpoint Value - Process Value) Channel B Direct Entry Value 2 Retransmits Direct Entry Value 2 (Manual Analog Control) Mode (40302/40310): Select the type of output and range. The Analog output jumpers must be set to match the output type and range selected. The Analog output can be calibrated to provide up to 5% of over range operation. Output Scaling Values: The Scaling Low value (40303/40311) corresponds to 0 V, 0 mA or 4 mA, depending on the range selected. The Scaling High value (40304/40312) corresponds to 10 V or 20 mA depending on the range selected. An inverse acting output can be achieved by reversing the Scaling Low and Scaling High points. Deadband (40305/40313): The output power change must be greater than the deadband value in order for the Analog output to update. This only applies when the Analog Output is assigned to Output Power. This setting can be used to reduce actuator activity. Update Time (40306/40314): To reduce excess valve actuator or pen recorder activity, the update time of the analog output can be set in seconds. A value of zero seconds results in an update time of 0.1 second. Direct Entry Value (40307/40315): If the analog output is programmed for Direct Entry, it retransmits this value. This value may be controlled by the host. Filter (40308-40316): Entering a 1 will apply averaging when the Update Time >=1. STEP 16 PROGRAMMING THE DLC COMMS PORT Note: If the software selectable communication settings are changed and then a download is performed, the controller will immediately respond to the new settings. Any further attempts to communicate to the controller must target the new address, with the new settings. MINIMUM TRANSMIT DELAY SERIAL SETTINGS BAUD RTU ASCII MODBUS Protocol (40405): RTU or ASCII Unit Address (40401): 1-247 38400 2 msec 2 msec Baud Rate (40402): 300 to 38400 19200 3 msec 2 msec Data Bits (40404): 7 or 8 9600 5 msec 2.3 msec Parity (40403): odd, even, or none Transmit Delay (40406): Programmable from 2-250 milliseconds. 4800 9 msec 4.6 msec The Transmit Delay is the time the DLC waits to respond to a serial 2400 17 msec 9.2 msec command, UNLESS the values in the table are larger. 1200 33 msec 18.4 msec Note: Changing the above parameters by writing to their registers directly will not update the DLC until Load Serial Settings register 600 65 msec 36.7 msec 40407 is a ‘1’. After a write, this register will return to ‘0’. 300 129 msec 73.4 msec DIP Switch Serial Settings: The DIP switches can be used to select the baud rate, parity, and unit address. When using the DIP switches to configure the serial settings, the Modbus communications mode will be RTU only. There is also a "Default Serial Settings" switch to quickly configure the DLC for use with the "RLCPRO" Programming Software. Software Selectable Serial Settings: Setting all of the DIP switches to the "off" position and having the "Default Serial Setting" terminal un-connected, enables Software Selectable Serial settings. When leaving the factory the Software Selectable serial settings are set to the Serial Communication Defaults. Software Selectable Serial Settings allows set-up of all serial settings including the choice of RTU or ACSII communications modes and the number of data bits. If the Software Selectable Serial Settings are changed, the load serial register must be used or power to the DLC must be removed and re-applied in order for the settings to take effect. The use of RLCPRO Programming software or another software program supporting Modbus protocol is required to write to the DLC serial settings registers (40401-40407). 14 Default Serial Settings: The DLC serial port can be temporarily set to the factory defaults by setting the Default serial communications DIP switch to the “up” position OR by placing a jumper from the “Default Serial Setting” terminal 7 (TBB) to Output common terminal 4 (TBA). Both of these have precedence over the DIP switch serial settings and the software selectable serial settings. Once the serial default DIP switch is set to the “off” position or the jumper is removed, the DLC serial settings will immediately change as programmed by the DIP switches or the software selectable serial settings if all of the DIP switches are in the “off” position. The Default Serial Settings are NOT loaded into the software selectable serial registers when the serial default setting switch/terminal is active, they must be explicitly changed. Serial Communication Defaults: 9600 baud, 1 start bit, no Parity, 1 stop bit, address 247, and RTU mode. Communications Diagnostics: The Communications Diagnostics function (MODBUS Function Code 08) can be used to troubleshoot systems that are experiencing communication errors. Press the Read button to retrieve the diagnostics information. The Commands Received and the Commands Processed values are automatically reset when the values are read, at each controller power-up, and when the Commands Received reaches 65536. Commands Received: The total number of messages received that started with the controller’s own address since the last reset or power up. Commands Processed: The number of “good” messages received. A “good” message is considered one that contained the correct unit address, parity, and checksum (CRC or LRC). STEP 17 PC PORT CONFIGURATION Go to the SETTINGS pull-down menu, and select PC PORT SETTINGS. The Communications Settings window allows you to set up the software properly to perform a download. Connection: Select the computer port (COMM 1-4) that the DLC is connected to. Note: The following settings must match the DLC. If you do not know or cannot recall the DLC settings, they can be temporarily set to factory defaults. Simply jumper the Default Serial Setting terminal 7 to Input Common terminal 4 or put the Default Serial Settings DIP switch in the “UP” position. The serial settings will default to RTU mode, 9600 baud, 8 data bits, no parity, with an address of 247. Protocol: RTU or ASCII Unit Address: 1-247 Baud Rate: 300, 600, 1200, 2400, 4800, 9600, 19200, 38400 Data Bits: 7 or 8 Parity: odd, even, or none Connect the DLC to the computer with the CBPRO007 interface cable (or any suitable RS232/RS485 converter). Apply power to the supply terminals of the DLC. RED LION CONTROLS MODEL DLC ALL FLASHING = CHECKSUM ERROR PWR/COMM. Note: The CBPRO007 download cable DOES NOT typically require power. In most cases it will derive its power from the PC. If communications can not be established, follow the troubleshooting guide. If it is determined that the converter requires power, attach a 12 VDC power supply to the VDC and common terminals of the cable. DLC CBPRO STEP 18 DOWNLOADING Go to the FILE pull-down menu, and select DOWNLOAD. The following screen prompts you to ensure that the proper file is downloaded to the correct controller. Click “OK” to continue. 15 CH A OP CH A ALM BOTH FLASHING = INPUT ERROR AUTOTUNE CH B OP CH B ALM RS485 MODBUS PROTOCOL BOTH FLASHING = INPUT ERROR STEP 19 SCRATCH PAD MEMORY The Scratch Pad category can be used to read or write to the Scratch Pad memory locations (4110141116). The Scratch Pad locations can be used to store user information. Data Format: Allows registers to be viewed in decimal or hexadecimal format. Upload: The Upload button causes SFDLC software to read the Scratch Pad registers from the controller. Download: The Download button causes SFDLC software to write to the Scratch Pad registers in the controller. Note: Downloading new values to the controller Scratch Pad locations overwrites the information that is currently stored in those registers. Defaults: For this category, there are no controller factory defaults. The defaults for this category are only SFDLC software basic default values. STEP 20 VIEW REGISTERS The View Registers category can be used as a method of diagnostics. Use the DLC Register Table as a reference of register assignments and data. First Register: This specifies the first register to be read in a block. # of Registers: This is the length of the block to be read. The controller supports block read and write commands up to 32 registers in length. The SFDLC software only allows 16 to be read in a block. Data Format: Allows registers to be viewed in decimal or hexadecimal format. Read: Clicking the Read button causes SFDLC software to read the selected registers from the controller. Write: Clicking the Write button causes SFDLC software to write the selected registers to the controller. Note: The Write button overwrites the existing register values, and may change the module setup and operation. Defaults: For this category, there are no controller factory defaults. By clicking Defaults, the present entries from the other SFDLC software category screens will be displayed. STEP 21 CALIBRATION The DLC is fully calibrated from the factory. Recalibration is recommended every two years. Each channel is calibrated separately. All calibration settings are stored in the non-volatile memory. Calibration may be performed by using SFDLC software or MODBUS commands. When using SFDLC for calibration, connect the signal or measuring source to the proper DLC terminals, verify the input or output jumper positions, select the type of calibration to be performed, and click the Calibrate button. Follow the calibration procedures in the software. Note: Allow the DLC to warm up for 30 minutes minimum and follow the manufacturer’s warm-up recommendations for the calibration source. INPUT CALIBRATION When calibrating the input, the millivolt calibration must be performed first. All other input types use the millivolt points. Each input range (non-thermocouple) also has its own internal references that are recalled when the range is selected. Non-used types need not be calibrated. Calibration Type: This specifies the type of calibration to be performed. Millivolt: Millivolt calibration requires a precision voltage source with an accuracy of 0.03% or better. It is used for thermocouple inputs and as a basis for all other input calibration types. RTD: RTD calibration requires a 0.1% (or better) precision 277.0 ohm resistor. Process Voltage: Process calibration requires a precision signal source with an accuracy of 0.03% (or better) that is capable of generating 10.00 V. Process Current: Process current calibration requires a precision signal source with an accuracy of 0.03% (or better) that is capable of generating 20.00 mA. Cold Junction: Cold Junction calibration requires a thermocouple of known accuracy of types T, E, J, K, C or N only and a calibrated external reference thermocouple probe. TC Type: This selects the type of TC that is being used to calibrate the cold junction. Scale: This selects the scale in which the Thermometer temperature is entered and the controller temperature is displayed. Thermometer: Enter the reference thermometer temperature here. DLC: This displays the DLC process temperature value after a cold junction calibration is completed to verify the accuracy. Calibrate: The Calibrate button initiates the calibration process after the appropriate settings are selected. 16 ANALOG OUTPUT CALIBRATION Calibration Type: This specifies the Analog Output point to be calibrated. Volts: Analog Output Voltage calibration requires a precision meter with an accuracy of 0.05% (or better) that is capable of measuring 10.00 V. mA: Analog Output Current calibration requires a precision meter with an accuracy of 0.05% (or better) that is capable of measuring 20.00 mA. Meter Value: After pressing the Calibrate button, this shows the value the DLC is outputting. Measure the actual output with an external meter and enter that value here. Press the Calibrate button again and follow the prompts. Calibrate: The Calibrate button initiates the calibration process after the appropriate settings are selected. APPLICATION POWER 18-36VDC/ 24VAC RED LION CONTROLS RED LION CONTROLS MODEL DLC MODEL DLC RS485 MODBUS PROTOCOL RS485 MODBUS PROTOCOL + ZONE 1 + ZONE 2 + ZONE 3 A plastic extrusion company was building a four-zone extruder, and wanted a centrally located, multi-zone interface. The interface needed to display the temperature and setpoint values, as well as the screw RPM and barrel pressure. The customer provided a speed proportional 0-10 Volt signal from a motor drive, and installed a 4-20 mA output pressure sensor in the extruder barrel. Each of the four heat/cool zones were equipped with a thermocouple. Three DLC-Dual Loop Controllers, with a G3 HMI, allowed the customer to build his own control system. Only three DLCs were required; two were needed to control the four temperature zones, and one was needed to monitor the two process signals. All three units were connected to the RS485 port of the G3 display. The customer created his own displays on the HMI, which allowed him to monitor and control the setpoints and alarms 4-20mA SIG. within the DLCs. The G3’s (FROM PRESSURE multi-protocol capability SENSOR) allowed it to tie the DLCs to his PLC, creating a true 0-10V SIG. centralized interface. (FROM MOTOR DRIVE) RED LION CONTROLS MODEL DLC RS485 MODBUS PROTOCOL + ZONE 4 FOUR-ZONE EXTRUDER HMI UNIT CONTROL MODE EXPLANATIONS MANUAL CONTROL MODE MODE TRANSFER In Manual Control Mode, the controller operates as an open loop system (does not use the setpoint and process feedback). The user enters a percentage of power through the Output Power register (40005/40021) to control the heat (reverse) or cool (direct) for Output OP1. When Alarm 2 is configured for Cooling (OP2), Manual operation provides 0 to 100% power to OP1 (heating) and -100 to 0% power to OP2 (Cooling). The Low and High Power limits are ignored when the controller is in Manual. For time proportional outputs, the output power is converted into output On time using the Cycle Time. For example, with a four second cycle time and 75% power, the output will be on (4 × 0.75) for three seconds and off for one second. For Analog Outputs (0-10 VDC or 0/4-20 mA), the percent output power is converted into a linear value according to the Percent Low and High scaling set for the analog output. For example, with 0 VDC (scaled 0.0%) to 10 VDC (scaled 100%) and 75% power, the analog output will be 7.5 VDC. When transferring the controller mode from or to Automatic, the controlling outputs remain constant, exercising true bumpless transfer. When transferring from Manual to Automatic, the power initially remains steady, but Integral Action corrects (if necessary) the closed loop power demand at a rate proportional to the Integral Time. The Control Mode can be changed through the Control Mode register (40041/40049). AUTOMATIC CONTROL MODE In Automatic Control Mode, the percentage of output power is automatically determined by PID or On/Off calculations based on the setpoint and process feedback. For this reason, PID Control and On/Off Control always imply Automatic Control Mode. 17 ON/OFF CONTROL ON/OFF CONTROL - HEAT/COOL OUTPUT FIGURES The controller operates in On/Off Control when the Proportional Band is set to 0.0%. In this control, the process will constantly oscillate around the setpoint value. The On/Off Control Hysteresis (balanced around the setpoint) can be used to eliminate output chatter. Output OP1 Control Action can be set to reverse for heating (output on when below the setpoint) or direct for cooling (output on when above the setpoint) applications. INPUT SP + 1/2 HYS SP HYS SP - 1/2 HYS ON/OFF CONTROL - REVERSE OR DIRECT ACTING FIGURES INPUT HEAT/COOL DEADBAND VALUE (db) = 0 REVERSE ACTING Output 1 (OP1) : OFF ON OFF Output 2 (OP2) : ON OFF ON SP+1/2 HYS SP INPUT SP-1/2 HYS Output 1 (OP1) : OFF INPUT ON SP + 1/2 (db) + 1/2 HYS SP + 1/2 (db) SP + 1/2 (db) - 1/2 HYS OFF DIRECT ACTING Output 1 (OP1) : SP-1/2 HYS Output 2 (OP2) : ON db SP - 1/2 (db) + 1/2 HYS SP - 1/2 (db) SP - 1/2 (db) - 1/2 HYS SP OFF HYS SP SP+1/2 HYS Output 1 (OP1) : HEAT/COOL DEADBAND VALUE (db) > 0 HYS OFF OFF OFF INPUT OFF ON ON HEAT/COOL DEADBAND VALUE (db) < 0 SP + 1/2 (db) + 1/2 HYS SP + 1/2 (db) SP + 1/2 (db) - 1/2 HYS For heat and cool systems, OP1 Control Action is set to reverse (heat) and the Alarm 2 Action is set to cooling (OP2). The Proportional Band is set to 0.0 and the Relative Gain in Cooling to 0.0. The Deadband in Cooling sets the amount of operational deadband or overlap between the outputs. The setpoint and the On/Off Control Hysteresis applies to both OP1 and OP2 outputs. The hysteresis is balanced in relationship to the setpoint and deadband value. OFF HYS db SP SP - 1/2 (db) + 1/2 HYS SP - 1/2 (db) SP - 1/2 (db) - 1/2 HYS Note: HYS in the On/Off Control Figures refers to the On/Off Control Hysteresis. HYS ON Output 1 (OP1) : Output 2 (OP2) : ON OFF OFF ON ON TYPICAL PID RESPONSE CURVE PID CONTROL P&I In PID Control, the controller processes the input and then calculates a control output power value by use of a modified Proportional Band, Integral Time, and Derivative Time control algorithm. The system is controlled with the new output power value to keep the process at the setpoint. The Control Action for PID Control can be set to reverse for heating (output on when below the setpoint) or direct for cooling (output on when above the setpoint) applications. For heat and cool systems, the heat (OP1) and cool (OP2) outputs can be used together in the PID Control. The PID parameters can be Auto-Tune or Manual Tune to the process. P&I&D INPUT SP P&D P only TIME REMOTE SETPOINT Channel B can operate as a Remote Setpoint Input to Channel A. Channel B PID control is not functional when the input is assigned as a Remote Setpoint. This mode of operation enables Cascade control (external), Ratio control, and Temperature Setpoint Slave control, among others. The Remote Setpoint value used internally by the controller is: Remote Setpoint = (Scaled CHB Input * Remote Setpoint Ratio Multiplier) + Remote Setpoint Bias Offset where Ratio Multiplier = 0.0001 to 3.2000 Bias Offset = -32000 to 32000 The Ratio Multiplier and Bias Offset parameters offer on-line scaling of the Remote Setpoint to adjust control ratios or biases among related processes. The Remote Setpoint is restricted to the setpoint low and high limit values for channel B. These parameters may be used to limit the range of the Remote Setpoint to a safe or more stable control range. For Remote Setpoint signal sources that change wildly or are too sensitive to process upsets, the CHA Setpoint Ramp Rate parameter (40110) can be used to ramp (rate limit) the Remote Setpoint reading. This can subsequently reduce the fluctuations of the secondary control loop. 18 PID TUNING EXPLANATIONS AUTO-TUNE AUTO-TUNE CODE FIGURE INPUT Auto-Tune is a user-initiated function where the controller automatically determines the Proportional Band, Integral Time, Derivative Time, Digital Filter, Control Ouput Dampening Time, and Relative Gain (Heat/Cool) values based upon the process characteristics. The Auto-Tune operation cycles the controlling output(s) at a control point three-quarters of the distance between the present process value and the setpoint. The nature of these oscillations determines the settings for the controller’s parameters. Prior to initiating Auto-Tune, it is important that the controller and system be first tested. (This can be accomplished in On/Off Control or Manual Control Mode.) If there is a wiring, system or controller problem, Auto-Tune may give incorrect tuning or may never finish. Auto-Tune may be initiated at start-up, from setpoint or at any other process point. However, insure normal process conditions (example: minimize unusual external load disturbances) as they will have an effect on the PID calculations. Auto-Tune cannot be initiated while running a profile. SP 2 TYPICAL RESPONSE CURVES WITH AUTO-TUNE CODES 0 TO 2. 1 0 TIME Start Auto-Tune 1. Enter the On/Off Control Hysteresis value. (For most applications, 10 is a suggested value.) 2. Enter the Deadband value, if using OP2. (For most applications, 0 is a suggested value.) 3. Enter the Setpoint value. (If Auto-Tune overshoot is unacceptable, then lower the value and restart.) 4. Enter the Auto-Tune Code. (See Figure for details) 5. Enter ‘1’ in the Auto-Tune Start register . (Channel A 40011/Channel B 40027). 6. The Auto-Tune LED will come on. SETPOINT AUTO-TUNE CONTROL POINT Auto-Tune Progress ½ HYS * ½ HYS * AUTO-TUNE COMPLETE, PID SETTINGS ARE CALCULATED AND LOADED INTO MEMORY AUTO-TUNE START The controller will oscillate the controlling output(s) for four cycles. The cycling phase can be monitored from the Auto-Tune Phase Register (Channel A 40012/ Channel B 40028). The time to complete the Auto-Tune cycles is process dependent. The controller should automatically stop Auto-Tune and store the calculated values when the four cycles are complete. If the controller remains in Auto-Tune unusually long, there may be a process problem. Auto-Tune may be stopped by entering ‘0’ in Auto-Tune Start Register (Channel A 40011/Channel B 40027). PID Adjustments AUTO-TUNE OPERATION (REVERSE ACTING) INPUT TIME PHASE Output 1 (OP1) : 1 2 3 4 ON OFF ON OFF * - On/Off Control Hysteresis starting value and allow the process sufficient time to stabilize before evaluating the effects of the new parameter settings. In some unusual cases, the Auto-Tune function may not yield acceptable control results or induced oscillations may cause system problems. In these applications, Manual Tuning is an alternative. In some applications, it may be necessary to fine tune the Auto-Tune calculated PID parameters. To do this, a chart recorder or data logging device is needed to provide a visual means of analyzing the process. Compare the actual process response to the PID response figures with a step change to the process. Make changes to the PID parameters in no more than 20% increments from the PROCESS RESPONSE EXTREMES OVERSHOOT AND OSCILLATIONS SLOW RESPONSE INPUT INPUT SP SP TIME TIME TO DAMPEN RESPONSE: - INCREASE PROPORTIONAL BAND. - INCREASE INTEGRAL TIME. - USE SETPOINT RAMPING. - USE OUTPUT POWER LIMITS. - RE-INVOKE AUTO-TUNE WITH A HIGHER AUTO-TUNE CODE. - INCREASE DERIVATIVE TIME. - CHECK CYCLE TIME. TO QUICKEN RESPONSE: - DECREASE PROPORTIONAL BAND. - DECREASE INTEGRAL TIME. - INCREASE OR DEFEAT SETPOINT RAMPING. - EXTEND OUTPUT POWER LIMITS. - RE-INVOKE AUTO-TUNE WITH A LOWER AUTO-TUNE CODE. - DECREASE DERIVATIVE TIME. 19 MANUAL TUNING Output Power (40005/40021) to drive the process value to the Setpoint value. Allow the process to stabilize after setting the Output Power. 6. Place the controller in Automatic Control Mode (40041/40049). If the process will not stabilize and starts to oscillate, set the Proportional Band two times higher and go back to Step 5. 7. If the process is stable, decrease Proportional Band setting by two times and change the setpoint value a small amount to excite the process. Continue with this step until the process oscillates in a continuous nature. 8. Fix the Proportional Band to three times the setting that caused the oscillation in Step 7. 9. Set the Integral Time to two times the period of the oscillation. 10. Set the Derivative Time to one-eighth (0.125) of the Integral Time. 11. Set the Output Dampening Time to one-fortieth (0.025) the period of the oscillation. A chart recorder or data logging device is necessary to measure the time between process cycles. This procedure is an alternative to the controller’s Auto-Tune function. It will not provide acceptable results if system problems exist. This procedure should be performed by directly accessing the controller’s registers. The register numbers correspond to (Channel A/Channel B). 1. Set the Proportional Band (40007/40023) to 10.0% for temperature inputs and 100.0% for process inputs. 2. Set both the Integral Time (40008/40024) and Derivative Time (40009/40025) to 0 seconds. 3. Set the Output Dampening Time (40121/40221) to 0 seconds. 4. Set the Output Cycle Time (40116/40216) to no higher than one-tenth of the process time constant (when applicable). 5. Place the controller in Manual Control Mode (40041/40049) and adjust the MODBUS INFORMATION The remaining sections of this bulletin list information for MODBUS conformity with DLC registers and coils data. MODBUS SUPPORTED FUNCTION CODES FC01: Read Coils FC16: Preset Multiple Registers 1. Valid coil addresses are 1-33. 2. All coils can be requested. 3. Block starting point can not exceed coil 33. 1. Valid write (preset) register addresses are are 40002-40005, 40007-40011, 40013, 40015-40016, 40018-40021, 40023-40027, 40029, 40031-40032, 40041-40042, 40044, 40046, 40049-40050, 40052-40053, 40065, 4006840070, 40073, 40076-40078, 40100-40122, 40131-40143, 40198-40222, 40231-40243, 40301-40316, 40321-40327, 40401-40407, 40421-40427, 40501-40505, 40601-40660, 40701-40760, 41101-41116. 2. No response is given with an attempt to write to more than 32 registers at a time. 3. Block starting point can not exceed the read and write boundaries. 4. If a multiple write includes read only registers, then only the write registers will change. 5. If the write value exceeds the register limit (see Register Table), then that register value changes to its high or low limit. FC05: Force Single Coil 1. Valid write (force) coil addresses are 1-4, 10-13, 15-16, 22-25, 27-33. 2. HEX <8001> is echoed back for a request to write to a read only coil, to indicate that the coil did not change. FC15: Force Multiple Coils 1. Valid write (force) coil addresses are 1-4, 10-13, 15-16, 22-25, 27-33. 2. Block starting point can not exceed coil 33. 3. If a multiple write includes read only coils, then only the write coils will change. FC03: Read Holding Registers 1. Valid register addresses are 40001-40032, 40041-40046, 40065-40070, 40073-40078, 40100-40122, 40131-40143, 40231-40243, 40301-40308, 40309-40316, 40321-40327, 40421-40427, 40501-40505, 40601-40660, 40701-40760, 41101-41116. 2. Up to 32 registers can be requested at one time. 3. Block starting point can not exceed the register boundaries. 4. HEX <8000> is returned in registers beyond the boundaries. 5. Holding registers are a mirror of Input registers. FC04: Read Input Registers 1. Valid register addresses are 30001-30032, 30041-30046, 30065-30070, 30073-30078, 30100-30122, 30131-30143, 30231-30243, 30301-30308, 30309-30316, 30321-30327, 30421-30427, 30501-30505, 30601-30660, 30701-30760, 31101-31116. 2. Up to 32 registers can be requested at one time. 3. Block starting point can not exceed register boundaries. 4. HEX <8000> is returned in registers beyond the boundaries. 5. Input registers are a mirror of Holding registers. 40049-40053, 40198-40222, 40401-40407, 41001-41010, 30049-30053, 30198-30222, 30401-30407, 31001-31010, FC08: Diagnostics FC06: Preset Single Register The following is sent upon FC08 request: Module Address, 08 (FC code), 04 (byte count), “Total Comms” count, “Total Good Comms” count, checksum of the string “Total Comms” is the total number of messages received that were addressed to the DLC. “Total Good Comms” is the total messages received by the DLC with good address, parity and checksum. Both counters are reset to 0 upon response to FC08, on power-up, and when Total Comms register rolls over. 1. Valid write (preset) register addresses are 40002-40005, 40007-40011, 40013, 40015-40016, 40018-40021, 40023-40027, 40029, 40031-40032, 4004140042, 40044, 40046, 40049-40050, 40052-40053, 40065, 40068-40070, 40073, 40076-40078, 40100-40122, 40131-40143, 40198-40222, 4023140243, 40301-40316, 40321-40327, 40401-40407, 40421-40427, 4050140505, 40601-40660, 40701-40760, 41101-41116. 2. HEX <8001> is echoed back that the register did not change during the request to write to a read only register. 3. If the write value exceeds the register limit (see Register Table), then that register value changes to its high or low limit. It is also returned in the response. FC17: Report Slave ID The following is sent upon FC17 request: Unit Address, 17 (FC code), RLC-DLCxx000 (model number), 0200 (for code version 2.00), 32 (number of read supported registers), 32 (number of writes supported registers), 16 (number of registers available for GUID/Scratch pad memory), checksum of the string. 20 SUPPORTED EXCEPTION CODES Cold Junction Calibration * 01: Illegal Function Cold Junction calibration requires a thermocouple of known accuracy of types T, E, J, K, C or N only and a calibrated external reference thermocouple probe. 1. Connect the thermocouple probe source to the proper DLC terminals. 2. Enter the connected thermocouple type into register 40101 (Ch A) or 40201 (Ch B). 3. Enter the scale (F or C) that matches the thermometer and the controller temperature, preferrably °C into register 40102 (Ch A) or 40202 (Ch B). 4. Enter 1 for high resolution into register 40103 (Ch A) or 40203 (Ch B). 5. Place an external reference thermometer probe at the end of the DLC probe. The two probes should be shielded from air movement and allowed sufficient time to equalize in temperature. (As an alternative, the DLC probe may be placed in a calibration bath of known temperature.) 6. To open calibration mode, enter 48 into register 40501. 7. To start CJ calibration, enter 10 (Ch A) or 110 (Ch B) into register 40501. 8. Read the Process Value register 40001 (Ch A) or 40017 (Ch B). 9. Subtract the external reference reading from the Process Value register reading. Adjust the results to tenths position, drop decimal point, and maintain the results sign. (If the difference is -2 degrees, then adjust to -2.0 and remove decimal point yielding a value of -20.) 10. Add the value from step 9 (maintain the sign) to the value existing in register 40502. 11. If necessary, continue to adjust the register 40502 value until the Process Value register 40001 (Ch A) or 40017 (Ch B) matches the external reference reading. 12. To exit CJ calibration, enter 11 (Ch A) or 111 (Ch B) into register 40501. 13. To save the calibration results and close calibration mode, enter 0 into register 40501. Issued whenever the requested function is not implemented in the controller. 02: Illegal Data Address Issued whenever an attempt is made to access a single register or coil that does not exist (outside the implemented space) or to access a block of registers or coils that falls completely outside the implemented space. 03: Illegal Data Value Issued when an attempt is made to read or write more registers or coils than the controller can handle in one request. 07: Negative Acknowledge Issued when a write to coil or register is attempted with an invalid string length. CHECKSUM ERRORS 1. Calibration checksum covers the area that contains calibration values for all ranges. When a calibration checksum error occurs, coil 1 becomes a “1”. 2. Parameter checksum covers the area that contains the stored Holding register settings. When this checksum error occurs, coil 2 becomes a “1”. 3. Integral and Offset/Manual Power checksum covers the area that contains the stored Integral register settings. When this checksum error occurs, coil 3 becomes a “1”. 4. Setpoint Controller Segment Memory checksum covers the memory area that contains the profile segments for channel A and B. When this checksum error occurs, coil 29 becomes a "1". 5. Setpoint Controller Status Memory checksum covers the memory area that contains the profile operating status. When this checksum error occurs, coil 30 becomes a "1" and aborts the profile putting channel in manual control at 0% power. 6. All LEDs except PWR/COMMS will flash as long as one of the errors exist. 7. The control and alarm outputs are disabled as long as one of the errors exist. 8. These errors can be cleared or activated manually by writing to the appropriate coil. (This does not correct the reason for the error. It may be necessary to reconfigure or calibrate.) 9. The checksums are verified at power up. RTD Calibration * RTD calibration requires a 0.1% (or better) precision 277.0 ohm resistor. 1. Connect a precision 277.0 ohm resistor, and a short, to terminals 1 & 2 (Ch B) or 4 & 5 (Ch A). During the complete procedure, short terminals 2 & 3 (Ch B) or 5 & 6 (Ch A). 2. Verify the input jumper is in the RTD position. 3. Enter 12 (ohms mode) into register 40101 (Ch A) or 40201 (Ch B). 4. To open calibration mode, enter 48 into register 40501. 5. To start RTD calibration, enter 20 (Ch A) or 120 (Ch B) into register 40501. 6. Leave 0 ohms (short) on terminals 1 & 2 (Ch B) or 4 & 5 (Ch A) for 10 seconds. 7. To store 0 ohm results, enter 21 (Ch A) or 121 (Ch B) into register 40501. 8. Apply 277 ohms by removing the short from terminal 1 & 2 (Ch B) or 4 & 5 (Ch A) for 10 seconds. 9. To store 277 ohm results, enter 22 (Ch A) or 122 (Ch B) into register 40501. 10. To save the calibration results and close calibration mode, enter 0 into register 40501. CALIBRATION USING MODBUS COMMANDS The DLC is fully calibrated from the factory. Recalibration is recommended every two years. Each channel is calibrated separately. All calibration settings are stored in the non-volatile memory. The DLC may be calibrated using MODBUS. However, the preferred method of calibrating the controller is through the SFDLC software. When calibrating the input, a successful millivolt calibration must be performed first. All other input types use the millivolt points. Each input range (non-thermocouple) also has its own internal references that are recalled when the range is selected. Non-used types need not be calibrated. Each of the procedures below show the calibration steps/register numbers for both channels A & B, however, only one channel can be calibrated at a time. Note: Allow the DLC to warm up for 30 minutes minimum and follow the manufacturer’s warm-up recommendations for the calibration or measuring source. Process Voltage Calibration * Process calibration requires a precision signal source with an accuracy of 0.03% (or better) that is capable of generating 10.00 V. 1. Connect the signal source to the proper DLC terminals. 2. Verify the input jumper is in the 10 V position. 3. Enter 14 (for voltage input) into register 40101 (Ch A) or 40201 (Ch B). 4. To open calibration mode, enter 48 into register 40501. 5. To start voltage calibration, enter 12 (Ch A) or 112 (Ch B) into register 40501. 6. Apply 0.00 V for a minimum of 10 seconds. 7. To store 0.00 V reading, enter 13 (Ch A) or 113 (Ch B) into register 40501. 8. Apply 10.00 V for a minimum of 10 seconds. 9. To store 10.00 V reading, enter 14 (Ch A) or 114 (Ch B) into register 40501. 10. To save the calibration results and close calibration mode, enter 0 into register 40501. mV Calibration Millivolt calibration requires a precision signal source with an accuracy of 0.03% (or better) that is capable of generating the range to be calibrated. It is used for thermocouple inputs and as a basis for all other input calibration types. 1. Connect the signal source to the proper DLC terminals. 2. Enter 13 (for mV input) into register 40101 (Ch A) or 40201 (Ch B). 3. To open calibration mode, enter 48 into register 40501. 4. To start mV calibration, enter 1 (Ch A) or 101 (Ch B) into register 40501. 5. Apply the appropriate calibration voltage for a minimum of 10 seconds. 6. To store the mV calibration reading, enter the corresponding range number into register 40501: RANGE Ch A Ch B 0 mV 14 mV 28 mV 42 mV 56 mV 2 3 4 5 6 102 103 104 105 106 7. Repeat steps 5 and 6 for each range to be calibrated for that channel. 8. To save the calibration results and end calibration, enter 0 into register 40501. * - Dependent on successful mV calibration. 21 Process Current Calibration * Restore Factory Settings Process current calibration requires a precision signal source with an accuracy of 0.03% (or better) that is capable of generating 20.00 mA. 1. Connect the signal source to the proper DLC terminals. 2. Verify the input jumper is in the 20 mA position. 3. Enter 15 (for current input) into register 40101 (Ch A) or 40201 (Ch B). 4. To open calibration mode, enter 48 into register 40501. 5. To start current calibration, enter 15 (Ch A) or 115 (Ch B) into register 40501. 6. Apply 0.00 mA for a minimum of 10 seconds. 7. To store 0.00 mA reading, enter 16 (Ch A) or 116 (Ch B) into register 40501. 8. Apply 20.00 mA for a minimum of 10 seconds. 9. To store 20.00 mA reading, enter 17 (Ch A) or 117 (Ch B) into register 40501. 10. To save the calibration results and close calibration mode, enter 0 into register 40501. The Factory Settings are listed in the DLC Register Table. This restore does not affect the calibration or communication settings of the DLC but may change all other settings for the channel. 1. To open calibration mode, enter 48 into register 40501. 2. To restore Factory Settings, enter 66 (Input Ch A and Analog Out 1) or 166 (Input Ch B and Analog Out 2) into register 40501. 3. To save the restore results and close calibration mode, enter 0 into register 40501. Clear Setpoint Controller Segment Memory 1. To open calibration mode, enter 48 into register 40501. 2. To clear Setpoint Controller Segment memory, enter 67 (CHA Segment memory) or 167 (CHB Segment Memory) into register 40501. 3. To save the Clear results and close calibration mode, enter 0 into register 40501. Analog Output Voltage Calibration Analog Output Voltage calibration requires a precision meter with an accuracy of 0.05% (or better) that is capable of measuring 10.00 V. Nominal Calibration Settings Nominal Calibration Settings does not require any calibration signals nor meters. This calibration should not be performed under normal circumstances. Caution: This procedure results in up to ±10% reading error and the DLC will no longer be within factory specifications. 1. Connect the meter to the proper DLC terminals. 2. Verify the output jumpers are in the V positions. 3. To open calibration mode, enter 48 into register 40501. 4. To start 0 volt calibration, enter 30 (Out 1) or 130 (Out 2) into register 40501. 5. Adjust register 40502 value until the external meter displays 0.00 V. 6. To start 10 volt calibration, enter 31 (Out 1) or 131 (Out 2) into register 40501. 7. Adjust register 40502 value until the external meter displays 10.00 V. 8. To save the calibration results and close calibration mode, enter 0 into register 40501. 1. To open calibration mode, enter 48 into register 40501. 2. To enter Nominal Calibration Settings, enter 77 (Input Ch A and Analog Out 1) or 177 (Input Ch B and Analog Out 2) into register 40501. 3. To save the Nominal Calibration Settings and close calibration mode, enter 0 into register 40501. Analog Output Current Calibration Analog Output Current calibration requires a precision meter with an accuracy of 0.05% (or better) that is capable of measuring 20.00 mA. 1. Connect the meter to the proper DLC terminals 2. Verify the output jumpers are in the I position. 3. To open calibration mode, enter 48 into register 40501. 4. To start 0 mA calibration, enter 32 (Out 1) or 132 (Out 2) into register 40501. 5. Adjust register 40502 value until the external meter displays 0.00 mA. 6. To start 20 mA calibration, enter 33 (Out 1) or 133 (Out 2) into register 40501. 7. Adjust register 40502 value until the external meter displays 20.00 mA. 8. To save the calibration results and close calibration mode, enter 0 into register 40501. * - Dependent on successful mV calibration. 22 DLC REGISTER TABLE The below limits are shown as Integers or HEX < > values. Read and write functions can be performed in either Integers or Hex as long as the conversion was done correctly. Negative numbers are represented by two’s complement. Note 1: The DLC should not be powered down while parameters are being changed. Doing so may corrupt the non-volatile memory resulting in checksum errors. REGISTER ADDRESS 1 REGISTER NAME LOW LIMIT 2 HIGH LIMIT 2 FACTORY SETTING 3 ACCESS COMMENTS CH A CH B CONTROLLING VALUES 40001 40017 Process Value N/A N/A N/A Read Only Process value of present input level. This value is affected by Input Type, Resolution, & Scaling. In Square Root Extraction Modes, the Process Value will read zero for inputs below 0.1% of full scale. 40002 40018 Setpoint Value -32000 32000 0 Read/Write Limited by Setpoint Limit Low and Setpoint Limit High. 40003 40019 Alarm 1 Value -32000 32000 0 Read/Write 40004 40020 Alarm 2 Value -32000 32000 0 Read/Write 0 or -1000 1000 0 Read/Write 1 = 0.1%, 0.0 = Off; Limited by Power Low Limit and Power High Limit in Automatic Control Mode. Negative percent is cooling (direct) available when AL2 is Cooling. Write only possible during Manual mode. N/A Read Only Deviation = Process Value - Setpoint Value; During Auto-Tune: Process Value - Auto-Tune Setpoint Value PID PARAMETERS 40005 40021 Output Power 40006 40022 Setpoint Deviation N/A N/A 40007 40023 Proportional Band 0 9999 40 Read/Write 0 = On/Off Control, 1 = 0.1% 40008 40024 Integral Time 0 9999 120 Read/Write 0 = Off, 1= 1 second 40009 40025 Derivative Time 0 9999 30 Read/Write 0 = Off, 1= 1 second 40010 40026 Offset Power -1000 1000 0 Read/Write 1 = 0.1%; Applied when Integral Time is 0. 40011 40027 Auto-Tune Start 0 1 0 Read/Write 0 = Stop, 1 = Start; Mirror of Coil 16/28. 40012 40028 Auto-Tune Phase N/A N/A N/A Read Only 0 = Off, 4 = Last phase during Auto-Tune 40013 40029 Auto-Tune Code 0 2 0 Read/Write 0 = Fastest response, 2 = Slowest response 0 = Off, 1 = On; Mirror of Coil 9/21. OUTPUT STATUS 40014 40030 Control Output OP1 N/A N/A N/A Read Only 40015 40031 Alarm Output AL1 0 1 0 Read/Write 40016 40032 Alarm Output AL2 / OP2 0 1 0 Read/Write 40041 40049 Control Mode 0 1 0 Read/Write 0 = Automatic, 1 = Manual; Mirror of Coil 12/24. 40042 40050 Disable Setpoint Ramping 0 1 0 Read/Write 0 = Enabled, 1 = Disabled; Mirror of Coil 13/25. 40043 40051 Setpoint Ramping In Process N/A N/A N/A Read Only 0 = No, 1 = Yes; Mirror of Coil 14/26. 40044 40052 Disable Integral Action 0 1 0 Read/Write 40045 40053 Ramping Setpoint Value N/A N/A N/A Read/Write 0 1 0 Read/Write 0 = Enabled, 1 = Disabled; Mirror of Coil 15/27 Actual Setpoint Value used for control (ramps when ramping enabled.) Limited by Setpoint Limit Low and Setpoint Limit High. 0 = Local Setpoint, 1= Remote Setpoint 0 = Off, 1 = On; A write of 1 is only possible when alarm is set for Manual. Mirror of Coil 10/22. 0 = Off, 1 = On; A write of 1 is only possible when alarm is set for Manual. Mirror of Coil 11/23. CONTROL STATUS 40046 Remote / Local Setpoint Select PROFILE OPERATION 40065 40073 Profile Operating Status 40066 40074 40067 40075 40068 40076 40069 40070 SETPOINT CONTROLLER MODEL ONLY Read/Write (0-3 only) 0 = Off; 1 = Abort; 2 = Run/Start, 3 = Pause, 4 = Error Delay (status only - writing a “4” will revert unit to mode “3” Pause) 0 = Ramp; 1 = Hold 0 3 0 Profile Phase N/A N/A N/A Read Only Profile Segment N/A N/A N/A Read Only Profile Phase Time Remaining 1 9999 N/A Read/Write 40077 Profile Cycle Count Remaining 1 250 0 Read/Write 40078 Advance Profile Phase 0 1 0 Read/Write 1 = Advances “running” Profile to next ramp or hold phase (0 = Stop, 1-20 = Current Segment) 1= 0.1 Minute; Can make temporary change on the fly Value Over-range = 32003 (may occur on extremely slow ramp; Ramp will function properly) 0-250; If Cycle Count (40326/40426) is 250 (Continuous operation), value will reset to 250 at 0. INPUT PARAMETERS 1 2 3 40198 Ch B Assignment 0 1 0 Read/Write 0 = PID, 1 = Remote Setpoint 40199 Local / Remote Setpoint Transfer Mode 0 2 0 Read/Write 0 = Normal (Output may bump) 1 = Auto (Output may bump) 2 = Track (Local Setpoint assumes value of Remote SP for Remote to Local Transfer) 40101 40201 Input Type 0 17 2 Read/Write See Input Listing 40102 40202 Temperature Scale 0 1 0 Read/Write 40103 40203 Resolution 0 1 0 Read/Write 0 = °F, 1 = °C, For Input Types 0-11. Input Types 0-12 0=Low (x1) whole input units, 1 = High (x10) tenth of input units, Input Type 13 0 = 0.1 mV, 1 = 0.01 mV, Input Types 14-15, N/A For Input Registers, replace the 4xxxx with a 3xxxx in the above register address. The 3xxxx are a mirror of the 4xxxx Holding Registers. An attempt to exceed a limit will set the register to its high or low limit value. See MODBUS Calibration for procedure on restoring Factory Settings. 23 DLC REGISTER TABLE Continued REGISTER ADDRESS 1 REGISTER NAME LOW LIMIT 2 HIGH LIMIT 2 FACTORY SETTING 3 ACCESS COMMENTS CH A CH B INPUT PARAMETERS 40104 40204 Rounding 1 100 1 Read/Write 40105 40205 Digital Input Filter 0 4 1 40106 40206 Span Correction / Remote Setpoint Ratio Multiplier 1 32000 10000 40107 40207 Offset Correction / Remote Setpoint Bias Offset -32000 32000 0 Read/Write 0 = Least, 4 = Highest 10000 = 1.0000 (applies no correction), 1 = 0.0001, For Read/Write Input Types 0-11. Applies to all inputs (0-15) for ChB when ChB is configured for Remote Setpoint (40198). For Input Types 0-13/ Applies to all inputs (0-15) for ChB Read/Write when ChB is configured for Remote Setpoint (40198). 40108 40208 Low Limit -32000 32000 0 Read/Write ChB value also applies to Remote Setpoint 40109 40209 High Limit -32000 32000 32000 Read/Write ChB value also applies to Remote Setpoint 40110 40210 Ramp Rate 0 32000 0 Read/Write Greater than 1 causes rounding starting at least significant digit. SETPOINT PARAMETERS 1 = 0.1° per minute for input types 0-11, 0.1 ohms for input type 12, 0.01 mV for input type 13, 0.1 process units for input types 14-15, 0 = off (ChB Ramp Rate is Nonfunctional in remote setpoint mode) SCALING POINTS PARAMETERS 40111 40211 Process Low -32000 32000 0 Read/Write For Input Types 14-15 40112 40212 Process High -32000 32000 1000 Read/Write For Input Types 14-15 40113 40213 Input Low -32000 32000 4000 Read/Write 1 = 0.001 V or 0.001 mA, For Input Types 14-15. 40114 40214 Input High -32000 32000 20000 Read/Write 1 = 0.001 V or 0.001 mA For Input Types 14-15. 40115 40215 Process Decimal Point 0 5 3 Read/Write Can be used by host to determine resolution of input. For Input Types 14-15. CH A CH B CONTROL (OP1) PARAMETERS 40116 40216 Cycle Time 0 2500 20 Read/Write 1 = 0.1 second 40117 40217 Control Action 0 1 0 Read/Write 0 = Reverse Acting, 1 = Direct Acting 40118 40218 Power Low Limit 0 or -100 100 0 Read/Write 40119 40219 Power High Limit 0 or -100 100 100 40120 40220 Sensor Failure Power Preset 0 or -100 100 0 40121 40221 Dampening Time 0 250 3 Read/Write 1 = 1 second 40122 40222 On/Off Control Hysteresis 1 250 2 Read/Write NON-FUNCTIONAL IN REMOTE SETPOINT MODE (SEE 40198) 1 = 1%; Negative percent is only available to OP2 when AL2 is set for Cooling. 1 = 1%; Negative percent is only available to OP2 when Read/Write AL2 is set for Cooling. 1 = 1%; Negative percent is only available to OP2 when Read/Write AL2 is set for Cooling. ALARM 1 (AL1) OUTPUT PARAMETERS 40131 40231 Action 0 8 3 Read/Write See Alarm Action Register Table. 40132 40232 Reset 0 1 0 Read/Write 0 = Automatic, 1 = Latched 40133 40233 Enable Standby Delay 0 1 0 Read/Write 0 = Disable, 1 = Enable 40134 40234 Hysteresis 1 250 1 Read/Write 40135 40235 On Delay 0 32000 0 Read/Write 1 = 1 second ALARM 2 (AL2) OUTPUT PARAMETERS 40136 40236 Action 0 9 3 Read/Write See Alarm Action Register Table. 40137 40237 Reset 0 1 0 Read/Write 0 = Automatic, 1 = Latched; Not for Cooling Action. 40138 40238 Enable Standby 0 1 0 Read/Write 0 = Disable, 1 = Enable; Not for Cooling Action. 40139 40239 Hysteresis 1 250 1 Read/Write Not for Cooling Action. 40140 40240 On Delay 0 32000 0 Read/Write 1 = 1 second; Not for Cooling Action. 0 2500 20 Read/Write 1 = 0.1 second; 0 = OP2 Off 0 100 10 Read/Write 1 = 0.1; 0 = On/Off Control -32000 32000 0 Read/Write COOLING (OP2) PARAMETERS 1 2 3 40141 40241 Cycle Time 40142 40242 Relative Gain 40143 40243 Deadband OUT 1 OUT 2 ANALOG OUTPUT PARAMETERS NON-FUNCTIONAL IN REMOTE SETPOINT MODE (SEE 40198) ANALOG MODEL ONLY 40301 40309 Assignment 0 11 0(Out 1) 6(Out 2) 40302 40310 Mode 1 3 3 Read/Write 1 = 0-10 V, 2 = 0-20 mA, 3 = 4-20 mA 40303 40311 Scaling Value Low -32000 32000 0 Read/Write Corresponds with 0 V, 0 mA or 4 mA output. 40304 40312 Scaling Value High -32000 32000 1000 40305 40313 Deadband 0 250 0 Read/Write 1 = 0.1%; Applies when Assignment is Output Power. 40306 40314 Update Time 0 250 0 Read/Write 0 = scan rate (10 updates/ sec) 1 = 1 second 40307 40315 Direct Entry Value -32000 32000 0 Read/Write Applies when Assignment is Direct Entry Value. 40308 40316 Filter 0 1 0 Read/Write 1 = Applies averaging when Update Time is >=1 Read/Write See Analog Output Assignment Register Table. Read/Write Corresponds with 10 V or 20 mA output. For Input Registers, replace the 4xxxx with a 3xxxx in the above register address. The 3xxxx are a mirror of the 4xxxx Holding Registers. An attempt to exceed a limit will set the register to its high or low limit value. See MODBUS Calibration for procedure on restoring Factory Settings. 24 DLC REGISTER TABLE Continued REGISTER ADDRESS 1 REGISTER NAME LOW LIMIT 2 HIGH LIMIT 2 FACTORY SETTING 3 ACCESS SETPOINT CONTROLLER PROFILE PARAMETERS COMMENTS CH A CH B SETPOINT CONTROLLER MODEL ONLY 40321 40421 Profile Power Cycle Mode 0 4 1 Read/Write 0 = Stop (control at current active SP); 1 = Abort (manual control, 0% power); 2 = Start; 3 = Resume; 4 = Pause 40322 40422 Profile Error Band Mode 0 3 0 Read/Write 0 = Disable Error Band, 1 = Error Band applies to Ramp Phase 2 = Error Band applies to Hold Phase 3 = Error Band applies to Both Ramp and Hold Phase 40323 40423 Profile Error Band 1 32000 10 Read/Write 1 = 1 process unit; During Hold phase, profile is paused when process error >= error band until process error (deviation) is within the Error band (Error Band - Error Band Hysteresis) 40324 40424 Profile Error Band Hysteresis 0 250 2 Read/Write 1 = 1 Process Unit 40325 40425 Profile End Segment 1 20 1 Read/Write Segment that ends the profile 40326 40426 Profile Cycle Count 1 250 1 Read/Write 1 - 249 = Number of times to run profile 250 = Run Profile continuously 40327 40427 Profile End Control Mode 0 1 0 Read/Write 0 = Manual Mode, 0% power; 1 = Automatic Control at last Setpoint SERIAL COMMUNICATION SETTINGS 40401 Unit (Node) Address 1 247 247 Read/Write Node serial DLC address. 40402 Baud Rate 0 7 5 Read/Write See Serial Baud Rate Register Table. 40403 Parity 1 3 1 Read/Write 1 = None, 2 = Even, 3 = Odd 40404 Data Bits 0 1 1 Read/Write 0 = 7 bits, 1 = 8 bits 40405 MODBUS Protocol 0 1 1 Read/Write 0 = ASCII Mode, 1 = RTU Mode 40406 Transmit Delay 2 250 2 Read/Write 2 = 2 msec; See Transmit Delay explanation. 40407 Load Serial Settings 0 1 0 Read/Write Changing 40401-40406 will not update the DLC until 40407 is 1. After a write, the communicating device must be changed to the new DLC settings and 40407 returns to 0. CALIBRATION 40501 Unit Calibration N/A N/A N/A Read/Write See MODBUS Calibration explanation. 40502 Calibration Data Register N/A N/A N/A Read/Write See MODBUS Calibration explanation. 40503 Non-Volatile Memory Write Disable 0 1 0 Read/Write 0 = Enable writes, 1 = Disable writes; Returns to 0 at power cycle. Mirror of Coil 4. 40504 Input Error Status Register N/A N/A N/A Read Only Bits 0-7 are mirror of Coils 5-8/17-20, See Coils Table. 0 N/A 0 Read/Write Bits 0-3 are mirror of Coils 1-3, See Coils Table. 40505 1 2 3 Checksum Error Status Register CHA CHB SETPOINT CONTROLLER PROFILE SEGMENTS 40601 to 40620 40701 to 40720 Setpoint Value Segment 1 - 20 40621 to 40640 40721 to 40740 40641 to 40660 40741 to 40760 SETPOINT CONTROLLER MODEL ONLY -32000 32000 Read/Write Limited by Setpoint Limit Low and Setpoint Limit High. Ramp Rate Segment 1 - 20 0 32000 Read/Write 1 = 0.1° per minute for input types 0-11, 0.1 ohms for input type 12, 0.01 mV for input type 13, 0.1 process units for input types 14-15, 0 = Off Hold Time Segment 1 - 20 0 9999 Read/Write 1 = 0.1 minute 41001-41010 Slave ID N/A N/A N/A Read Only RLC-DLC1xx00 (model) 2.00 version (maybe higher) 32 reads, 32 writes 16 scratch. See FC17 explanation. 41101-41116 GUID/Scratch Pad N/A N/A N/A Read/Write This area is for the user to store any related information. This register area does not affect DLC operations. For Input Registers, replace the 4xxxx with a 3xxxx in the above register address. The 3xxxx are a mirror of the 4xxxx Holding Registers. An attempt to exceed a limit will set the register to its high or low limit value. See MODBUS Calibration for procedure on restoring Factory Settings. 25 COILS TABLE COIL ADDRESS COIL NAME MIRROR REGISTER ACCESS COMMENTS 1 Calibration Checksum Error 40505 (bit 0) Read/Write 1 = Error; Causes Process Value to be 32100, Disables control and alarm outputs, causes flashing LEDs. Writing a zero clears the error. 2 Parameter Checksum Error 40505 (bit 1) Read/Write 1 = Error; Causes Process Value to be 32100, Disables control and alarm outputs, causes flashing LEDs. Writing a zero clears the error. 3 Integral and Offset/Manual Power Checksum Error 40505 (bit 2) Read/Write 1 = Error; Causes Process Value to be 32100, Disables control and alarm outputs, causes flashing LEDs. Writing a zero clears the error. 4 Non-Volatile Memory Write Disable 40503 Read/Write 1 = Disables writes to the non-volatile memory; Returns to 0(writes are enabled) at power cycle. CH A CH B 5 17 Shorted RTD Input Error 40504 Read Only 1 = Shorted RTD; Causes process value to be -32002, disables alarms, sets control output(s) to sensor failure power preset level, causes flashing LEDs. 6 18 Open Thermocouple, RTD, or Extreme Process Input Over/ Under Range Input Error 40504 Read Only 1 = Input Error; Causes process value to be 32002, disables alarms, sets control output(s) to sensor failure power preset level, causes flashing LEDs. Signal or Sensor Under Range Input Error 40504 Read Only 1 = Under Range Error; Causes process value to be -32001, maintains control output at present level, causes flashing LEDs. Process Value (<-32000) Under Range Input Error 40504 1 = Under Range Error; Causes process value to be -32003, maintains control Read Only output at present level until input causes Sensor FailurePower Preset Level, causes flashing LEDs. Signal or Sensor Over Range Input Error 40504 Read Only 1 = Over Range Error; Causes process value to be 32001, maintains control output at present level, causes flashing LEDs. Process Value (>32000) Over Range Input Error 40504 7 19 8 20 9 21 Control Output OP1 State 40014/40030 1 = Over Range Error; Causes process value to be 32003, maintains control output Read Only at present level until input causes Sensor FailurePower Preset Level, causes flashing LEDs. Read Only 0 = Off, 1 = On 10 22 Alarm 1 Output AL1 State 40015/40031 Read/Write 0 = Off, 1 = On; A write of 1 is only possible when alarm is set for Manual. 11 23 Alarm 2 Output AL2/OP2 State 40016/40032 Read/Write 0 = Off, 1 = On; A write of 1 is only possible when alarm is set for Manual. 12 24 Control Mode 40041/40049 Read/Write 0 = Automatic Mode, 1 = Manual Mode 13 25 Disable Setpoint Ramping 40042/40050 Read/Write 0 = Enabled, 1 = Disabled 14 26 Setpoint Ramping In Process 40043/40051 Read Only 0 = No, 1 = Yes 15 27 Disable Integral Action 40044/40052 Read/Write 0 = Enabled, 1 = Disabled 16 28 Auto-Tune Start 40011/40027 Read/Write 0 = Stop, 1 = Start 40011/40027 SETPOINT CONTROLLER MODEL ONLY 29 Setpoint Controller Segment Memory Checksum Errror 40505 (bit 4) 30 Setpoint Controller Status Memory Checksum Error 40505 (bit 5) Advance Profile Phase 40070/40078 31 32 33 Local/Remote Setpoint Select 40046 1 = Checksum Error in A or B Setpoint Controller Segment memory (40601-40760), Read/Write causes process value to be 32100 disables control and alarm outputs, causes flashing LEDs. 1 = Checksum Error in A or B Setpoint Controller Operating Status memory, disables Read/Write control and alarm outputs, causes flashing LEDs, and aborts profile putting channel in manual control at 0% power. Read/Write 1 = Advance running Profile to next phase Read/Write 0 = Local Setpoint; 1 = Remote Setpoint ALARM 1 (40131/40231) AND ALARM 2 (40136/40236) ACTION REGISTER TABLE INPUT TYPE REGISTER (40101/40201) TABLE MODE 0 1 2 3 4 5 6 7 8 TYPE Thermocouple Thermocouple Thermocouple Thermocouple Thermocouple Thermocouple Thermocouple Thermocouple Thermocouple -T -E -J -K -R -S -B -N -C MODE TYPE 9 10 11 12 13 14 15 16 17 RTD platinum 385 RTD platinum 392 RTD nickel 672 Linear Ohms Linear mV (1 = 10mV) Process Voltage Process Current Process Voltage, Square Root Ext. Process Current, Square Root Ext. MODE ANALOG OUTPUT ASSIGNMENT REGISTER (400301/40309) TABLE MODE 0 1 2 3 4 5 6 7 8 9 10 11 ACTION 0 1 2 3 4 5 6 7 8 9 ASSIGNMENT Manual Absolute HI (Balanced) Absolute LO (Balanced) Absolute HI (Unbalanced) Absolute LO (Unbalanced) Deviation HI Deviation LO Band Inside Acting Band Outside Acting Cooling (Alarm 2 only) SERIAL BAUD RATE REGISTER (40402) TABLE Output Power A Process Value A Setpoint A Ramping Setpoint A Deviation A Direct Entry Value 1 Output Power B Process Value B Setpoint B Ramping Setpoint B Deviation B Direct Entry Value 2 MODE 0 1 2 3 4 5 6 7 26 BAUD 300 600 1200 2400 4800 9600 19200 38400 TROUBLESHOOTING PROBLEM CAUSE REMEDIES Power LED will not light Controller power Check controller power connections and voltage level Process Value not changing or incorrect Input signal Incorrect channel Incorrect programming Check input signal connections and signal level Check proper channel setup, reading and connections Check input setup, scaling values, and re-download Alarms not functioning properly Calculated trigger points are over +32000 or below -32000 Adjust alarm value, alarm hysteresis, and setpoint value to ensure valid trigger points Process Value stays at -32001 or +32001 Input Signal (sensor) under-range or over-range * Check input type, level, channel, jumpers and re-download. Replace sensor. Perform calibration. Process Value stays at -32002 Shorted RTD sensor * Check input sensor, level, channel, jumpers and re-download. Replace probe. Process Value stays at +32002 Open TC or RTD sensor * Check input sensor, level, channel, jumpers and re-download. Replace probe. Process Value stays at -32003 or +32003 Process Value underrange (<-32000) or overrange (>+32000) Check input level, scaling, jumpers and re-download Process Value stays at +32100, All LEDs Flashing, Alarms disabled Parameter checksum error † Calibration checksum error † Integral and Offset/Manual Power checksum error † Setpoint Controller Segment Memory checksum error † Will not communicate (Comm. LED not flashing) Setpoint Controller Status Memory checksum error † Re-download SFDLC file Perform calibration procedure Consult Factory Check A & B Setpoint Ramp Rate and Hold Time Segments. Change minimum of 1 segment register for each channel to cause a new checksum to be written Consult Factory Incorrect serial settings (DLC port) Incorrect serial settings (computer port) Incorrect wiring Verify DLC communications setup Go to pull down menu SETTINGS,PC PORT SETTING Try switching A+ and B- lines Note: The DLC serial settings must match the device that it is communicating with. If you do not know or cannot recall the DLC settings, they can be reset back to factory defaults. Simply jumper the Default Serial terminal to Input Common or by putting the Default Serial setting DIP switch in the “UP” position. * Can also be monitored by accessing coils 5-8 and 17-20, or register 40504. † Can also be monitored by accessing coils 1-3, 29-30 or register 40505. For further technical assistance, contact technical support. 27 LIMITED WARRANTY (a) Red Lion Controls Inc., Sixnet Inc., N-Tron Corporation, or Blue Tree Wireless Data, Inc. (the “Company”) warrants that all Products shall be free from defects in material and workmanship under normal use for the period of time provided in “Statement of Warranty Periods” (available at www.redlion.net) current at the time of shipment of the Products (the “Warranty Period”). EXCEPT FOR THE ABOVE-STATED WARRANTY, COMPANY MAKES NO WARRANTY WHATSOEVER WITH RESPECT TO THE PRODUCTS, INCLUDING ANY (A) WARRANTY OF MERCHANTABILITY; (B) WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE; OR (C) WARRANTY AGAINST INFRINGEMENT OF INTELLECTUAL PROPERTY RIGHTS OF A THIRD PARTY; WHETHER EXPRESS OR IMPLIED BY LAW, COURSE OF DEALING, COURSE OF PERFORMANCE, USAGE OF TRADE OR OTHERWISE. Customer shall be responsible for determining that a Product is suitable for Customer’s use and that such use complies with any applicable local, state or federal law. (b) The Company shall not be liable for a breach of the warranty set forth in paragraph (a) if (i) the defect is a result of Customer’s failure to store, install, commission or maintain the Product according to specifications; (ii) Customer alters or repairs such Product without the prior written consent of Company. (c) Subject to paragraph (b), with respect to any such Product during the Warranty Period, Company shall, in its sole discretion, either (i) repair or replace the Product; or (ii) credit or refund the price of Product provided that, if Company so requests, Customer shall, at Company’s expense, return such Product to Company. (d) THE REMEDIES SET FORTH IN PARAGRAPH (c) SHALL BE THE CUSTOMER’S SOLE AND EXCLUSIVE REMEDY AND COMPANY’S ENTIRE LIABILITY FOR ANY BREACH OF THE LIMITED WARRANTY SET FORTH IN PARAGRAPH (a). Red Lion Controls Headquarters 20 Willow Springs Circle York PA 17406 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 Red Lion Controls Europe Softwareweg 9 NL - 3821 BN Amersfoort Tel +31 (0) 334 723 225 Fax +31 (0) 334 893 793 Red Lion Controls India 201-B, 2nd Floor, Park Centra Opp 32 Mile Stone, Sector-30 Gurgaon-122002 Haryana, India Tel +91 984 487 0503 Red Lion Controls China Unit 1102, XinMao Plaza Building 9, No.99 Tianzhou Road ShangHai, P.R. China 200223 Tel +86 21 6113 3688 Fax +86 21 6113 3683